A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : - 

a) 16/9 b) 4 / 3 c) 3/4 d) 9 /16

1 Answer

Answer :

 A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  9 /16

Related questions

Description : 42 The efficiency of a transformer will be maximum when A. copper losses = hysteresis losses B. Hysteresis losses = eddy current losses C. Eddy current losses = copper losses D. Copper losses = iron losses

Last Answer : D. Copper losses = iron losses

Description : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

Last Answer : A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is 70.7%

Description : 5 The efficiency of a transformer is maximum when A. It runs at half full load B. it runs at full load C. its Cu loss equal iron loss D. it runs over load

Last Answer : C. Its cu loss equal iron loss

Description : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is :  (A) 7000 W (B) 6000 W (C) 8000 W (D) 4000 W

Last Answer : At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is : 6000 W

Description : The efficiency of a transformer is mainly dependent on (A) core losses. (B) copper losses. (C) stray losses. (D) dielectric losses.

Last Answer : Ans: A Core loss has prominent value over other losses

Description : 40 No load test on a transformer is carried out to find A. Copper loss B. magnetising current C. Magnetising current and loss D. Efficiency of the transformer

Last Answer : C. Magnetising current and loss

Description : 22 No load test on a transformer is carried out to find A. copper loss B. magnetising current C. Magnetising current and no load loss D. Efficiency of the transformer

Last Answer : C. Magnetising current and no load loss

Description : 48.During light loads, the transformer efficiency is low because A. Secondary output is low B. Transformer losses are high C. Fixed loss is high in proportion to the output D. Cu loss is small

Last Answer : C. Fixed loss is high in proportion to the output

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : During short circuit test iron losses are negligible because A. The current on secondary side is negligible B. The voltage on secondary side does not vary C. The voltage applied on primary side is low D. Full-load current is not supplied to the transformer

Last Answer : C) the voltage applied on primary side is low

Description : Auto-transformer makes effective saving on copper and copper losses, when its transformation ratio is?

Last Answer : Auto-transformer makes effective saving on copper and copper losses, when its transformation ratio is approximately equal to 1.

Description : A 150 kW electric motor has an efficiency of 92 %, when it operates at full load. Calculate the losses in the machine.  (A) 92 kW (B) 150 kW (C) 163 kW (D) 13 kW 

Last Answer : efficiency  -output /input * 100 150/0.92----------163(input) losses-----(163--150)  ---------13kw.

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : [53] The iron loss of the transformer is negligible during short circuit test because A. The entire input is just sufficient to meet Cu losses only B. Flux produced is a small fraction of the normal flux C. Iron core becomes fully saturated D. Supply frequency is held constant

Last Answer : B. Flux produced is a small fraction of the normal flux

Description : 43 The purpose of providing an iron core in a transformer is to A.Provide support to windings B. Reduce hysteresis loss C. decrease the reluctance of the magnetic path D. reduce eddy current losses

Last Answer : C. Decrease the reluctance of the magnetic path

Description : 73 The full load copper loss of a transformer is 1600W. At half-load the copper loss will be A. 6400W B. 1600W C. 800W D. 400W

Last Answer : D. 400W

Description : Full load copper loss in a transformer is 1600 watts. At half load the copper loss will be: A) 6400 watt B) 1600 watt C) 800 watt D) 400 watt

Last Answer :  Full load cupper loss in a transformer is 1600 watts. At half load the cupper loss will be: 400 watt

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Last Answer : The full-load copper loss of a trans¬former is 1600 W. At half-load, the copper loss will be 400 W.

Description : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

Last Answer : A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is 87.8%

Description : A transformer operates 24 hours day at full -load. It's full -load efficiency is :  (A) equal all day efficiency (B) more than all -day efficiency (C) less than all -day efficiency (D) equal to maximum efficiency

Last Answer : A transformer operates 24 hours day at full -load. It's full -load efficiency is : equal all day efficiency 

Description : What will be the efficiency when the transformer operates at unity power factor and 60% of full load 

Last Answer : What will be the efficiency when the transformer operates at unity power factor and 60% of full load 96.5%

Description : A 50 KVA transformer has iron loss 2 kW on full load. Calculate its iron loss at 75% of full load.

Last Answer : Iron loss is dependent on voltage and independent of load. Hence iron loss at 75% of Load = Iron loss at full load = 2 kW

Description : In an actual transformer the iron loss remains practically constant from no load to full load because?

Last Answer : In an actual transformer the iron loss remains practically constant from no load to full load because core flux remains practically constant.

