A megger is being used to test the insulation of an AC generator. The resistance value of a dry, clean winding will _____________.  A. continue to rise as test potential is maintained, becoming fairly steady as the dielectric-absorption effect of insulation stabilizes B. remain constant as the temperature of the windings increases C. continue to drop as test potential is maintained, becoming fairly steady after 5-7 minutes D. stabilize after approximately 2-4 minutes of fluctuation

1 Answer

Answer :

Answer: A

Related questions

Description : You are testing the insulation in an AC generator with a megohmeter. The resistance value of a dry, clean winding will ____________. A. continue to rise as the test potential is maintained, ... fairly steady after 5 to 7 minutes D. stabilize after approximately 2 to 4 minutes of fluctuation

Last Answer : Answer: A

Description : When a megohmmeter is used to test insulation, the gradual rise of the pointer reading as a result of continued cranking, is caused by _____________. A. good conductor resistance B. the ... insulation C. the inductive reactance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: D

Description : In preparing to take insulation resistance readings on a main generator, the windings should be grounded for about 15 minutes prior to the test to _____________. A. allow accurate zeroing of the meter ... the windings D. help the windings to cool to the same temperature as the ground test connection

Last Answer : Answer: C

Description : When a megohmmeter is used to test the insulation of a large motor, the initial dip of the pointer toward 'zero' is caused by ____________. A. good insulation B. the capacitance of the ... of the current along the surface of dirty insulation D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When using a megohmmeter to test the dielectric strength of wire insulation, a continuous series of slight downscale kicks by the pointer is result of ____________. A. good insulation B. the ... dirty insulation C. the capacitance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : Which of the conditions listed will indicate the need to clean the insulation on the windings of an electric motor? A. Higher than normal operating temperature. B. Excessive vibration at normal speed. C. Sparking at the brushes. D. High megger readings.

Last Answer : Answer: A

Description : When a megohmmeter is used to test the dielectric strength of wire insulation, the initial dip of the pointer toward 'zero' is caused by _____________. A. good insulation B. the leakage of ... of dirty insulation C. the capacitance of the circuit D. the dielectric absorption effect of the insulation

Last Answer : Answer: C

Description : The main purpose of an electric space heater installed in a large AC generator is to _____________. A. keep the lube oil warm for quick starting B. prevent moisture from condensing in the ... is shutdown C. prevent the windings from becoming brittle D. prevent acidic pitting of the slip rings

Last Answer : Answer: B

Description : The main purpose of an electric space heater installed in a large AC generator is to _____________. A. prevent the windings from becoming brittle B. prevent moisture from condensing in the windings during ... C. prevent acidic pitting of the slip rings D. keep the lube oil warm for quick starting

Last Answer : Answer: B

Description : The greatest detrimental effect on idle electrical equipment, such as cargo pump motors, is the _____________. A. loss of residual magnetism B. absorption of moisture in the insulation C. insulation varnish flaking D. dirt collecting on the windings

Last Answer : Answer: B

Description : Routine maintenance of dry-type transformers should include ____________. A. cleaning the windings, if accessible, with a vacuum cleaner or very low pressure air B. measuring and recording the winding ... . making sure that the units are close to bulkheads or corners to protect them from damage

Last Answer : Answer: A

Description : Motor name plate data includes '°°C rise'. This indicates the _____________. A. actual running temperature of the winding from no load to full load B. permissible temperature rise ... above normal full load operating temperature D. maximum allowable temperature rise for continuous no load service

Last Answer : Answer: B

Description : When troubleshooting motor controllers, a shorted relay or contactor coil is often indicated by _______________. A. a resistance reading of 'infinity' on an ohmmeter B. charred insulation and/or a blown ... of the coil's leads to ground D. a higher-than-normal voltage reading across the winding

Last Answer : Answer: B

Description : A generator has been exposed to water and is being checked for its safe operation. Therefore, it is necessary to _______________. A. check for shorted coils with a growler B. take moisture readings with a ... a megger D. ground the commutator, or slip rings and run it at half load for 12 hours

