Explain clearly the three positions in 415 V breaker. 

1 Answer

Answer :

a. Service position: Power connections and control connections are available to the

breaker.

b. Test position: Power connections are cut off but control connections are available

to the breaker and it can be tested.

c. Disconnect position or rack out position: This is for maintenance of the breaker

and in this positions both the control and power connections are not available. 

Related questions

Description : What are the built in protections provided in 415 V breaker?  

Last Answer : a. DINF (making current magnetic release) This consists of a laminated magnetic circuit. This is placed under the lower current terminal pole. This is provided for all the three poles. It has a core that rotates ... by a lever. It is placed in front of the breaker. Setting range is 60% to 100%.  

Description : What is the purpose of spring charging in 415 V breaker? 

Last Answer : If the breaker is to be closed and tripped manually the closing time and tripping time would vary from person to person. Also it would not be very fast. So spring charging is provided. It ... timings irrespective of the operator and its action is fast and closing and tripping time is very less. 

Description : What are the types of cables used in 6.6 kV and 415 V system voltages? 

Last Answer : In 6.6 kV system AC (unearthed) grade having stranded aluminium conductors cables are used. Their insulation's are as follows. 1. XLPE - Crossed linked polyethylene insulation. 2. FRLS PVC - Fire ... V grade copper or aluminium stranded cables are used. Their insulations are HR PVC and FS type. 

Description : What are the interlocks between 415 V and 6.6 kV switch gear? 

Last Answer : 6.6 kV Breaker closed cannot rack in or out. Service lever cannot move while breaker closed. Breaker cannot be closed in in-between position. 415 V Breaker door cannot be opened when breaker is ... . Breaker cannot be closed in in-between position. Breaker closed cannot be rack in or out. 

Description : What is the difference between lockout of 6.6 kV and 415 V CB’s?

Last Answer : Voltage levels. Manual / auto reset. Lockout relays of 415 V breakers are all Electro-magnetic type. There is no mechanical latch. But in 6.6 kV it is of mechanical latch type relays.

Description : What are the protections used in 415 V Class II side?

Last Answer : LV to UPS 1. CTZM 2. 50 (instantaneous over current) 3. short circuit UPS to PMCC S & T 1. 51 RYB (inverse over current) 2. 27 (under voltage) 3. 51N (earth fault) From Class III to Class II tie CTZM at Class III and 51, 51N at Class II. 

Description : What are the protections used in Class III & Class IV 415 V LV side?  

Last Answer : Class III 415 V LV side 1. 51 (inverse over current) 2. 50 (instantaneous over current) 3. 27 (under voltage) 4. 51N (earth fault) 5. 64 (REF)  Class IV 415 V LV side 1. 51 RYB (inverse over current) 2. 51N (earth fault) 

Description : Why resistance grounding preferred for less than 33 kV and more than 415 V?

Last Answer : a) To limit the earth fault current for equipment safety else, high short ckt forces dislocate in windings/bus bars etc, b) Over voltage due to arcing ground reduced c) Permits earth fault protection (not possible in ungrounded system)

Description : A 100 kVA, 415 V(line), star-connected synchronous machine generates rated open circuit voltage of 415 V at a field current of 15 A. The short circuit armature current at a field current of 10 A is equal to the ... unit saturated synchronous reactance is  (A) 1.731 (B) 1.5 (C) 0.666 (D) 0.577

Last Answer : 0.6

Description : Brother A and B had some savings in the ratio 5:6. They decided to buy a gift for their sister, sharing the cost in the ratio 4:5. After they bought, A is left with three-fourth of his amount, while B is left with Rs.497. Then, the value of the gift is a) 215 b) 115 c) 315 d) 415 e) None of these

Last Answer : Answer: C Let the savings of A and B are 5x, 6x and the share cost of gift are 4y, 5y respectively. According to question, For A, 5x-4y=3/4×5x =>x=16y/5 For B, 6x-5y=497 =>6×16y/5-5y=497 =>y=35 Cost of gift=4y+5y=9×35 =315

Description : The winch shown in the illustration operates in any of the positions with the master switch in the 'lower' direction, but will not 'hoist' in any of the master switch hoist positions. Which of the listed faults ... '2M' in the power circuit may be badly corroded. D. Series relay 'FR' may be open.

