Description : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is 500 kVA and its pu ... its pu leakage impedance is (A) 0.20 (B) 0.10 (C) 0.05 (D) 0.025
Last Answer : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is ... .05 pu. If the rating of second transformer is 250 kVA, its pu leakage impedance is 0.10