Two transformers of identical voltages but different capacities are operated in parallel, for satisfactory load sharing: a) Impedances should be equal b) Per unit impedance must be equal c) per unit impedance and X/R ratio must be equal d) Impedance and X/R ratio must be equal

1 Answer

Answer :

Ans: C

Related questions

Description : When two transformers are operating in parallel, they will share the load as under: (A) proportional to their impedances. (B) inversely proportional to their impedances. (C) 50% - 50% (D) 25%-75%

Last Answer : Ans: A High rating transformer has higher impedance. kVA rating α Impedance of transformer

Description : Two transformers operating in parallel will share the load depending upon their (A) Rating. (B) Leakage reactance. (C) Efficiency. (D) Per-unit impedance.

Last Answer : Ans: A Transformers having higher kVA rating will share more load.

Description : Can Transformers be Operated at Voltages other than Nameplate Voltages?

Last Answer : In some cases, transformers can be operated at voltages below the nameplate rated voltage. In NO case should a transformer be operated at a voltage in excess of its name- plate rating unless taps are ... 10 KVA, the reduced rating would be 5 KVA, or in direct proportion to the applied voltage.

Description : If the percentage impedances of the two transformers working in parallel are different, then?

Last Answer : If the percentage impedances of the two transformers working in parallel are different, then parallel operation will still be possible, but the power factors at which the two transformers operate will be different from the power factor of the common load.

Description : Can transformers be operated at voltages other than nameplate voltages?

Last Answer : In some cases, transformers can be operated at voltages below the nameplate rated voltage. In NO case should a transformer be operated at a voltage in excess of its nameplate rating, unless taps are ... 10 kVA, the reduced rating would be 5 kVA, or in direct proportion to the applied voltage.

Description : What will happen if transformer in parallel connection have different percentage impedance or X/R ratio ?

Last Answer : A difference in the ratio of the reactance value to resistance value of the per unit impedance results in a different phase angle of the currents carried by the two paralleled transformers; one ... of the combined output. Hence, the real power will not be proportionally shared by the transformers.

Description : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is 500 kVA and its pu ... its pu leakage impedance is  (A) 0.20 (B) 0.10 (C) 0.05 (D) 0.025

Last Answer : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is ... .05 pu. If the rating of second transformer is 250 kVA, its pu leakage impedance is 0.10

Description : Two transformers having the same p.u. impedance connected in parallel share the connected load (A) equally (B) in proportion to the respective ratings (C) in proportion to the voltage ratio (D) in proportion to the zero phase displacement

Last Answer : Two transformers having the same p.u. impedance connected in parallel share the connected load in proportion to the respective ratings

Description : Which of the following statements is correct for the illustrated circuit? EL-0020 A. 'R1', 'R2', and 'R3' are connected in series. B. 'R1', 'R2', and 'R3' are connected in parallel. C. The voltages measured across 'R1', 'R2', and 'R3' are equal. D. The total resistance equals 1/R1 + 1/R2 + 1/R

Last Answer : Answer: A

Description : Two transformers with identical voltage ratings are working in parallel to supply common load. The percentage impedance of one transformer is higher compared to that of other. The load sharing ... respective impedance (4) Depend on the resistance to leakage reactance ratio of each transformer

Last Answer : Two transformers with identical voltage ratings are working in parallel to supply common load. The percentage impedance of one transformer is higher compared to that of other. The load sharing between the two transformer will: Be inversely proportional of their respective impedance

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : Which of the methods listed is used to maintain equal load sharing between two compound wound DC generators operating in parallel? A. The shunt fields are interconnected. B. The shunt field rheostats ... are connected in series. D. The series fields of both generators are connected in parallel.

Last Answer : Answer: D

Description : Two 3-phase transformers cannot be operated in parallel, if their :  (A) kVAs are different (B) phase sequences are different (C) % impedances are different (D) voltage ratios are different

Last Answer : Two 3-phase transformers cannot be operated in parallel, if their : phase sequences are different

Description : Can 60 Hz transformers be operated at 50 Hz?