Last Answer : Answer: C

Description : Which of the listed conditions could indicate the need for cleaning electrical insulation? A. Low ambient temperature B. Low operating temperature C. High dielectric strength D. Low megger readings

Last Answer : Answer: D

Description : A constant output voltage from an AC generator is maintained by the _____________. A. prime mover governor B. exciter generator C. voltage regulator D. reverse power relay

Last Answer : Answer: C

Description : Three factors responsible for the change in voltage as load is applied to an AC generator are: 1) the drop in resistance in the armature circuit, 2) the change in flux, and 3) the ____________. A. armature winding speed B. inductance load drop C. coil pitch factor D. armature reactance voltage drop

Last Answer : Answer: D

Description : Basically, a magnetic amplifier is a saturable reactor with the addition of _____________. A. AC to the bias winding B. variable capacitance to all windings C. eddy current protectors D. a rectifier in the load circuit

Last Answer : Answer: D

Description : When using a megohmmeter to test insulation, good insulation will be indicated by _____________. A. slight kicks of the needle down scale B. a downward dip followed by a gradual climb to the true resistance ... C. a gradual rise in the pointer reading at the outset D. the initial dip of the pointer

Last Answer : Answer: B

Description : The amount of voltage induced in the windings of an AC generator depends on ____________. A. the number of conductors in series per winding B. the speed at which the magnetic field passes across the winding C. the strength of the magnetic field D. all of the above

Last Answer : Answer: D

Description : When a megohmmeter is being used on a alternating current machine, the meter pointer will dip toward 'zero' and then gradually rise to the true resistance value if the motor insulation is _____________. A. grounded B. good C. shorted D. dirty

Last Answer : Answer: B

Description : An operating characteristic appearing on the name plates of shipboard AC motors is _____________. A. the type of winding B. input kilowatts C. temperature rise D. locked rotor torque

Last Answer : Answer: C

Description : Routine maintenance of dry-type transformers should include ______________. A. preventing the entrance of water from broken pipe lines steam lines B. keeping protective surfaces and insulating bushings free of ... debris C. periodic testing of insulation resistance with a megger D. all of the above

Last Answer : Answer: D

Description : Discharge switches are often located on hand-driven meggers. The purpose of these switches is to discharge capacitive charges stored in the _____________. A. megger hand generator B. megger movement coils C. tested equipment while conducting test D. tested equipment after testing

Last Answer : Answer: D

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter pointer _____________. A. fluctuating around a ... slightly downscale as voltage is applied D. continually rising as the test voltage is applied

Last Answer : Answer: C

Description : When a megohmmeter is being used to test insulation resistance, current leakage along the surface of the insulation is indicated by the megohmmeter's pointer _____________. A. dipping toward ... kicking slightly down scale as voltage is applied D. fluctuating around a constant resistance reading

Last Answer : Answer: C

Description : The reactive power drawn by a motor from an AC generator is the power which is _____________. A. used to establish the magnetic field of the motor B. lost in overcoming friction in the ... by current flow through the windings D. transmitted directly through the rotor shaft to perform useful work

Last Answer : Answer: A

Description : The most practical way to control the voltage output of an AC generator is to vary the _____________. A. number of windings B. speed of the rotating field C. strength of the rotating magnetic field D. power factor of the load

Last Answer : Answer: C

Description : The amount of voltage induced in the windings of an AC generator depends mainly on _____________. A. the number of field poles energized B. the speed at which the stator windings rotate through the magnetic field C. the strength of the magnetic field D. all of the above

Last Answer : Answer: C

Description : The voltage output of an AC generator is accurately controlled by _____________. A. changing the sensitivity of the prime mover to large changes in voltage B. varying the reluctance of the air gap C. varying the DC exciter voltage D. shorting out part of the armature windings

Last Answer : Answer: C

Description : In an AC generator, direct current from a separate source is passed through the windings of the rotor _____________. A. by means of slip rings and brushes B. by means of a commutator C. by means of rotating bar magnet D. to minimize the danger of arc over

