Why under voltage tripping of motor is incorporated in motor feeder breakers? 

1 Answer

Answer :

The under voltage can occur in case of bus fault. If the motors are kept connected they will feed the fault which may cause the damage. Due to the back feeding from the motor the motor will slow down very fast. Hence process system will come to halt very fast. (In case pht motor will not rotate for the designed 3 minute period in case of bus under voltage).  

Related questions

Description : The purpose of a short circuit forcing module (short time trip) installed in a branch line is to provide ____________. A. high speed clearance of low impedance short circuits in the branch B. ... C. isolation of short circuits by selective tripping of branch circuit breakers D. all of the above

Last Answer : Answer: D

Description : . If the power distribution system shown in figure 2-22 uses selective tripping, what is the time delay rating for each of the circuit breakers shown?

Last Answer : CB1-long time delay; CB2, CB3-short time delay; CB4 through

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Which of the listed precautions should be taken when cleaning the internals of a motor with compressed air? A. Open the machine on both ends so as to allow the air and dust to escape. B. Be certain that the ... panel. C. Be certain that the air is clean and as dry as possible. D. All of the above.

Last Answer : Answer: D

Description : What are the protections provided for motor feeder?  

Last Answer : Ith - Thermal over load I2S - Unbalance load I0S - Earth fault protection I1t - Stalling protection I1Inst. - Short circuit protection 

Description : The size of the feeder is determined primarily by (A) the current it is required to carry. (B) the percent variation of voltage in the feeder. (C) the voltage across the feeder. (D) the distance of transmission.

Last Answer : Ans: A Size of conductor depends upon amount of current flow.

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : The timer element of a reverse power relay cannot be energized unless _____________. A. the power flow is the same as the tripping direction B. the power flow is the opposite to the tripping direction C. the movement of the disk is damped by a permanent magnet D. one generator is motorized

Last Answer : Answer: A

Description : In addition to testing the calibration of a circuit breaker, maintenance should include all of the following EXCEPT ______________. A. changing out of magnetic elements and thermal heaters yearly B. ... for loose or missing parts D. making sure foreign matter does not block tripping element

Last Answer : Answer: A

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : The timer element of a reverse power relay cannot be energized unless _____________. A. one generator is fully motorized B. the movement of the disk is damped by a permanent magnet C. the power flow is the same as the tripping direction D. the power flow is the opposite to the tripping direction

Last Answer : Answer: C

Description : Why breaker tripping is prohibited on very low pressure?  

Last Answer : The efficiency with which the arc quenching is taking place in the breaker depends on the air pressure. So if the air pressure is low effective arc quenching will not take place which will result in damage of CB. Hence the tripping of the breaker at very low air pressure is prevented.  

Description : Which of the following equipment, for regulating the voltage in distribution feeder, will be most economical ? (a) Static condenser (b) Synchronous condenser (c) Tap changing transformer (d) Booster transformer

Last Answer : (d) Booster transformer

Description : Transmitted power remaining the same, if supply voltage of a D.C. 2-wire feeder is increased 100 percent, saving in copper is (a) 25 percent (b) 50 percent (c) 75 percent (d) 100 percent

Last Answer : (b) 50 percent

Description : In accordance with Coast Guard Regulations (46 CFR), a steering gear feeder circuit from the emergency switchboard or alternate power supply must have the capacity for continuous operation of the rudder 15° side to side in not more than 60 seconds for a A. 1/4 hour B. 1/2 hour C. 1 hour D. 2 hours

Last Answer : Answer: B

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : The electrical schematic shown in the illustration indicates the lighting feeder circuit is _____________. EL-0014 A. three phase, 450 volt, and 60 cycle B. three phase, 120 volt, and 60 cycle C. single phase, 120 volt, and 60 cycle D. not specified

Last Answer : Answer: A

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. main bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : What are the types of graded used in line of radial relay feeder?

Last Answer : Definite time relay and inverse-definite time relay.

Description : As shown in the illustration, a 'pitch cutback' feature is incorporated in the system. This circuit reduces pitch amount to prevent engine overload when it senses ____________. EL-0095 A. pitch error of ... servo' C. excessive propeller speed or fuel to either engine D. only one engine on the line

Last Answer : Answer: C

Description : Insulation resistance of high voltage circuit breakers is more than (a) 1 mega ohms (b) 10 mega ohms (c) 100 mega ohms (d) 500 mega ohms

Last Answer : (c) 100 mega ohms

Description : Low voltage circuit breakers have rated voltage of less than___________-. A. 220 V B. 400V C. 1000 V D. 10,000 V.