Last Answer : The transformers rated below 1 KVA can be used on 50 Hz service. Transformers 1 KVA and larger, rated at 60 Hz, should not be used on 50 Hz service, due to the higher losses and resultant heat ... designs are required for this service. However, any 50 Hz transformer will operate on a 60 Hz service.

Description : The forced oil and air circulation method is usual one for transformers of capacities (a) upto 5 MVA (b) upto 10 MVA (c) upto 20 MVA (d) 30 MVA upwards

Last Answer : (d) 30 MVA upwards

Description : When a transmission line has a load impedance same as that of the characteristic impedance, the line is said to be a) Parallel b) Perpendicular c) Polarized d) Matched

Last Answer : Ans: D

Description : What is Meant by "Impedance" in Transformers?

Last Answer : ANSWER: Impedance is the current limiting characteristic of a transformer and is expressed in percentage.

Description : What is meant by “impedance” in transformers? Why is it important?

Last Answer : A. Impedance is the current limiting characteristic of a transformer and is expressed in percentage. It is used for determining the interrupting capacity of a circuit breaker or fuse employed to protect the primary of a transformer

Description : The efficiency of two identical transformers under load conditions can be determined by?

Last Answer : The efficiency of two identical transformers under load conditions can be determined by back-to-back test.

Description : The electrical diagram shown in the illustration shows _____________. EL-0021 A. 'R1', 'R2', and 'R3' are connected is series B. 'R1', 'R2', and 'R3' are connected in parallel C. the voltages measured across ... if 'R1', 'R2' and 'R3' have different values D. the total resistance equals R1 + R2 + R3

Last Answer : Answer: B

Description : If the molar heat capacities (Cp or Cv) of the reactants and products of a chemical reaction are identical, then, with the increase in temperature, the heat of reaction will (A) Increase (B) Decrease (C) Remain unaltered (D) Increase or decrease; depends on the particular reaction

Last Answer : (C) Remain unaltered

Description : The load sharing characteristics of two diesel alternators operating in parallel are directly related to the setting of their governors' ____________. A. load limit B. idle speed C. speed limit D. speed droop

Last Answer : Answer: D

Description : When two generators are on the line and are sharing the load equally, they are said to be operating in _____________. A. frequency B. series C. parallel D. resonance

Last Answer : Answer: C

Description : The load sharing characteristics of two diesel generators operating in parallel are mostly dependent on their governor ____________. A. load limit settings B. idle speed settings C. speed limit settings D. speed droop settings

Last Answer : Answer: D

Description : List the factors that affect the load sharing in parallel operating generators?

Last Answer : The total active and reactive power delivered to the load, connected across the common bus-bars, are shared among Synchronous generators, operating in parallel, based on the following three factors ... characteristic/input · Excitation level and · Percentage synchronous impedance and its R/X ratio

Description : The voltages across various discs of suspension insulators having identical discs are different due to:  (A) Surface leakage currents  (B) Series capacitance of lines  (C) Shunt capacitance to ground  (D) Series and shunt capacitances

Last Answer : The voltages across various discs of suspension insulators having identical discs are different due to: Shunt capacitance to ground 

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in?

Last Answer : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in loading of the transformers not in proportion to their kVA ratings.

Description : Parallel straight line pattern of temperature distribution for both hot and cold fluids is observed in case of heat exchanger of the type (A) Parallel flow with equal heat capacities (B) Counter ... (C) Counter flow with unequal heat capacities (D) Parallel flow with unequal heat capacities

Last Answer : (B) Counter flow with equal heat capacities

Description : In a 3-phase 4-wire distribution system three unbalanced but equal magnitude impedances are connected between respective lines and neutral. The magnitude of current in the neutral conductor for RYB and RBY phase sequences ... ) zero (B) same (C) different (D) same in magnitude but differs in phase.

Last Answer : In a 3-phase 4-wire distribution system three unbalanced but equal magnitude impedances are connected between respective lines and neutral. The magnitude of current in the neutral conductor for RYB and RBY phase sequences are different 

Description : Which of the following statements is true concerning the operation of two alternators in parallel? A. The cycles per second of each alternator are the same. B. Both alternator governors must be set ... be the same on each alternator. D. The load must always be divided equally between alternators.