Description : 64)During the short-circuit test on a small transformer the frequency is increased from 50-200Hz. The copper losses will increase by a factor of A. 16 B. 4 C. 1 D. 1/4

Last Answer : A) 16

Description : 45 The function of conservator in a transformer is A. To protect against internal fault B. To reduce copper as well as core losses C. To cool the transformer oil D. To take care of the expansion and contraction of transformer oil due to variation of temperature of surroundings

Last Answer : D. To take care of the expansion and contraction of transformer oil due to variation of temperature of surroundings

Description : 8 The transformer core is laminated to A. Reduce the copper losses B. Reduce the core losses C. Reduce the eddy current losses D. None of the above

Last Answer : C. Reduce the eddy current losses

Description : 7 The main advantage of auto transformer over a two winding transformer is A. Hysteresis losses are reduced B. Saving in winding material C. Copper losses are negligible D. Eddy losses are totally eliminated

Last Answer : A) hysteresis losses is reduced

Description : For a constant load current, transformer maximum efficiency occurs at   (a) any power factor (b) zero power factor leading (c) zero power factor lagging (d) unity power factor 

Last Answer : For a constant load current, transformer maximum efficiency occurs at unity power factor 

Last Answer : An ideal transformer will have maximum efficiency at a load such that copper loss equal to iron loss.

Description : For a transformer, operating at constant load current, maximum efficiency will occur at?

Last Answer : For a transformer, operating at constant load current, maximum efficiency will occur at unity power factor.

Description : Which losses in a transformer varies significantly with load  a. Hysteresis losses b. Eddy current losses c. Copper losses d. Core losses 

Last Answer : Which losses in a transformer varies significantly with load Copper losses

Description : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are?

Last Answer : In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are hysteresis and eddy current losses.

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : Why are iron losses considered as constant losses in transformer?

Last Answer : Iron losses depend on supply frequency and flux density in the core. For all normal operations, the frequency of flux reversals which is same as supply frequency is constant and the value of flux density ... . Hence iron losses remain constant under all load conditions. i-e from no-load to full-load

Description : A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

Last Answer : A

Description : Which of the following losses is/are present in every direct current generator armature? A. Winding copper loss B. Core eddy current loss C. Magnetic hysteresis loss D. All of the above.

Last Answer : Answer: D

Description : The term power budgeting refers to ∙ A. the cost of cable, connectors, equipment and installation ∙ B. the loss of power due to defective components ∙ C. the total power available minus the attenuation losses ∙ D. the comparative costs of fiber and copper installations

Last Answer : C. the total power available minus the attenuation losses

Description : 70] Silicon steel used in laminations mainly reduces A. Hysteresis loss B. Eddy current losses C. Copper loss D. All of the above

Last Answer : A. Hysteresis loss

Description : The armature of a dc machine is laminated to reduce: (A) Eddy current loss (B) Hysteresis loss (C) copper losses (D) friction and windage losses

Last Answer : Ans: A Thinner the laminations, greater is the resistance offered to the induced e.m.f., smaller the current and hence lesser the I2R loss in the core.

Last Answer : Transformer efficiency is maximum when copper losses are equal to iron losses.

Description : Select insulating materials for following parts : (i) Insulation between heating element and base plate of electric iron. (ii) Insulation used over copper or aluminium conductor used for making coils. (iii) Transformer bushings. (iv) Insulation between transmission line and pole.

Last Answer : Parts Insulating Materials  Insulation between heating element and base plate of electric iron. Mica Insulation used over copper or aluminium conductor used for making coils.  ... Transformer bushings Porcelain  Insulation between transmission line and pole. Porcelain

Description : Iron losses in a D.C. machine are independent of variations in (a) speed (b) load (c) voltage (d) speed and voltage

Last Answer : Ans: b

Description : List the losses occurring in transformer.

Last Answer : (1) Iron losses: (a) Eddy current losses (b) Hysteresis losses (2) Copper losses

Description : Eddy current losses in transformer cores can be reduced by the use of  1. Solid cores  2. Laminated cores  3. Ferrites  Select the correct answer using the codes given below : (a) 2 and 3 only (b). 1 and 2 only (c) 1 and 3 only (d) 1, 2 and 3

Last Answer : Eddy current losses in transformer cores can be reduced by the use of  1. Solid cores  2. Laminated cores  3. Ferrites  Select the correct answer using the codes given below : (a) 2 and 3 only (b). 1 and 2 only (c) 1 and 3 only (d) 1, 2 and 3

Description : When a source is delivering maximum power to a load, the efficiency of the circuit is always (a) 50% (b) 75% (c) 100% (d) Depends on the circuit parameters

Last Answer : When a source is delivering maximum power to a load, the efficiency of the circuit is always 50%

Description : Which of the following methods does not take into account the maximum temperature rise under variable load conditions ? (a) Equivalent power method (b) Equivalent current method (c) Method of average losses (d) Equivalent torque method

Last Answer : (c) Method of average losses

Description : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: A. 4 kVA B. 0.25 kVA C. 16 kVA D. 8 kVA

Last Answer : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: 16 kVA

Description : 74)Power transformers are generally designed to have maximum efficiency around A. No load B. Half load C. Near full load D. 10% overload

Last Answer : C. Near full load

Description : Power transformers should be designed to have maximum efficiency (a) at one-fourth load (b) at one-half load (c) at or near full load (d) any of the above

Last Answer : (c) at or near full load