Purpose of Over current & earth fault relay; type- CAG  

1 Answer

Answer :

This relays are designed for instantaneous phase or earth fault protection and instantaneous high set over current protection.; A standard hinged-armature unit forms the basic movement for this relay. It consists an operating coil mounted on a cylindrical iron core bolted to a frame at one end. This frame extends along the side of the coil, with its end forming a knife-edge on which the armature is pivotally mounted. The armature is 'L' shaped and pivoted at its corner so that one arm can be attracted to the end of the core while the other arm to operate a set of contacts.  

Related questions

Description : Purpose of Directional inverse Over current & earth fault relay; type- CDD

Last Answer : Directional phase or earth fault protection of ring-mains, parallel transformers, transformer feeders, parallel feeders etc., employing the time graded principle.; This relay comprises an inductive ... induction disc unit. The directional unit is normally provided with voltage polarising coils. 

Description : How generator earth fault relay works? 

Last Answer : 100% earth fault relay works on the principle involving monitoring of neutral side and line side components of 3rd harmonic voltages produced by generator in service. Since the machine is grounded with ... be detected by VL3 neutral displacement module, which is tuned to find frequency.   

Description : Will rotor earth fault relay operate for earth fault in main exciter winding or RCU Diode Bridge also? 

Last Answer : Yes. 

Description : Purpose of over current relay (Inverse); type- CDG  

Last Answer : It is a self powered inverse time over current and earth fault relay, used for selective phase and earth fault protection in time graded systems for A.C. machines, transformers, feeders ... it rotates the driving torque increases and offsets the changing restraining torque of the control spring. 

Description : Action carried out by the relay and circuit breaker during fault condition?

Last Answer : Answer: After the relay sensing the fault condition, relay operates and close the trip coils. The effect of this will be circuit breaker operate to open the contacts.

Description : Draw a neat sketch of earth fault protection of auxiliary circuit of electric loco. State the function of relay and isolating resistance.

Last Answer : Ans: Earth fault protection for auxiliaries in Loco: Function of relay: The earth fault occurring anywhere in the auxiliary circuit gets monitored by the relay which acts to trip the main CB. Function of ... star point to earth through a high resistance so that the relay operation is avoided.

Description : Which of the following statements is incorrect? (a) Station batteries are used to operate relay only (b) The lightning arresters are basically surge diverters (c) An impedance relay has maximum fault current when fault occurs near the relay (d) A high speed relay has an operation of 1 to 2 cycles

Last Answer : (a) Station batteries are used to operate relay only

Description : If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will be

Last Answer : If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will be 10

Description : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be

Last Answer : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be 10 A

Description : Why earth fault current of generator should not be reduced below 5A? 

Last Answer : To limit over voltage due to neutral shift.  

Description : Why not high resistance for earth fault than using grounding transformer & resistor 0.45 ohms?

Last Answer : It is mechanically unwide. Difficult to manufacture.  

Description : In the following partial sequence of mRNA, a mutation of the template DNA results in a change in codon 91 to UAA. The type of mutation is 88 89 90 91 92 93 94 GUC GAC CAG UAG GGC UAA CCG (A) Missene (B) Silent (C) Nonsense (D) Frame shit

Last Answer : Answer : B

Description : relay is preferred for phase fault on short transmission line. (a) Induction type (b) Reactance (c) Impedance (d) None of the above

Last Answer : (b) Reactance

Description : Why core balance CT is preferred over residual connected CT’s to sense earth fault in 6.6 kV feeders?

Last Answer : a) To avoid relay mal-operation due to CT saturation b) Better sensitivity is got. c) High pickup and TMS avoided in IDMT earth fault relay. 

Description : Purpose of Local breaker back-up relay; type -CTIG

Last Answer : To safe guard against the drastic consequences of failure to clear faults rapidly, many power supply authorities install 2 independent systems of protection for major transmission lines. There remains however the ... reset, which enables the time delay to be set closer to the breaker trip-time. 

Last Answer : CAG - Controller of Auditor General

Description : One feature is common to the following bodies. Find it out. Supreme Court, Election Commission, UPSC, Office of CAG – (1) They are advisory bodies. (2) They are extra constitutional bodies (3) They are controlled by legislature. (4) They are constitutional bodies.

Last Answer : (4) They are constitutional bodies Explanation: They are all constitutional bodies. Constitutional Bodies in India are formed by the Constitution which helps the Government to run properly ... the administration of specific functions. Some additional bodies help them by providing advisory functions.

Description : Vote-on-account means – (1) Statutory acceptance of planning bill (2) Statutory acceptance of money bill (3) Statutory acceptance of report of account checking and documents produced by CAG (4) Statutory acceptance of expenditure related to demands of grants till the passage of planning bill

Last Answer : (4) Statutory acceptance of expenditure related to demands of grants till the passage of planning bill Explanation: When the government needs to withdraw any money from the Consolidated Fund of India to ... Fund of India to meet the government's expenses is generally known as a vote-on-account.

