Purpose of Local breaker back-up relay; type -CTIG

1 Answer

Answer :

To safe guard against the drastic consequences of failure to clear faults rapidly, many power supply authorities install 2 independent systems of protection for major transmission lines. There remains however the possibility of the circuit breaker itself failing to operate and this hazard is traditionally covered by remote breaker back-up.; CTIG relay is a 3 phase or 2 phase and earth fault instantaneous over current unit intended for use with a time delay to give back-up protection in the event of a circuit breaker failure. A particular feature of the CTIG relay is a fast reset, which enables the time delay to be set closer to the breaker trip-time. 

Related questions

Description : What is Local Breaker Back up protection? 

Last Answer : In case of local breaker fails to operate during fault due to mechanical failure this protection will protect the system from sever damage. It will trip all the other breakers in that bus after time delay. 

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

Last Answer : Answer: B

Description : Action carried out by the relay and circuit breaker during fault condition?

Last Answer : Answer: After the relay sensing the fault condition, relay operates and close the trip coils. The effect of this will be circuit breaker operate to open the contacts.

Description : Purpose of Over current & earth fault relay; type- CAG  

Last Answer : This relays are designed for instantaneous phase or earth fault protection and instantaneous high set over current protection.; A standard hinged-armature unit forms the basic movement for this relay. It consists an ... to the end of the core while the other arm to operate a set of contacts.  

Description : Purpose of Directional inverse Over current & earth fault relay; type- CDD

Last Answer : Directional phase or earth fault protection of ring-mains, parallel transformers, transformer feeders, parallel feeders etc., employing the time graded principle.; This relay comprises an inductive ... induction disc unit. The directional unit is normally provided with voltage polarising coils. 

Description : Purpose of over current relay (Inverse); type- CDG  

Last Answer : It is a self powered inverse time over current and earth fault relay, used for selective phase and earth fault protection in time graded systems for A.C. machines, transformers, feeders ... it rotates the driving torque increases and offsets the changing restraining torque of the control spring. 

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : What is the purpose of compressed air in SF6 breaker?

Last Answer : This used for drive for opening and closing of the contacts. (Arc quenching is taken care by SF6 gas) 

Description : What is the purpose of header breaker in water circuit?

Last Answer : The header breaker ensures oil pressure greater than that of water pressure always. Therefore there is no leak of water into oil.  

Description : What is the purpose of spring charging in 415 V breaker? 

Last Answer : If the breaker is to be closed and tripped manually the closing time and tripping time would vary from person to person. Also it would not be very fast. So spring charging is provided. It ... timings irrespective of the operator and its action is fast and closing and tripping time is very less. 

Description : Burden of a protective relay is the power (a) required to operate the circuit breaker (b) absorbed by the circuit of relay (c) developed by the relay circuit (d) none of the above

Last Answer : (b) absorbed by the circuit of relay

Description : For a traction transformer circuit breaker state: 1) Rated current and rupturing capacity 2) Any two tests it should be capable of withstanding 3) Overall tripping time and relay time.

Last Answer : Ans: 1) Rated current --- 750 A and Rupturing capacity --- 500 MVA  2) Any two tests it should be capable of withstanding --- Breaking test , Reclosing test , Endurance test ( any two )  3) Overall tripping time --- 0.14 sec and Relay time --- 0.04 sec 

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : Considering the function of the circuit shown in the illustration, what is the purpose of supplying the thrust lever potentiometers with both (+) and (-) 15 volts? EL-0095 A. To select which ... alternate voltage supply if the other fails. D. So as to automatically select the position of Relay #

Last Answer : Answer: B

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : What is the purpose of anti-pumping relay?

Last Answer : When closing signal is continuously existing even after the closing of the breaker the anti-pumping relay will be picked up and it will not allow the breaker to close back in case of tripping of the breaker. 

