If the illustrated test is being performed to determine which winding is grounded and the light does not come on then __________. EL-0027 A. winding is grounded and you should continue on to the next winding to see if any others are grounded B. winding is not grounded and you should continue on to the next winding until the light comes on designating that winding as grounded C. test is meaningless because you can not determine if a winding is grounded without a megger. D. ground is not in the windings but probabily in the pecker head, you should check and retape the line lead connections

1 Answer

Answer :

Answer: B

Related questions

Description : In the illustrated test, if the lamp fails to light on any of the three windings then _________. EL-0027 A. all three windings are grounded and the motor should be sent out for repair B. ... the motor controller and the controller should be checked D. the test should be redone at a higher voltage

Last Answer : Answer: C

Description : When using the test set-up shown in the illustration, the lighted lamp indicates the winding is ____________. EL-0027 A. grounded B. good C. open D. shorted

Last Answer : Answer: A

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D

Description : The circuit illustrated represents a 2 wire DC ground detecting system. If the positive bus is grounded and the test button is pushed, which of the lamps will be brightest? EL-0008 A. X B. Y C. both will be equal brightness. D. both will go out.

Last Answer : Answer: C

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : When using a megohmmeter to determine which shunt field coil is grounded in a DC machine, you must ____________. A. insulate the field frame from the ship's hull B. disconnect each shunt ... C. use a motor driven high capacity megohmmeter D. remove all main line lead connections before testing

Last Answer : Answer: B

Description : To determine if a stator coil is grounded, you should use a/an _____________. A. ammeter B. ground detection lamp C. magneto D. megger

Last Answer : Answer: D

Description : You are testing the insulation in an AC generator with a megohmeter. The resistance value of a dry, clean winding will ____________. A. continue to rise as the test potential is maintained, ... fairly steady after 5 to 7 minutes D. stabilize after approximately 2 to 4 minutes of fluctuation

Last Answer : Answer: A

Description : The vertical dotted line connecting the small circular symbols at coordinates '05L', '09L', '13L', '21L', '25L', etc., shown in the illustration, indicate that all _______________. EL-0100 A. contacts are ... board 'TB2' C. wires are grounded at both ends of the line D. wires have a common shield

Last Answer : Answer: B

Description : In preparing to take insulation resistance readings on a main generator, the windings should be grounded for about 15 minutes prior to the test to _____________. A. allow accurate zeroing of the meter ... the windings D. help the windings to cool to the same temperature as the ground test connection

Last Answer : Answer: C

Description : As shown in the illustration, what maintenance would be required of the circuit components? EL-0058 A. Change out both 'C' units monthly. B. Clean the glass surrounding 'E1' & 'E2' as needed. C. File ... upper end of 'G' every six months. D. Take megger readings on 'E1' & 'E2' windings quarterly.

Last Answer : Answer: B

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : A generator has been exposed to water and is being checked for its safe operation. Therefore, it is necessary to _______________. A. check for shorted coils with a growler B. take moisture readings with a ... a megger D. ground the commutator, or slip rings and run it at half load for 12 hours

Last Answer : Answer: C

Description : If you obtain a low resistance reading with a megohmmeter connected between terminals 'A' and 'C' of the three-phase, wye-connected winding shown in the illustration, there is __________. EL-0074 A. no open circuit ... 'B' C. an open circuit between 'A' and 'C' D. an open circuit in both windings

Last Answer : Answer: A

Description : Which of the following statements is true regarding the illustrated circuit? El-0069 A. This full wave bridge should never be used aboard ship because the ground on lead 'A' will show on ... be direct current suitable for electronic circuits requiring voltage regulation. D. All the above are true.

Last Answer : Answer: B

Description : The reading at 'M' on the megger scale illustrated, is ____. EL-0044 A. 7.1 meg ohms B. 71 meg ohms C. .71 meg ohms D. 200,000,000 ohms

Last Answer : Answer: A

Description : The reading at 'C' on the megger scale illustrated, is ________. EL-0044 A. 200,000 ohms B. 2,000,000 ohms C. 20,000,000 ohms D. 200,000,000 ohms

Last Answer : Answer: C

Description : If all three ground-detection lamps continue to burn at equal intensity after the test button is depressed and released, which of the listed conditions is indicated? A. No grounds exist B. All three phases are grounded C. The test switch is faulty D. The current transformers are shorted out

Last Answer : Answer: A

Description : Which of the listed types of motor controllers and starters is illustrated? EL-0080 A. Across-the-line B. Primary-resistor C. Autotransformer D. Part-winding

Last Answer : Answer: C

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test, because the ___________. A. static charge of the machine ... number of leakage paths C. insulation may be damaged D. insulation may be covered with moisture