Last Answer : Low voltage circuit breakers have rated voltage of less than 1000 V.

Last Answer : Insulation resistance of high voltage circuit breakers is more than 100 mega ohms.

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : You can determine if a circuit breaker has tripped by ________________. A. examining the position of the handle B. checking for which of the breakers is warm C. looking for a burned-out link D. all of the above

Last Answer : Answer: A

Description : A 'dead front' switchboard is one _____________. A. without switches on it B. with insulated switches and no exposed terminals C. without circuit breakers D. without safety hand rails nor rubber mats

Last Answer : Answer: B

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : What are different types of circuit breakers employed in thermal power plant?

Last Answer : Answer: For low voltage operation 415/220V vacuum circuit breakers or air break circuit breakers are employed. For voltage ratings about 6.6kV and beyond SF6 circuit breakers are employed.

Description : What are different types of circuit breakers employed in thermal power plant?

Last Answer : For low voltage operation 415/220V vacuum circuit breakers or air break circuit breakers are employed. For voltage ratings about 6.6kV and beyond SF6 circuit breakers are employed.

Description : Why Isolation switches are provided along with the circuit breakers?

Last Answer : Isolation switches are provided for separating the disconnected element from the live portion of the system for the purpose of safety

Description : Air Blast Circuit Breakers Advantages Disadvantages

Last Answer : Air Blast Circuit Breakers Advantages Disadvantages In air blast circuit breakers, compressed air at a pressure of 20-30 kg/cm2 is employed as an arc quenching medium. Air blast circuit breakers ... air blast circuit breaker current chopping problem exists There is a problem of re-striking voltage

Description : Why we need isolation transformers in power circuit ? why cant we use breakers to isolate?

Last Answer : In Isolation transformer is used, if there is change in parameter values of any side, the other side parameters will remain unchanged.

Description : How direct tests are conducted in circuit breakers?

Last Answer : Using a short circuit generator as the source. Using the power utility system or network as the source.

Description : State the different types of circuit breakers.

Last Answer : Air ,oil,vacuum circuit breakers.

Description : Write the classifications of test conducted on circuit breakers.

Last Answer : Type test Routine test Reliability test Commissioning test

Description : Write the classification of circuit breakers based on the medium used for arc extinction?

Last Answer : Air break circuit breaker Oil circuit breaker Minimum oil circuit breaker Air blast circuit breaker SF6 circuit breaker Vacuum circuit breaker

Description : What is the significance of SF6 gas pressure in 6.6kV breakers?

Last Answer : Density gauge Green – correct SF6 pressure (3 –3.5bar) Yellow – pressure for breaking system fault current (refilling should be done) Red – SF6 pressure less than 2 bar, which indicates leak in the system. 

Description : What are the protections provided in PMCC circuit breakers?

Last Answer : 1. IDMT O/C (CDG 34). 2. IDMT E/F (CDG 11).  3. Under voltage (40% of 110V). 

Description : What FCN was implemented to avoid reactor trip on 220V-DC failure of PHT and PPP breakers?

Last Answer : The breaker close position supervision relay VAA 21 is changed by VAJC type, contacts position do not change if 220V-DC is lost now.

Description : What is the difference in action of lock out pressure signal on 6.6 kV and 220 kV breakers?

Last Answer : When lock out signal comes to 6.6 kV breakers the breaker will trip. Where as in case of 220 kV breakers the breaker will not trip. If the breaker is open it will be open only and can not be closed. If it is in closed condition it will be closed.

Description : What type breakers are provided in 6.6 kV buses?

Last Answer : ABB. Make, SF6 gas, 1250A and 2000A capacity circuit breakers are provided in 6.6 kV buses. 

Description : Which of the following actions must be carried out before a voltage tester can be used to test the three line fuses to a three-phase motor? A. The fuses must be removed from the circuit. B. The ... disconnected and tagged. D. Nothing need be done as long as the motor is running under a light load.

Last Answer : Answer: B