State the methods used to measure insulation resistance and explain Dielectric Absorption method.

1 Answer

Answer :

There are three types of tests for measuring insulation resistance: 

1. Spot test reading or Short Time test 

2.Time-resistance test or Dielectric absorption test or Testing methods based on the PI & DAR 

3. Step voltage test 


Explanation to measure insulation resistance by Dielectric Absorption method:- 

The megger is connected across the insulation. Take successive readings at fixed time interval For this method, two readings are taken at 30 seconds and 60 seconds respectively to calculate DAR And also for 1 minute and 10 minutes, respectively to calculate PI. The PI and DAR are commonly used to quantify the time resistance test result. A curve is plotted from the readings. Good insulation shows a continuous increase in the resistance value over a period of time and if value of PI is greater than 2 or 4 and value of DAR is greater than between 1.25 to 1.6 If reading is stagnant and it does not increase as expected, the insulation may be weak and service may be needed and if value of PI is less than 2 and value of DAR is less than 1.25

image

Related questions

Description : When a megohmmeter is used to test insulation, the gradual rise of the pointer reading as a result of continued cranking, is caused by _____________. A. good conductor resistance B. the ... insulation C. the inductive reactance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: D

Description : Explain vacuum impregnation method used for Re-varnishing of insulation with neat diagram.

Last Answer : Figure of process of vaccum impregnation:-  Explain the process of vacuum impregnation:- The plant consists of: 1. A large air tight chamber (VIC) i.e. processing or impregnation chamber. 2 ... )curing temperature varies from 90°C to 110°C for 10-20 minutes in some cases one to two hours.

Description : When a megohmmeter is used to test the insulation of a large motor, the initial dip of the pointer toward 'zero' is caused by ____________. A. good insulation B. the capacitance of the ... of the current along the surface of dirty insulation D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When using a megohmmeter to test the dielectric strength of wire insulation, a continuous series of slight downscale kicks by the pointer is result of ____________. A. good insulation B. the ... dirty insulation C. the capacitance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : When a megohmmeter is used to test the dielectric strength of wire insulation, the initial dip of the pointer toward 'zero' is caused by _____________. A. good insulation B. the leakage of ... of dirty insulation C. the capacitance of the circuit D. the dielectric absorption effect of the insulation

Last Answer : Answer: C

Description : Describe any four methods used to reduce earth resistance.  

Last Answer : To reduce earth resistance following steps/methods are necessary: 1. Earth pit of more depth & width- breadth should be made. 2. Use of higher size/cross section of earthing material like ... galvanized. 12. Electrodes should be placed in the earth in the upright vertical position. 

Description : Indicate the three types oftransmissionline energylosses. a. I2R, R , and temperature b. Radiation, I2R, and dielectric heating c. Dielectric separation, insulation breakdown, and radiation d. Conductor heating, dielectric heating, and radiation resistance.

Last Answer : b. Radiation, I2R, and dielectric heating

Description : Name the method used to measure following resistances:- (i) Low resistance (ii) Medium resistance (iii) Insulation resistance (iv) Earth resistance.

Last Answer : Following are the methods used to measure resistances:-  (i) Low resistance: 1.Voltmeter-Ammeter Method 2. Kelvin's Double bridge Method  (ii) Medium resistance: 1.Voltmeter-Ammeter Method 2. ... of Charge Method  (iv) Earth resistance : 1. Fall of Potential Method 2. Earth tester

Description : State the methods of Neutral Grounding. State difference between Earthing and grounding. 

