The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are (A) 4, 0.4 (B) 100, 10 (C) 4, 10 (D) 100, 0.4

1 Answer

Answer :

The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are 100, 0.4

Related questions

Description : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

Last Answer : A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is 0.01

Description : If the inertia constant H of a machine of 200 MVA is 2 p.u., its value corresponding to 400 MVA will be   (a) 4 p.u. (b) 2 p.u. (c) 1.0 p.u. (d) 0.5 p.u. 

Last Answer : If the inertia constant H of a machine of 200 MVA is 2 p.u., its value corresponding to 400 MVA will be 1.0 p.u.

Description : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

Last Answer : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: 400 Mega Joule

Description : Which of the following statements is incorrect ? (a) Lightning arrestors are used before the switchgear (b) Shunt reactors are used as compensation reactors (c) The peak short current is (1.8 xV2) ... component (d) The MVA at fault is equal to base MVA divided by per unit equivalent fault reactance

Last Answer : (a) Lightning arrestors are used before the switchgear

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

Last Answer : A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is 5/6 p.u.

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Last Answer : 800

Description : A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

Last Answer : c

Description : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

Last Answer : A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of 0.02 P.U

Description : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

Last Answer : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he 0.52

Description : Which of the following parameter can be neglected for a short line ? (a) Inductance (b) Capacitance (c) Resistance (d) Reactance

Last Answer : (b) Capacitance

Description : Consider the following statements. Which of these statements are correct ?  (1) Reactance relays are preferred for ground fault relaying  (2) Impedance relays are most suitable for:protecting long transmission lines  (3) Mho relays are best ... (1) and (3) (C) (2) and (4) (D) (1), (2) and (4)

Last Answer : Consider the following statements. Which of these statements are correct ?  (1) Reactance relays are preferred for ground fault relaying  (2) Impedance relays are most suitable for:protecting long transmission lines  (3) Mho relays are ... (1) and (3) (C) (2) and (4) (D) (1), (2) and (4)

Description : A reactance relay is (A) Voltage restrained directional relay (B) Directional restrained over-current relay (C) Voltage restrained over current relay (D) Directional restrained over voltage relay

Last Answer : A reactance relay is Directional restrained over-current relay

Description : The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is (A) 0.5 p.u. (B) 0.96 p.u. (C) 1.5 p.u. (D) 1.8 p.u.

Last Answer : The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is 1.5 p.u.

Description : The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:  (A) 0.3 (B) 0.6 (C) 0.003 (D) 0.006 

Last Answer : 3

Description : The zero sequence current of a generator for line to ground fault is j 2.4 p.u. The current through the neutral during the fault is (a) j 0.8 p.u (b) j 2.4 p.u. (c) j 0.24 p.u. (d) j 7.2 p.u. 

Last Answer : j7.2

Description : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

Last Answer : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is 1.088 p.u.

Description : The forced oil and air circulation method is usual one for transformers of capacities (a) upto 5 MVA (b) upto 10 MVA (c) upto 20 MVA (d) 30 MVA upwards

Last Answer : (d) 30 MVA upwards

Description : The voltage at the two ends of a transmission line are 132 KV and its reactance is 40 ohm. The Capacity of the line is (A) 435.6 MW (B) 217.8 MW (C) 251.5 MW (D) 500 MW

Last Answer : (A) 435.6 MW

Description : The component labeled 'CR1' in the circuit shown in the illustration __________________. EL-0085 A. varies its anode/cathode polarity depending on 'RL' current B. rectifies the varying voltage from the ... reactance to smooth ripple D. establishes a constant reference voltage for the base of 'Q1'

Last Answer : Answer: D

Description : What is the moment of inertia acting on a rectangle of width 15 mm and depth 40 mm about base by using theorem of parallel axes? a. 320 x 103 mm4 b. 300 x 103 mm4 c. 240 x 103 mm4 d. 80 x 103 mm

Last Answer : a. 320 x 103 mm4

Description : For a 500 Hz frequency excitation, a 50 km long power line will be modeled as

Last Answer : For a 500 Hz frequency excitation, a 50 km long power line will be modeled as long line

Description : What is the maximum value of a load which consume 500 KWh per day at a load factor of 0.40, if the consumer increases the load factor of 0.50 without increasing the maximum demand?

Last Answer : 52.08 kW is the maximum value of a load which consume 500 KWh per day at a load factor of 0.40, if the consumer increases the load factor of 0.50 without increasing the maximum demand.

