The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

1 Answer

Answer :

The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: 400 Mega Joule

Related questions

Description : A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

Last Answer : c

Description : A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Last Answer : 800

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

Last Answer : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of 0.02 P.U

Description : The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are (A) 4, 0.4 (B) 100, 10 (C) 4, 10 (D) 100, 0.4

Last Answer : The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are 100, 0.4

Description : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

Last Answer : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is 5/6 p.u.

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer :  As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : If the inertia constant H of a machine of 200 MVA is 2 p.u., its value corresponding to 400 MVA will be   (a) 4 p.u. (b) 2 p.u. (c) 1.0 p.u. (d) 0.5 p.u. 

Last Answer : If the inertia constant H of a machine of 200 MVA is 2 p.u., its value corresponding to 400 MVA will be 1.0 p.u.

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the infinite bus voltage is 1 pu. The ... fault at the generator terminal is  (A) 53.5 (B) 60.2 (C) 70.8 (D) 79.6

Last Answer : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the ... clearing angle, in degrees, for a three-phase dead short circuit fault at the generator terminal is 79.6

Description : A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

Last Answer : 89

Description : The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:  (A) 0.3 (B) 0.6 (C) 0.003 (D) 0.006 

Last Answer : 3

Description : A 100 km long transmission line is loaded at 110 kV.if the loss of line is 5 MW and the load is 150 MVA, the resistance of the line is?

Last Answer : P = I^2  *  R 5*10^6  = [(150*10^6) / (110*10^3)  *  R R = 2.7 ohm/phase

Description : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

Last Answer : A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be 240 

Description : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is (A) 1204 MW (B) 1504 MW (C) 2085 MW (D) 2606 MW

Last Answer : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is 2085 MW

Description : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

Last Answer : An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately P / 4

Description : The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

Last Answer : Vscos¢s-Vrcos¢r=IR

Description : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill

Last Answer : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill 2000 MW .

Description : The X:R ratio of 220 kV line as compared to 400 kV line is?

Last Answer : The X:R ratio of 220 kV line as compared to 400 kV line is smaller.

Description : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be?

Last Answer : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be 0.30.

Description : During a disturbance on a synchronous machine, the rotor swings form A to B before finally setting down to steady state at point C on the power angle curve. The speed of the machine during oscillation is synchronous at point(s)

Last Answer : During a disturbance on a synchronous machine, the rotor swings form A to B before finally setting down to steady state at point C on the power angle curve. The speed of the machine during oscillation is synchronous at point(s) only at C

Description : For a two-rotor system, the length of one shaft (A) is twice the other (B), then what is the relation between the mass moment of inertia of the shafts. A 2I(A) = I(B) B I(A) = 2I(B) C I(A) = I(B) D 2I(A) = 3I(B)

Last Answer : A 2I(A) = I(B)

Description : In case of a universal motor, torque pulsation is minimized by _________. (A) load inertia (B) rotor inertia (C) both rotor and load inertia (D) none of the above

Last Answer : Ans: C In a universal motor, torque pulsation is minimized by rotor and load inertia.

Description : How is a 100 MVA transformer cooled?

Last Answer : 100 MVA Transformer is cooled by forced oil forced water cooling method..

Description : Large industrial consumers are supplied electrical energy at (a) 400 V (b) 11 kV (c) 66 kV (d) 400 kV

Last Answer : (c) 66 kV

Description : The spokes used in the wheel of a bicycle increase its – (1) Moment of inertia (2) Velocity (3) Acceleration (4) Momentum

Last Answer : (1) Moment of inertia Explanation: A spoke is one of some number of rods radiating from the center of a wheel (the hub where the axle connects), connecting the hub with the round ... synthetic fibers, are also occasionally used. Metal spokes used in bicycles also increase the moment of inertia.

Description : The spokes used in the wheel of a bicycle increase its (1) Moment of inertia (2) Velocity (3) Acceleration (4) Momentum

Last Answer : Moment of inertia

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: A. 2,000 V B. 6,000 V C. 666 V D. 3,464 V

Last Answer : In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: 3,464 V

Description : The zero sequence current of a generator for line to ground fault is j 2.4 p.u. The current through the neutral during the fault is (a) j 0.8 p.u (b) j 2.4 p.u. (c) j 0.24 p.u. (d) j 7.2 p.u. 

Last Answer : j7.2

Description : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are (A) 6 (B) 12 (C) 16 (D) 24

Last Answer : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are 24

Description : For optimum generator scheduling for different power plants, the minimum fuel cost is obtained when

Last Answer : For optimum generator scheduling for different power plants, the minimum fuel cost is obtained when The incremental fuel cost of each plant multiplied by the penalty factor is the same

Description : A large AC generator, supplying power to an infinite bus, has a sudden short-circuit occurring at its terminals. Assuming the prime mover input and the voltage behind the transient reactance to remain constant immediately after the fault, acceleration of the generator rotor is

Last Answer : A large AC generator, supplying power to an infinite bus, has a sudden short-circuit occurring at its terminals. Assuming the prime mover input and the voltage behind the transient reactance ... , acceleration of the generator rotor is inversely proportional to the moment of inertia of the machine

Description : For cost and safety, the outdoor substations are installed for voltages above (a) 11 kV (b) 33 kV (c) 60kV (d) 110kV

Last Answer : (b) 33 kV

Description : The operating voltage of extra high tension cables is upto (a) 6.6 kV (b) 11 kV (c) 33 kV (d) 66 kV (e) 132 kV

Last Answer : (d) 66 kV

Description : The operating voltage of supertension cables is up to (a) 3.3 kV (b) 6.6 kV (c) 11 kV (d) 33 kV

Last Answer : (d) 33 kV

Description : Overhead system can be designed for operation up to (a) 11 kV (b) 33 kV (c) 66 kV (d) 400 kV

Last Answer : (c) 66 kV

Description : The underground system cannot be operated above (a) 440 V (b) 11 kV (c) 33 kV (d) 66 kV

Last Answer : (d) 66 kV

Description : Pressure cables are generally not used beyond (a) 11 kV (b) 33 kV (c) 66 kV (d) 132 kV

Last Answer : (c) 66 kV

Description : For transmission of power over a distance of 200 km, the transmission voltage should be (a) 132 kV (b) 66 kV (c) 33 kV (d) 11 kV

Last Answer : (a) 132 kV

Description : Pin type insulators are generally not used for voltages beyond (a) 1 kV (b) 11 kV (c) 22 kV (d) 33 kV

Last Answer : (d) 33 kV