Last Answer : Neutral Grounding connections are of three types:  1. Solid earthing 2. Resistance earthing 3. Reactance earthing SR. NO. Earthing Grounding 1 Earthing means connecting the dead part ... earthing provides suitable means for earth fault protecting system.  10

Description : Out of the following methods of heating the one which is independent of supply frequency is (A) electric arc heating (B) induction heating (C) electric resistance heating (D) dielectric heating

Last Answer : (C) electric resistance heating

Description : The removal of paint from electrical equipment, such as generators, should be cautiously undertaken because ____________. A. the mechanical shock of paint removal lessens the dielectric strength ... phase windings frequently become isolated from each other due to dust interference at the terminals

Last Answer : Answer: B

Description : Which of the listed conditions could indicate the need for cleaning electrical insulation? A. Low ambient temperature B. Low operating temperature C. High dielectric strength D. Low megger readings

Last Answer : Answer: D

Description : Due to which of the following reasons the cables should not be operated too hot ? (a) The oil may loose its viscosity and it may start drawing off from higher levels (b) Expansion of the ... instability may rise due to the rapid increase of dielectric losses with temperature (e) All of the above

Last Answer : (e) All of the above

Description : The breakdown of insulation of the cable can be avoided economically by the use of (a) inter-sheaths (b) insulating materials with different dielectric constants (c) both (a) and (b) (d) none of the above

Last Answer : (c) both (a) and (b)

Description : If a cable of homogeneous insulation has a maximum stress of 10 kV/mm, then the dielectric strength of insulation should be (a) 5 kV/mm (b) 10 kV/mm (a) 15 kV/mm (d) 30 kV/mm

Last Answer : (b) 10 kV/mm

Description : Compare direct and Indirect method of testing.  

Last Answer : Sr No.  Parameter Direct Testing Indirect Testing   1 Nature of loading  The m/c is actually loaded at full load. The m/c is not actually loaded but machine run on N.L. 2 ... 1.O.C. and S.C test on transformer/Alternator / I.M. , 2. Swinburne test on DC machines. 

Description : When working on electrical circuits containing large capacitors, in addition to deenergizing the circuit, which of the listed precautions should also be taken? A. Keep all radio equipment ... capacitor insulation resistance. C. Ground the capacitor terminals. D. Check capacitor circuit polarity.

Last Answer : Answer: C

Description : A galvanometer is an instrument used to measure ___________. A. thickness of galvanized metal B. resistance of electrical wiring insulation C. very small amounts of current or voltage D. quantity of galvans in an electric circuit

Last Answer : Answer: C

Description : Before using a volt-ohmmeter to measure resistance readings, you should _____________. A. replace all batteries B. test the insulation resistance of the leads C. make sure the test leads do not touch D. hold the leads together and 'zero' the meter

Last Answer : Answer: D

Description : Which of the listed statements is correct when using an analog multimeter as an ohmmeter? A. The pointer should be adjusted to zero each time a new resistance range is selected. B. The ... C. Ohmmeters are not sufficiently sized to measure conductor insulation resistance. D. All of the above.

Last Answer : Answer: D

Description : A megger is to measure insulation resistance of a cable. The cable should be connected to   (a) Battery (b) DC supply (c) AC supply (d) No supply  

Last Answer : majorly in DC as well as AC......but ans is Battery

Description : To measure insulation resistance of equipments of voltage rating upto 440 V the megger generator must generate   (a) 220 V (b) 440 V (c) 500 V (d) None of these 

Last Answer : 500 V

Description : State types of maintenance. Explain each with example. 

Last Answer : Maintenance are classified as below:- 1. Preventive Maintenance (PM) 2. Routine /daily maintenance 3. Periodic maintenance/Time based maintenance (TBM) 4. Predictive maintenance (PDM) 5. ... by the manufacturer. It involves partial or complete dismantling of the equipment/machine and overhaul.

Description : State and explain properties of transformer oil.  

Last Answer : Following are the properties of transformer oil:-  1. Dielectric strength :- It should be have a high dielectric strength  2. Specific resistance:- It should be have a high Specific ... be not contain impurities such as sulpher & its compounds to avoid rusting & sludge formation. 

Description : State the objective of testing. Explain the role of BIS (Bureau of Indian Standards) in testing of electrical machines. 