Description : Untuned viscous damper ( houdaille Damper) is used with variable speed machine being control by ratio can be given by A) (damper inertia) / (main system inertia) B) (main system inertia) / (damper inertia) ... X damper inertia) / (main system inertia) D) (2 X main system inertia) / (damper inertia)

Last Answer : A) (damper inertia) / (main system inertia)

Description : Untuned viscous damper ( houdaille Damper) is used with variable speed machine being control by ratio can be given by A) (damper inertia) / (main system inertia) B) (main system inertia) / (damper inertia) ... X damper inertia) / (main system inertia) D) (2 X main system inertia) / (damper inertia)

Last Answer : A) (damper inertia) / (main system inertia)

Description : The synchronous reactance of the synchronous machine is ______________. (A) Ratio between open circuit voltage and short circuit current at constant field current (B) Ratio between short circuit ... (D) Ratio between short circuit voltage and open circuit current at different field current

Last Answer : Ans. A The Synchronous reactance of a synchronous machine is a total steady state reactance, presented to applied voltage, when rotor is running synchronously without excitation. Therefore , XS = Ef / IS = Emf of OC for same If / short circuit current

Description : Can u run the report with out a parameter form

Last Answer : Yes it is possible to run the report without parameter form by setting the PARAM value to Null

Description : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be?

Last Answer : The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be 0.30.

Description : Moment of Inertia of triangular section about an axis passing through its base is given by a.bh3/12 b.bh3/32 c.bh3/36 d.None of the above e.Tapered bearing

Last Answer : a. bh3/12

Description : The ratio of moments of inertia of a triangular section about its base and about a centroidal axis  parallel to its base, is  (A) 1.0  (B) 1.5  (C) 2.0  (D) 3.0 

Last Answer : (D) 3.0 

Description : The moment of inertia of a triangular section (height h, base b) about its base, is  (A) bh²/12  (B) b²h/12  (C) bh3 /12  (D) b 3h/12 

Last Answer : (C) bh3 /12 

Description : A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

Last Answer : 89

Description : The base of a cubical tank is `25 m xx 40 m`. The volume of water in the tank is increasing at the rate of `500 m^(3)//min`. Find the rate at which th

Last Answer : The base of a cubical tank is `25 m xx 40 m`. The volume of water in the tank is ... Find the rate at which the height of water is increasing.

Description : The total value of extra widening required at a horizontal curve on a two lane hill road of radius 42 m for a design speed of 50 kmph and for vehicles with wheel base 6 m, is (A) 0.500 m (B) 0.589 m (C) 1.089 m (D) 0.089 m

Last Answer : Answer: Option C

Description : A cement concrete road is 1000 m long, 8 m wide and 15 cm thick over the sub-base of 10 cm thick gravel. The box cutting in road crust is (A) 500 m3 (B) 1000 m3 (C) 1500 m3 (D) 2000 m3

Last Answer : (C) 1500 m3

Description : 1. Assume that there are only two goods: A and B In the base year, Quantity Price A 10 $1 B 10 $4 In the current year, Quantity Price A 20 $ 5 B 25 $20 The Consumer Price Index (CPI) for the current year is: a. 50 b. 100 c. 200 d. 500 e. 60

Last Answer : d. 500

Description : ______ is the perpendicular distance between point of application of force and axis of rotation. (1) Moment arm (2) Moment of Inertia (3) Altitude (4) Base

Last Answer : (1) Moment arm Explanation: The magnitude of the moment of force acting about a point or axis is directly proportional to the distance of the force from the point or axis.

Description : What is the full form of 'MVA' ? -How To ?

Last Answer : The full form of 'MVA' is Motor Vehicles Act

Description : What is the full form of MVA ?

Last Answer : MVA full version Mega Volt Ampere.

Description : How is a 100 MVA transformer cooled?

Last Answer : 100 MVA Transformer is cooled by forced oil forced water cooling method..

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer : A. As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : If we give 2334 A, 540V on Primary side of 1.125 MVA step up transformer, then what will be the Secondary Current, If Secondary Voltage=11 KV?

Last Answer :  As we know the Voltage & current relation for transformer-V1/V2 = I2/I1 We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps. By putting these value on Relation540/11000= I2/2334 So,I2 = 114.5 Amps

Description : For which of the following ratings of the transformer differential protection is recommended ? (a) above 30 kVA. (b) equal to and above 5 MVA (c) equal to and above 25 MVA (d) none of the above

Last Answer : (b) equal to and above 5 MVA

Description : Transformers with a capacity of upto _____ have a cooling radiator system with natural cooling (a) 2 MVA (b) 5 MVA (c) 7.5 MVA (d) 10 MVA

Last Answer : (d) 10 MVA

Description : Newton's first law is often referred to as which of the following? w) The law of straight-line motion. x) The law of momentum y) The law of inertia z) F = ma (Spell out M-A)

Last Answer : ANSWER: Y -- THE LAW OF INERTIA