Last Answer : Answer: A

Description : The 'function generator' of the control circuit illustrated _______________. EL-0095 A. can be programmed to produce a non-linear output for a linear input depending on operating conditions B. is used for ... which or how many engines are needed for a required vessel speed D. all of the above

Last Answer : Answer: A

Description : Explain The Working Principal Of The Circuit Breaker?

Last Answer : Circuit Breaker is one which makes or breaks the circuit. It has two contacts namely fixed contact & moving contact. Under normal condition the moving contact comes in contact with fixed contact thereby ... the open circuit Arc is extinguished by the Arc Quenching media like air, oil, vacuum etc.

Description : Explain the working principle of the circuit breaker

Last Answer : A:Circuit Breaker is one which makes or breaks the circuit.It has two contacts namely fixed contact & moving contact. Under normal condition the moving contact comes in contact with fixed contact thereby forming ... . Arc is extinguished by the Arc Quenching media like air, oil, vacuum, SF6 gas etc.

Description : T.V. transmission cannot cover a very large area because _____ A. The strength of T.V. waves is very limited B. Picture cannot be transmitted clearly after a specific distance C. The shape of the earth is spherical D. The air is not a good conductor of light and sound/waves

Last Answer : ANSWER: C

Description : T.V. transmission cannot cover a very large area because A. the strength of T.V. waves is very limited B. picture cannot be transmitted clearly after a specific distance C. the shape of the earth is spherical (Answer) D. the air is not a good conductor of light and sound/waves

Last Answer : C. the shape of the earth is spherical (Answer)

Description : How serious is a triglyceride reading of 415 in a senior?

Last Answer : Wow! My understanding is that it should be under 200. That would seem to be off the charts, but I also understand that the result should be taken in context with other readings, such as total cholesterol, ... does raise a red flag and your s/o should check with a physician to have other tests run.

Description : What is 415 round to the nearest 100?

Last Answer : 400

Description : Highest test partnership by a pair in test cricket history is 415 runs. A. Jayasuriya and Mahnama (SL Vs India) B. Sangakara and Jayawardene (SL Vs SA) C. Neil McKenzie and Gram Smith (SA Vs Bangladesh) D. Trott and Broad (Eng Vs Pak)

Last Answer : ANSWER: C

Description : Highest test partnership by a pair in test cricket history is 415 runs. A. Jayasuriya and Mahnama (SL Vs India) B. Sangakara and Jayawardene (SL Vs SA) C. Neil McKenzie and Gram Smith (SA Vs Bangladesh) D. Trott and Broad (Eng Vs Pak)

Last Answer : ANSWER: C

Description : Highest test partnership by a pair in test cricket history is 415 runs. A. Jayasuriya and Mahnama (SL Vs India) B. Sangakara and Jayawardene (SL Vs SA) C. Neil McKenzie and Gram Smith (SA Vs Bangladesh) D. Trott and Broad (Eng Vs Pak)

Last Answer : ANSWER: C

Description : Highest test partnership by a pair in test cricket history is 415 runs. A. Jayasuriya and Mahnama (SL Vs India) B. Sangakara and Jayawardene (SL Vs SA) C. Neil McKenzie and Gram Smith (SA Vs Bangladesh) D. Trott and Broad (Eng Vs Pak)

Last Answer : ANSWER: C

Description : The compression in steel (fS) at failure for Fe - 415 grade steel using stress-strain curve shall be [ A ] 0.87 fy [ B ] 0.75 fy [ C ] 0.45 fy [ D ] 0.55 fy