Last Answer : 1. Objective of testing is to finding error/defects in machine/equipment/ product. 2. To confirm whether the results obtain during testing are within tolerance limits specified by BIS / ISS 3. To ... BIS/ISS specified standards. 5. To avoid in convinces & accidents BIS plays important role.  

Description : What you mean by dielectric absorption test?

Last Answer : Whenever we apply a potential from the megger to test the IR value, initially the needle of the megger will go to low value of the resistance. This is due the capacitance effect of the ... A. After the test terminals to be discharged so that molecules may return to their unstressed state. 

Description : Choose the best definition of dielectric loss. a) Absorption of electric energy by dielectric in an AC field b) Dissipation of electric energy by dielectric in a static field c) Dissipation of heat by dielectric d) Product of loss tangent and relative permittivity

Last Answer : a) Absorption of electric energy by dielectric in an AC field

Description : Explain importance and purpose of earthing. 

Last Answer : Importance and purpose of earthing is as below:- 1. To provide an alternative path for the leakage current to flow towards earth. 2. To save human life from danger of electrical shock due to ... equipment body (frame) below the earth potential in the event of fault from safety point of view. 

Description : The greatest detrimental effect on idle electrical equipment, such as cargo pump motors, is the _____________. A. loss of residual magnetism B. absorption of moisture in the insulation C. insulation varnish flaking D. dirt collecting on the windings

Last Answer : Answer: B

Description : State any eight causes of fire. 

Last Answer : Following are the Causes of electrical Fires:- 1. Overloading on cables/wires/machine causes possibility of fire. 2. Use of too many device plugged into a circuit, causing heated wire & possible a ... & equipment's used in hazards area are not used as per the specification/type of protection.

Description : State the basic requirements of foundation for :(i) Static equipment’s (ii) Rotating equipment’s

Last Answer : Following are the basic requirements of foundation to be considered in designing the machine foundation for :(i) Static equipment's (ii) Rotating equipment's  1. Depth of foundation should be ... it.  11. The dimension of foundation should be proportional to safe bearing capacity of soil.

Description : State the procedure for developing preventive maintenance schedule. 

Last Answer : Procedure of PM is as below:-  Step 1:- Inspection: What to inspect and how to inspect? Maintenance engineer / team should inspect the plan under working condition. Prepare the check ... :- Check the availability of trained & skilled technician to do maintenance before starting the work.

Description : State any eight safety precautions to be followed while working with an electric installation. 

Last Answer : Wear safety boot and use right tool for the right job

Description : State any one application of each tool : (i) Earth tester (ii) Megger (iii) Bearing puller (iv) Growler 

Last Answer : i) Earth Tester :- It is used to measure earth resistance.  ii) Megger :- Megger is used to find out (measure) insulation resistance of electrical machine/equipment.  iii) ... is an electrical device used to find out shorted turn faults in armature winding and stator winding of motor.

Description : State any four advantages of preventive maintenance. 

Last Answer : Following are the advantages of Preventive Maintenance:- 1. It increases life of machine/equipment. 2. It prevents premature failure. 3. It keeps the machine in good working condition by reducing wear and ... more expensive than the same job done PM/preplanned (and may take 10 times longer).

Description : State the factors on which severity of electric shock depends. 

Last Answer : The severity of shock depends on following factors.  1. Magnitude voltage of the system.  2. The period or duration for which the area of contact with lives part.  3. It is also depends on ... 200mA  May cause fibration of heart  6 Above -200mA Causes death, severe burns 

Description : What are the different methods used to measure the resistance?

Last Answer : The different methods developed to measure the resistances are as follows. a. Wheat stone bridge. b. Slide wire bridge. c. Post office box. d. Ohm meter. e. AVO meter or multi meter. f. Bridge megger. g. Megger.