Last Answer : Answer: A

Description : A load with an impedance of 440 ohms is connected across the secondary of the transformer illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given

Last Answer : Answer: B

Description : A load with an impedance of 440 ohms is connected across the secondary of the device illustrated. If the input voltage is 110 VAC and the step-up ratio is 10 to 1, what will be the primary current? EL-0055 A. 2.5 amps B. 25 amps C. 250 amps D. current cannot be determined with information given

Last Answer : Answer: B

Description : Which of the following statements is true concerning simple parallel resistance circuits? A. The total current flow equals the sum of the individual currents. B. The total current flow equals the ... resistance. D. The total voltage equals the sum of the individual voltages across each resistance.

Last Answer : Answer: A

Description : Which of the following statements concerning a simple parallel resistance circuit is correct? A. The voltage drop across each resistor is the same. B. The total current flow equals the reciprocal ... resistances. D. The total voltage equals the sum of the individual voltages across each resistance.

Last Answer : Answer: A

Description : Three equal impedances are first connected in delta across a 3 -phase balanced supply. If the same impedances are connected in star across the same supply then,

Last Answer : A

Description : If l1 and l2 are the lengths of long and short spans of a two way slab simply supported on four edges and carrying a load w per unit area, the ratio of the loads split into w1 and w2acting on strips parallel to l2 and l1 is (A) ... l1 (B) w1/w2 = (l2/l1)² (C) w1/w2 = (l2/l1)3 (D) w1/w2 = (l2/l1)

Last Answer : Answer: Option D

Description : In a series-RLC circuit, what is the condition of the circuit if there is high impedance, low current, and low reactance voltages

Last Answer : Nonresonant (circuit is either above or below resonance)

Description : The transmit and receive elements of a sound-powered telephone handset are _____________. A. identical and can be used for either function B. of similar construction but different enough to be used only for ... only for its own function D. constructed so that each can fit only in its own recess

Last Answer : Answer: A

Description : Adiabatic bulk modulus is equal to:  A. Υ × P; where Υ: the ratio of the specific heat capacities of the gas, P: pressure B. Pressure C. The ratio of the specific heat capacities of the gas D. Υ ⁄ P; where Υ: the ratio of the specific heat capacities of the gas, P: pressure

Last Answer : Υ × P; where Υ: the ratio of the specific heat capacities of the gas, P: pressur

Description : Isothermal bulk modulus is equal to A. Υ × P; where Υ: the ratio of the specific heat capacities of the gas, P: pressure B. Pressure C. The ratio of the specific heat capacities of the gas D. Υ ⁄ P; where Υ: the ratio of the specific heat capacities of the gas, P: pressure

Last Answer : Pressure

Description : Two transformers operating in parallel will share the load depending upon their

Last Answer : Two transformers operating in parallel will share the load depending upon their Per unit impedance

Description : If a three-phase induction motor is operated under a light load and it develops an open in one of its supply lines, the motor will _____________. A. continue to run, but will vibrate and have reduced ... speed up due to the reduced number of poles C. run cooler due to reduced current flow D. stop

Last Answer : Answer: A

Description : Equalization of the power factors of two alternators operating in parallel is accomplished _____________. A. manually, by adjusting the governor controls B. automatically, by automatic voltage regulators ... the output of current transformers D. automatically, by the designed action of the governors

Last Answer : Answer: B

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : What are the conditions for parallel operation of two transformers ?

Last Answer : Transformers which are to be operated parallel should have to satisfy the following conditions: Polarities of both the transformers should be same else lead to short circuit Voltage rating of ... Phase displacement of transformers should be same Phase sequence of two transformers should be same

Description : What are the Conditions for parallel operation of transformers?

Last Answer : A. a) Same voltage ratio of transformer: If two transformers of different voltage ratio, are connected in parallel with same primary supply voltage, there will be a difference in secondary voltages. If ... not in same phase sequence, during the cycle, each pair of phases will be short circuited.

Description : What are the advantages of parallel operation of transformers?

Last Answer : A. 1) To maximize electrical power system efficiency: Generally electrical power transformer gives the maximum efficiency at full load. If we run numbers of transformers in parallel, we can switch ... running in parallel can be removed from system to balance the capital investment and its return.