Last Answer : Answer: A

Description : When testing a capacitor with an analog type ohmmeter, a good capacitor will be indicated when _____________. A. there is no meter deflection B. the meter deflects to a low resistance value and ... deflects to a low resistance value and increases rapidly to a higher value, but stays fairly low

Last Answer : Answer: C

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test as the ______________. A. insulation may be damaged ... number of leakage paths D. larger machines may acquire a charge of static electricity during operation

Last Answer : Answer: D

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test, because the ___________. A. static charge of the machine ... number of leakage paths C. insulation may be damaged D. insulation may be covered with moisture

Last Answer : Answer: A

Description : The removal of paint from electrical equipment, such as generators, should be cautiously undertaken because ____________. A. the mechanical shock of paint removal lessens the dielectric strength ... phase windings frequently become isolated from each other due to dust interference at the terminals

Last Answer : Answer: B

Description : As shown in the illustration, what maintenance would be required of the circuit components? EL-0058 A. Change out both 'C' units monthly. B. Clean the glass surrounding 'E1' & 'E2' as needed. C. File ... upper end of 'G' every six months. D. Take megger readings on 'E1' & 'E2' windings quarterly.

Last Answer : Answer: B

Description : To carry out an insulation resistance test, one terminal of the megohmmeter should be connected to the winding, with the other terminal being connected to the ____________________. A. power supply B. variable resistor C. frame of the machine D. armature

Last Answer : Answer: C

Description : To measure insulation resistance of equipments of voltage rating upto 440 V the megger generator must generate   (a) 220 V (b) 440 V (c) 500 V (d) None of these 

Last Answer : 500 V

Description : Which of the following statements, concerning the general maintenance of a brushless generator, is correct? A. Paint should be applied to insulating surfaces on an annual basis. B. Alcohol should be used to ... . D. Accessible generator parts should be wiped with a clean dry rag on a periodic basis.

Last Answer : Answer: D

Description : The hook-on AC volt-ammeter consists essentially of a split-core and a rectifiertype instrument connected to the secondary winding of a _____________. A. potential transformer B. control transformer C. current transformer D. reactance transformer

Last Answer : Answer: C

Description : What are the necessary tests to determine the efficiency, voltage regulation, and temperature rise of winding & insulation of transformer?

Last Answer : 1.Direct loading test 2.Open circuit test 3. Short circuit test 4. Sumpner's or back to back test

Description : A saturable-core reactor operates on the principle of controlling a load winding's inductance by varying the core's _____________. A. dielectric B. permeability C. reactance D. inductance

Last Answer : Answer: B

Description : An open in the armature of a DC motor is suspected, but is not found by visual inspection of the commutator. The next step in troubleshooting this problem is to ________________. A. conduct a ... windings C. conduct an insulation resistance test of the armature D. test the commutator for a ground

Last Answer : Answer: A

Description : When the current flow through a copper wire increases, its _____________. A. resistance will decrease B. insulation will burn C. temperature will increase D. conductivity will increase

Last Answer : Answer: C

Description : An AC generator produces 60 Hz at 1800 RPM. If the generator speed is increased to 1830 RPM, the cycles will _____________. A. remain at 60 Hz B. increase to 61 Hz C. decrease to 59 Hz D. increase to 63 Hz

Last Answer : Answer: B

Description : Which statement is true concerning a split-phase induction motor? A. Motor rotation can be reversed without changing the windings or leads. B. Motor speed can be readily adjusted from zero to full ... proper wiring. D. Motor rotation can be reversed by reversing the leads on the starting winding.

Last Answer : Answer: D

Description : Moisture absorbed in the windings or condensed on the surface of electrical machinery insulation ________. A. is good for long term preserving since most insulation is organic and contains some amount B. ... D. reduces the amount of current supplied or drawn by the machine so horsepower is limited

Last Answer : Answer: B

Description : In testing a three-phase delta winding for an open circuit using a megohmmeter, you must ______________. A. test each phase with all connections intact B. measure the voltage across the open ... groups to avoid short circuiting D. open the delta-connections to avoid shunting the phase being tested

Last Answer : Answer: D