Description : A megohmmeter is used to measure _____________. A. voltage B. dielectric strength C. current D. power

Last Answer : Answer: B

Description : The bridge used to measure the dielectric loss of an insulator is: A) Anderson bridge B) Wien’s bridge C) Schering bridge D) Any of the above

Last Answer : C)Schering bridge

Description : Explain speed control method of 3 phase induction motor by the following methods: (1) Pole changing (2) Rotor resistance control (3) Stator voltage

Last Answer : 1) Pole Changing Method:  Synchronous speed is given by, From the above equation of synchronous speed, it can be seen that synchronous speed (and hence, running speed) can ... in voltage and consequently the speed decreases and vice versa. Ultimately speed depends on the supply voltage.

Description : State any two applications of each for the following types of electrical heating : (i) Direct resistance heating(ii) Indirect induction heating (iii) Direct.arc heating (iv) Dielectric heating

Last Answer : (i) Direct resistance heating:- 1. This type of heating used for industrial purpose 2. Salt bath heating: This utilized for the purpose of carbonizing, tempering, quenching and hardening of steel tools 3. ... purpose. 14)In foundry for heating of sand, core, which are used in molding processes.

Description : The operator of electrical motors should keep a constant check on the loads they carry because _____________. A. low loads necessitate frequent insulation cleaning B. exceeding nameplate values shortens ... wasted if full loading is not utilized D. power factor correction methods are load dependent

Last Answer : Answer: B

Description : Classify the insulating materials as per operating temperature. Give two examples of each type.

Last Answer : Sr.No.  Insulation Classes  Maximum permissible temperature (0C) Insulating Material 1 Class-Y or O  900 Cotton, silk, paper, press board, wood, cellulose-, PVC, VIR. (Cotton, silk, ... adhesive coating.  7 Class- C  Over 1800 Porcelain, ceramics, glass, quartz. 

Description : Describe Effect of misalignment of direct coupled drives.

Last Answer : Following are the effects of misalignment of direct coupled drives:- 1. There will be excess vibrations. 2. Increase in noise level. 3. Increases in friction loss. 4. The shaft will bent. 5. There ... stresses on coupling & shaft. 13. Early wear & tear of both driving & driven machine.

Description : List routine tests to be conducted on 3 phase transformer as per 1S-2026-2011. 

Last Answer : Following tests are conducted/carried out on Transformer as per IS 2026 Routine tests of transformer include:- 1. Winding resistance measurement.(Both HV and LV winding ) 2. Measurement of ... Tests on on-load tap-changer, where appropriate. 11. To check against leakages through gaskets.

Description : List any four internal causes for abnormal operation of electrical equipment’s. 

Last Answer : Internal causes:- 1. Open circuit 2. Short circuit 3. Earth fault 4. Loose connection 5. Deposit of dirt and dust near ventilation passage 6. Low insulation resistance 7. Improper maintenance 8. Poor ... problems 13. Failure of cooling system 14. Excess wear and tear of internal parts 15. Ageing.

Description : Prepare troubleshooting chart for transformer as per IS- 10028-1981 (4 trouble) and Induction motor (4 troubles). 

Last Answer : Troubleshooting chart for I.M. :-  Sr.No Type of fault/abnormal conditions/Troubles Causes Remedies 1 Motor fails to start or not accelerate (Faults in starting supply ... 1.Unequal terminal voltage. 2. Single phase operation 3.Unbalanced voltage Rectify the Cause

Description : Describe the factors affecting preventive maintenance schedule. 

Last Answer : Following factors affect the PM schedule:- 1. Non availability of spares & raw material. 2. Non availability of tools, trackless, jacks, fixture required for PM. 3. Non availability of trained & skilled ... the work is held up for certain period. This is also a cause of disturbing a PM schedule.

Description : List any eight contamination agents of the transformer oil. 

Last Answer : The insulating oil gets contaminated when the following impurities are present in oil. 1. Presence of dissolved moisture content. 2. Presence of water content. 3. Presence of dissolved gases ... sulpher content 9. Presence of acetones content. 10. Presence of dissolved oil decay products content