Last Answer : Answer: A

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : In the illustrated device, the part labeled '1A' _________. EL-0001 A. are start and run windings for a single phase shaded pole induction motor B. is the stator for a polyphase induction ... armature for a squirrel cage rotor motor D. are direct current shunt field windings for a universal motor

Last Answer : Answer: B

Description : Before servicing the device indicated as 'A' in panels #1 and #3 of the illustration, the device labeled 'CT' must __________. EL-0003 A. have the disconnected leads taped to prevent ... D. have one lead grounded to discharge static electricity for the prevention of damage to electronic components

Last Answer : Answer: C

Description : An open in the armature of a DC motor is suspected, but is not found by visual inspection of the commutator. The next step in troubleshooting this problem is to ________________. A. conduct a ... windings C. conduct an insulation resistance test of the armature D. test the commutator for a ground

Last Answer : Answer: A

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test as the ______________. A. insulation may be damaged ... number of leakage paths D. larger machines may acquire a charge of static electricity during operation

Last Answer : Answer: D

Description : If reading AC current with the illustrated device and unsure of the range as a precaution , the first step should be to _________. EL-0047 A. secure power and test for voltage B. disconnect the ... resistance and use Ohm's law to calculate current D. unable to safely measure current with the device

Last Answer : Answer: A

Description : The electrician reports to you that he has obtained low (but above 1 megohm) megger readings on the windings of a deck winch motor. Upon checking the records of that motor, you find the readings have ... yea A. motor be replaced B. windings be dried C. windings be cleaned D. readings are acceptable

Last Answer : Answer: D

Description : In the illustrated ground detection system with a ground on phase A, if the switch is opened __________. EL-0009 A. lamp A will dim or go out depending on the severity of the ground B. all three ... lamp A will be brighter D. lamp A will start flickering if the ground is in an AC induction motor

Last Answer : Answer: B

Description : As a general rule, the first troubleshooting action to be taken in checking faulty electric control devices is to _____________. A. draw a one line diagram of the circuitry B. test all fuses and measure the line voltage C. take megger readings D. insulate the apparatus from ground

Last Answer : Answer: B

Description : In the illustrated circuit, what is the phase relationship of the amplifier output compared to the input? EL-0022 A. 0° in-phase B. 180° out of phase C. phase angle of the input divided by power factor D. unable to determine without the value of the bias voltage

Last Answer : Answer: B

Description : The circuit illustrated represents a single phase AC ground detecting system. If a ground occurs on line 'B', which of the lamps will burn the brightest? EL-0008 A. X B. Y C. Both will be equal brightness. D. both will go out.

Last Answer : Answer: A

Description : When troubleshooting a console circuit card suspected of being faulty, first check operating voltages, clean the card and then _________________. A. make sure wired connections and push-on connectors ... circuit traces with an ohmmeter D. measure the gain of each transistor or integrated circuit

Last Answer : Answer: A

Description : If reading the AC voltage from the line lead of a 440 VAC controller the range switch illustrated should be set to ___________. EL-0047 A. 1,000 V B. 250 V C. R X 10,000 D. Unable to safely read with this meter.

Last Answer : Answer: A

Description : If the illustrated device is fully discharged, what will be the result? EL-0061 A. The battery will be short circuited because the mud space will be filled with lead sulfate B. The electrolyte ... minimum sulfuric acid. D. The plates will be maximum lead oxide and sponge lead minimum lead sulfate.

Last Answer : Answer: C

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : While starting a main propulsion synchronous motor, the ammeter pegs out at maximum and then returns to the proper value after synchronization. This indicates the _____________. A. motor has started ... field windings are grounded C. slip rings are dirty D. power transmission cables are grounded

Last Answer : Answer: A

Description : Which of the conditions listed will indicate the need to clean the insulation on the windings of an electric motor? A. Higher than normal operating temperature. B. Excessive vibration at normal speed. C. Sparking at the brushes. D. High megger readings.

Last Answer : Answer: A

Description : The reading at 'M' on the megger scale shown in the illustration, is __________. EL-0044 A. 7.1 meg ohms B. .71 meg ohms C. 71 meg ohms D. 200,000,000 ohms

Last Answer : Answer: A

Description : The reading at 'V' on the megger scale shown in the illustration, is __________. EL-0044 A. 40 meg ohms B. 0.40 meg ohms C. 4.0 kilo ohms D. 40,000 ohms

Last Answer : Answer: D

Description : The reading at 'P' on the megger scale shown in the illustration, is __________. EL-0044 A. 15 meg ohms B. 1.5 meg ohms C. 1.5 kilo ohms D. 150,000 ohms

Last Answer : Answer: B

Description : Which statement is true concerning a split-phase induction motor? A. Motor rotation can be reversed without changing the windings or leads. B. Motor speed can be readily adjusted from zero to full ... proper wiring. D. Motor rotation can be reversed by reversing the leads on the starting winding.

Last Answer : Answer: D