Description : A generator is prevented from becoming motorized by the use of a/an _____________. A. overspeed trip B. reverse power relay C. back pressure trip D. governor controls

Last Answer : Answer: B

Description : Why CT operated over load relay is using for loads of high acceleration time upto 30 seconds? How it getting back?

Last Answer : The saturable current transformers linearly transforms the current upto twice the set current, but above this value the transformer core gets saturated and the secondary current is proportionally less. Thus ... overload. When current reduces the core gets de-saturated, as material design is such. 

Description : Fuses placed in series with a thermal trip-type circuit breaker are used for _____________. A. time-delay protection B. short-circuit protection C. short duration surge protection D. sustained overload protection

Last Answer : Answer: B

Description : What is the type of 220 kV circuit breaker? 

Last Answer : 220 kV, SF6 breaker, single pole, puffer type. 

Description : The operating torque of the upper induction disc-type element, or timer element, of an AC reverse power relay is obtained from ____________. A. the main bus B. a separate battery source C. line voltage D. electromagnets

Last Answer : Answer: D

Description : A three-phase, induction-type motor experiences an open in one phase. Which of the listed automatic protective devices will prevent the machine from being damaged? A. Overspeed trip B. Thermal overload relay C. Three-pole safety switch D. Magnetic blowout coil

Last Answer : Answer: B

Description : Moldboard consists of following types : a) General purpose. c) Sod or breaker b) Stubble. d) All of the above

Last Answer : All of the above

Description : Which of the following busbar arrangement is generally employed in distribution system: a) One-and-half breaker arrangement b) Main and transfer arrangement c) Ring main distribution system d) Single busbar arrangement system

Last Answer : Ans: C

Description : Coast Guard Regulations (46 CFR) require each switchboard to have ___________. A. non-conductive deck covering at the frount B. non-conductive deck coverings at the rear C. a name plate for each circuit breaker D. all the above

Last Answer : Answer: D

Description : Before any work on electrical or electronic equipment is performed, which of the following precautions should be carried out? A. De-energize the applicable switchboard bus. B. Bypass the interlocks. C. ... supply circuit breaker in the open position. D. Station a man at the circuit supply switch.

Last Answer : Answer: C

Description : Which of the synchroscope illustrations depicts the appropriate direction of rotation and position for closing the circuit breaker when paralleling AC generators? EL-0053 A. A B. B C. C D. D

Last Answer : Answer: D

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B

Description : Which of the following actions must be carried out prior to closing the alternator circuit breaker according to the graph shown in the illustration? EL-0002 A. Increase the alternator voltage. B. Decrease the line voltage. C. Increase the line voltage. D. Decrease the line frequency.

Last Answer : Answer: A

Description : An alternator will fail to produce line voltage as a result of _____________. A. a closed circuit breaker B. oxidized slip rings C. improperly staggered brushes D. exciter generator failure

Last Answer : Answer: D

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : As shown in the illustration, 'B' is a ____________. EL-0058 A. single-pole, double-throw switch B. double-pole, single-throw switch C. double-pole, double-throw switch D. circuit breaker

Last Answer : Answer: C

Description : If an electric motor fails to start, you should FIRST check the _____________. A. phase sequence B. ampere load C. fuse or circuit breaker D. line frequency

Last Answer : Answer: C

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : After closing the circuit breaker to place two similar alternators in parallel, the NEXT step is to balance the _____________. A. power factor B. voltage load C. kilowatt load D. ampere load

Last Answer : Answer: C

Description : When an AC or a DC motor fails to start, the FIRST step in troubleshooting should be to check the ____________. A. motor windings for obvious opens B. motor controller leads for continuity C. fuse or circuit breaker D. motor controller leads for grounds

Last Answer : Answer: C

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : Prior to closing the breaker when paralleling two AC generators, the recommended practice is to have the frequency of the incoming machine _____________. A. slightly less than the line frequency B. the same as the line frequency C. slightly greater than the line frequency D. all of the above

Last Answer : Answer: C