Explain the behavior of generator when operating alone and operating parallel with
grid.

1 Answer

Answer :

Generator operating alone.
a) The power factor of generator depends on load power factor.
b) The terminal voltage decreases when generator is loaded.
c) Governor decides the frequency of generator.
d) Increase in excitation increases the terminal voltage of the generator.

Generator parallel with grid.
a) If we increase the steam input to the generator the frequency of the generator will not change. It will remain practically constant as same as grid frequency. That is grid decides the frequency of the generator.
b) Increase in the excitation will not increase the terminal voltage. Instead the reactive power out put of the generator increases. This reactive power supplies for the magnetizing current of motors, transformers and etc.
c) Increase in the steam input increases the active power of the generator.
d) If generator is under excited it will draw leading reactive current from the grid.

Related questions

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : If three AC generators are operating in parallel, and one of them were to 'pull out' of synchronism with the other two generators, the ____________. A. normally operating AC generators will ... AC generators will overspeed and unload D. AC generator pulling out of synchronism will become motorized

Last Answer : Answer: B

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ahead or behind ... as it rotates. This co A. hunting B. direct coupling C. peaking D. harmonic coupling

Last Answer : Answer: A

Description : If the driving torque, such as that produced by a diesel engine, creates pulsations when coupled with a synchronous generator operating in parallel; the generator rotor may be periodically pulled ... windings B. direct coupling C. increase governor speed droop D. decreasing governor speed droop

Last Answer : Answer: A

Description : A triac thyristor functions as a control device and is basically ________________. A. two NPN transistors in parallel with a common base lead B. a diode in series with a temperature sensitive capacitor C. two ... -back SCR's with a common gate lead D. a triode tube with an extra heavy grid element

Last Answer : Answer: C

Description : Consider the following statements:  1. A grid connected induction generator always supplies leading reactive power to the bus  2. An overexcited synchronous motor draws current at a lagging power factor  3. An underexcited synchronous ... (c) 1, 3 and 4 are correct (d) 1, 2, 3 and 4 are correct 

Last Answer : Consider the following statements:  1. A grid connected induction generator always supplies leading reactive power to the bus  2. An overexcited synchronous motor draws current at a lagging power factor  3. An underexcited ... correct (c) 1, 3 and 4 are correct (d) 1, 2, 3 and 4 are correct 

Description : What will be the frequency of a three-phase, six pole, AC generator operating at 1800 revolutions per minute? A. 60 hertz B. 90 hertz C. 120 hertz D. 180 hertz

Last Answer : Answer: B

Description : On electrical generators one of the bearings is isolated from the bedplate. This insulating block should not be painted and must be kept clean to ___________. A. protect operating personnel from shock ... the prime mover as it warms up D. eliminate shaft currents to prevent damaging the bearings

Last Answer : Answer: D

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : A flickering ground detection lamp on a DC system would indicate a _____________. A. multiple-ground condition in the distribution system B. ground in an armature coil of an operating machine C. ground in a motor accompanied with a short D. short between two adjacent bars of the generator commutator

Last Answer : Answer: B

Description : As shown in the illustration, operating the reversing switch will change the polarity of the ______________. EL-0101 A. generator field B. generator armature C. motor armature D. all of the above

Last Answer : Answer: D

Description : The voltage of an operating AC turbogenerator is raised or lowered by adjusting the _____________. A. exciter generator governor controls B. synchronizing switch C. phase sequence switch D. generator field exciter

Last Answer : Answer: D

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : To increase the frequency of an operating AC generator, you should ____________. A. increase the field excitation B. decrease the field excitation C. increase the number of magnetic poles D. increase the speed of the prime mover

Last Answer : Answer: D

Description : The 'function generator' of the control circuit illustrated _______________. EL-0095 A. can be programmed to produce a non-linear output for a linear input depending on operating conditions B. is used for ... which or how many engines are needed for a required vessel speed D. all of the above

Last Answer : Answer: A

Description : Since the characteristics of the device shown in figure 'A' of the illustration includes a stable voltage and low current while operating, it can be suitably used in _____________. EL-0065 A. oscillators ... . class A and B amplifiers C. generator rectifier and filtering supplies D. all of the above

Last Answer : Answer: A

Description : Induction generator a) can not work in isolation b) can work in isolation c) should work in parallel with synchronous generators d) any of the mentioned

Last Answer : Ans: C

Description : Coast Guard Regulations (46 CFR) require that each alternating current generator arranged for parallel operation shall be provided with _____________. A. more than one means of excitation B. individual circuit fuses C. a high back-pressure trip D. a reverse-power trip

Last Answer : Answer: D

Description : A vessel is equipped with two ship's service generators. Generator #1 is rated at 900 kw and generator #2 is rated at 600 kw. During parallel operation, with a hotel load of 1,000 kw, what should be the kw load on generator #2? A. 100 kw B. 400 kw C. 500 kw D. 600 kw

Last Answer : Answer: B

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : Which of the following should be the FIRST step in removing a generator from parallel operation? A. Trip the generator off the switchboard. B. Turn off all electrical equipment. C. Remove the load from the 'off going' generator. D. Increase the cycles of the generator staying on the line.