Last Answer : [ B ] 0.75 fy

Description : According to IS: 456-2000 the ultimate moment of resistance of a slab for Fe - 415 HYSD bars is; [ A ] Mu = 0.138 fck bd2 [ B ] Mu = 0.145 fck bd2 [ C ] Mu = 0.152 fck bd2 [ D ] Mu = 0.165 fck bd2

Last Answer : [ A ] Mu = 0.138 fck bd2

Description : The Minimum percentage of secondary steel in slabs for Fe- 415 grade steel should be __________ of Gross cross-section area [ A ] 0.12% [ B ] 0.15% [ C ] 0.20% [ D ] 0.25%

Last Answer : [ A ] 0.12%

Description : For Fe- 415 steel and M20grade concrete, the balanced percentage of steel is [ A ] 0.65% [ B ] 0.75% [ C ] 0.86% [ D ] 0.96%

Last Answer : [ D ] 0.96%

Description : The Minimum amount of steel for Main reinforcement in slab should be (Fe 415- grade of steel) [ A ] 0.12 percent of gross cross sectional area [ B ] 0.15 percent of gross cross sectional area [ C ] 0.20 percent of gross cross sectional area [ D ] 0.25 percent of gross cross sectional area.

Last Answer : [ A ] 0.12 percent of gross cross sectional area

Description : As per IS: 1139, permissible stress in compression steel reinforcement for High Yield strength deformed bars is [ A ] 140 N/mm2 [ B ] 190 N/mm2 [ C ] 230 N/mm2 [ D ] 415 N/mm2

Last Answer : [ B ] 190 N/mm2

Description : As per IS:1139, the characteristic yield strength for cold twisted deformed bars is [ A ] 250 N/mm2 [ B ] 415 N/mm2 [ C ] 500 N/mm2 [ D ] 550 N/mm2

Last Answer : [ C ] 500 N/mm2

Description : As per IS:1139, the characteristic yield strength for hot rolled High yield strength deformed bars is [ A ] 250 N/mm2 [ B ] 415 N/mm2 [ C ] 500 N/mm2 [ D ] 550 N/mm2

Last Answer : [ B ] 415 N/mm2

Description : Which of the following busbar arrangement is generally employed in distribution system: a) One-and-half breaker arrangement b) Main and transfer arrangement c) Ring main distribution system d) Single busbar arrangement system

Last Answer : Ans: C

Description : Coast Guard Regulations (46 CFR) require each switchboard to have ___________. A. non-conductive deck covering at the frount B. non-conductive deck coverings at the rear C. a name plate for each circuit breaker D. all the above

Last Answer : Answer: D

Description : Before any work on electrical or electronic equipment is performed, which of the following precautions should be carried out? A. De-energize the applicable switchboard bus. B. Bypass the interlocks. C. ... supply circuit breaker in the open position. D. Station a man at the circuit supply switch.

Last Answer : Answer: C

Description : Which of the synchroscope illustrations depicts the appropriate direction of rotation and position for closing the circuit breaker when paralleling AC generators? EL-0053 A. A B. B C. C D. D

Last Answer : Answer: D

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B

Description : Which of the following actions must be carried out prior to closing the alternator circuit breaker according to the graph shown in the illustration? EL-0002 A. Increase the alternator voltage. B. Decrease the line voltage. C. Increase the line voltage. D. Decrease the line frequency.

Last Answer : Answer: A

Description : An alternator will fail to produce line voltage as a result of _____________. A. a closed circuit breaker B. oxidized slip rings C. improperly staggered brushes D. exciter generator failure

Last Answer : Answer: D

Description : In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

Last Answer : Answer: B

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : As shown in the illustration, 'B' is a ____________. EL-0058 A. single-pole, double-throw switch B. double-pole, single-throw switch C. double-pole, double-throw switch D. circuit breaker

Last Answer : Answer: C

Description : If an electric motor fails to start, you should FIRST check the _____________. A. phase sequence B. ampere load C. fuse or circuit breaker D. line frequency

Last Answer : Answer: C

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A