Description : Vote on Account is meant for - (1) Vote on the report of CAG (2) To meet unforeseen expenditure (3) Appropriating funds pending due to passing of budget Budget (4) None of the above

Last Answer : (3) Appropriating funds pending due to passing of budget Explanation: The Vote on Account is the Special Provision given to the government to obtain the vote of Parliament to withdraw Money when the budget for the new financial year is not released or the elections are underway.

Description : Who appoints the Finance Cornmission in India? (1) Governor, R.B.I. (2) CAG of India (3) President of India (4) Central Finance Minister

Last Answer : (3) President of India Explanation: Article 280 of the Constitution of India requires the Constitution of a Finance Commission every five years, or earlier. It is established by President of ... other members to be appointed by the president. The first finance commission was established in 1951.

Description : If a relay fails to operate for a fault within its reach, it is said to

Last Answer : If a relay fails to operate for a fault within its reach, it is said to Under reach

Last Answer : Reactance relay is preferred for phase fault on short transmission line.

Description : What is the difference between over voltage relay and over current relay?

Last Answer : A:The current increases not only for over voltages but also for under voltage(As most of the loads are non-linear in nature). So,the over voltage protection & over current protection are completely ... , for a better protection of the system.It should have both over voltage & over current relay.

Description : When voltage increases then current also increases then what is the need of over voltage relay and over current relay? Can we measure over voltage and over current by measuring current only?

Last Answer : No. We can't sense the over voltage by just measuring the current only because the current increases not only for over voltages but also for under voltage (As most of the loads are non-linear in ... So, for a better protection of the system. It should have both over voltage & over current relay.

Description : What is the advantage of CMM relay over normal Inv. O/C current relay?

Last Answer : Inv. O/C relay under protects at low current and over protects at high currents. CMM: accounts for both +ve and -ve sequence currents i.e. Single phasing / unbalance supply conditions ... closely matched to motor heating characteristic. So it is better than thermal overload relay also. 

Description : Why IDMT over current relay is always used as backup?

Last Answer : Because setting has to be 200% to emergency loading and TMS be large to grade with feeder. Therefore very slow for internal faults/terminal faults/uncleared LV faults. 

Description : What is the characteristic of inverse time over current relay?  

Last Answer : If the fault current increases the time of the operation of the relay will be decreases.  

Description : When voltage increases then current also increases then why we need of over voltage relay and over current relay? Can we measure over voltage and over current by measuring current only?

Last Answer : No. We cannot sense the over voltage by just measuring the current only because the current increases not only for over voltages but also for under voltage (As most of the loads are non-linear in ... , for a better protection of the system. It should have both over voltage & over current relay.

Description : Inverse definite minimum time lag relay is also called ___________ (A) pilot relay. (B) differential relay. (C) over current relay. (D) directional overcurrent relay.

Last Answer : Ans: B Inverse definite minimum time lag relay characteristic is inverse but minimum time is fixed. The operating time is inversely proportional to the magnitude of actuating quantity.

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : Considering the function of the circuit shown in the illustration, what is the purpose of supplying the thrust lever potentiometers with both (+) and (-) 15 volts? EL-0095 A. To select which ... alternate voltage supply if the other fails. D. So as to automatically select the position of Relay #

Last Answer : Answer: B

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : What is the purpose of anti-pumping relay?

Last Answer : When closing signal is continuously existing even after the closing of the breaker the anti-pumping relay will be picked up and it will not allow the breaker to close back in case of tripping of the breaker. 

Description : The inverse definite mean time relays are used for over current and earth fault protection of transformer against (a) heavy loads (b) internal short-circuits (c) external short-circuits (d) all of the above

Last Answer : (b) internal short-circuits

Last Answer : The inverse definite mean time relays are used for over current and earth fault protection of transformer against internal short-circuits.

Description : What is the purpose of the earth fault indication on the switch board?

Last Answer : It detects and indicates phase to earth fault on a circuit.

Description : When earth fault occurs: a) voltage potential at the earth mat increases due to grounding b) voltage potential at the earth mat decreases due to grounding c) voltage potential at the earth mat remains zero irrespective of fault d) none of the above

Last Answer : Ans: A

Description : Why 2 types of earth fault relays in 6.6 kV side of transformers?

Last Answer : I – Trips 6.6 kV breakers only. It gives primary protection for 6.6 kV bus bars. I1 – Trips the both HT and LT breakers. It acts as a backup to ref and also acts as backup to bus bar earthfault relay. 

Description : Moisture absorbed in the windings or condensed on the surface of electrical machinery insulation ________. A. is good for long term preserving since most insulation is organic and contains some amount B. ... D. reduces the amount of current supplied or drawn by the machine so horsepower is limited

Last Answer : Answer: B

Description : Will main generator differential relay pick up for generator earth faults? 

Last Answer : No earth fault current limited to 5A, while differential setting is 10%. 

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : Which of the listed procedures is the best way to tell if a motor has become overloaded? A. Measure the current flow and compare it with the motor full load current flow as shown on the nameplate. ... Watch for telltale signs of smoke coming from the motor. D. Periodic opening of the O/L relay coil

Last Answer : Answer: A

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D