Last Answer : Answer: C

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : A shunt-wound DC generator is one in which the shunt field windings are in parallel with the _____________. A. commutator B. brushes C. armature D. all of the above

Last Answer : Answer: D

Description : A DC shunt generator has its field windings connected in _____________. A. series with the series windings B. parallel with the field rheostat C. series with the armature windings D. parallel with the armature windings

Last Answer : Answer: D

Description : Grid lines are parallel to  (A) Magnetic meridian of the central point of the grid  (B) Line representing the central true meridian of the grid  (C) Geographical equator  (D) None of these

Last Answer : (B) Line representing the central true meridian of the grid

Description : Chandigarh is a city which has roads generally parallel or perpendicular to each other. The ideal water supply system in such a city should be a. Dead and system b. Grid Iron system* c. Ring system d. Any of them

Last Answer : b. Grid Iron system*

Description : The load sharing characteristics of two diesel alternators operating in parallel are directly related to the setting of their governors' ____________. A. load limit B. idle speed C. speed limit D. speed droop

Last Answer : Answer: D

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : If the excitation of an alternator operating in parallel is decreased below normal, its _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. ampere load will be greatly increased D. kilowatt load will be greatly decreased

Last Answer : Answer: B

Description : Severe vibration, accompanied by flashover at the collector rings of an alternator operating in parallel, is a symptom of _____________. A. reverse current motorization B. loss of synchronism C. destructive overspeeding D. reversed polarity

Last Answer : Answer: B

Description : An alternator operating in parallel begins to vibrate severely and eventually trips out on the reverse power relay. The cause of the vibration was a result of ______________________. A. the ... C. the alternator was operating out of synchronism D. flashover at the alternator collector rings

Last Answer : Answer: C

Description : Which of the methods listed is used to maintain the division of load between two compound-wound, DC generators operating in parallel? A. The shunt fields are interconnected. B. The shunt ... generators are connected in series. D. The equalizer connection parallels the series fields of all machines.

Last Answer : Answer: D

Description : When two generators are on the line and are sharing the load equally, they are said to be operating in _____________. A. frequency B. series C. parallel D. resonance

Last Answer : Answer: C

Description : Equalization of the power factors of two alternators operating in parallel is accomplished _____________. A. manually, by adjusting the governor controls B. automatically, by automatic voltage regulators ... the output of current transformers D. automatically, by the designed action of the governors

Last Answer : Answer: B

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : If the energy input is significantly reduced to the prime mover of one shipboard alternator operating in parallel with others, that alternator will _____________. A. continue to operate at no load B. lose ... overspeed C. begin to motorize and then trip out D. slow down and operate at reduced load

Last Answer : Answer: C

Description : If field excitation is suddenly lost to an alternator operating in parallel, that alternator will _____________. A. supply excessive current to the bus B. operate at the same load, but with reduced voltage C. lose its load and tend to overspeed D. become overloaded and slow down

Last Answer : Answer: C

Description : Two AC generators of the same capacity are operating in parallel. One with a zero speed droop setting and the other with a 5% speed droop. If its capacity is not exceeded, the unit whose ... B. maintain the frequency of the system C. have poor sensitivity characteristics D. have poor power response

Last Answer : Answer: B

Description : A change in field excitation of an alternator operating in parallel will cause a change in its _____________. A. alternator frequency B. kilowatt load C. voltage output D. all of the above

Last Answer : Answer: C

Description : If the excitation is increased to one of two alternators operating in parallel, the _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. kilowatt load will be greatly increased D. ampere load will be greatly decreased

Last Answer : Answer: A

Description : To equalize the power factor of two alternators operating in parallel, the ____________. A. field excitation of both units is adjusted B. governors of both units are adjusted C. phase sequence is altered D. kilowatt load is evenly divided

Last Answer : Answer: A

Description : Which is a function of the voltage regulators used with AC generators? A. To cut out generators when they are no longer required. B. To cut in additional generators automatically as ... between generators operating in parallel. D. To divide reactive current between generators operating in parallel.

Last Answer : Answer: D

Description : The division of the kilowatt load between two AC generators operating in parallel is controlled by the settings and characteristics of the _____________. A. voltage regulators B. field rheostats C. reverse power relays D. prime mover governors

Last Answer : Answer: D

Description : Kilowatt load is divided between two AC generators operating in parallel by _____________. A. adjusting the governor controls B. varying the excitation voltage C. increasing both prime mover speeds simultaneously D. decreasing both prime mover speeds simultaneously

Last Answer : Answer: A