What is the % overload allowed for TG and DG?

1 Answer

Answer :

For TG nil

For DG 110% for 2 hours. 

Related questions

Description : Why motoring should be prevented in TG and DG? 

Last Answer : In TG motoring prevented due to the turbine limitation otherwise last stage blade will fails. In DG motoring prevented, because of unburned fuel catches fire in DG. 

Description : When TG works as induction generator?

Last Answer : When excitation alone lost.  

Description : What are the materials used for TG rotor and blades?

Last Answer : TG rotor is made up of alloy steel and blades are made up of stainless steel.  

Description : Why we do 2 types of earthing on transformer i.e.: body earthing & neutral earthing, what is function. I am going to install a 5oo kva transformer & 380 kva DG set what should the earthing value?

Last Answer : The two types of earthing are Familiar as Equipment earthing and system earthing. In Equipment earthing: body (non conducting part) of the equipment should be earthed to safeguard the human ... earthing will be further classified into directly earthed, Impedance earthing, resistive (NGRs) earthing.

Description : What are the protections provided for DG?

Last Answer : 1. Differential protection (87). 2. Over speed of engine. 3. Reverse power protection (in LOCA condition time delay). 4. Low lubricating oil pressure. 5. Cooling water temperature high. 6. 6 ... 8. Emergency stops push button. In LOCA condition 4 - 8 protections are not permitted to operate. 

Description : What are stages of DG starting? 

Last Answer : 1. At start signal compressed air through solenoid valve passes over piston and rotates the shaft. 2. At speed >60-rpm ignition starts. 3. Closing of excitation starts at >800-rpm. 4. At speed of > 900-rpm rated speed and rated voltage signal starts. 5. Closing of over speed is at >1150-rpm. 

Description : What are the auxiliaries required for DG? 

Last Answer : 1. Starting air system. Components are compressor, air dryer, air receiver, solenoid valve for start control, pneumatic starting air valve, air distributor and injection valve at each cylinder. This system operates at ... one RTD each. 10. LCP is provided one each for each DG. 

Description : Why neutral breaker used in DG neutral grounding?

Last Answer : In case of high earth fault currents it is therefore normal practice to install a circuit breaker in the neutral of the generator in order to reduce the total fault clearance time. 

Description : Why in DG E/F protection, we do not open class IV CB’s or supply CB’s?

Last Answer : Delta of aux. Transformer prevents E/F currents from grid into DG neutral.  

Description : The lipoprotein with the fastest electrophoretic mobility and lowest TG content are (A) VLDL (B) LDL (C) HDL (D) Chylomicrones

Last Answer : Answer : C

Description : .If the DNA codons are ATG ATG ATG and a cytosine base is inserted at the beginning, then which of the following will result? (a) CAT GAT GAT G (b) A non-sense mutation (c) C ATG ATG ATG (d) CA TGA TGA TG

Last Answer : (a) CAT GAT GAT G

Description : .If the DNA codons are ATG ATG ATG and a cytosine base is inserted at the beginning, then which of the following will result? (a) CAT GAT GAT G (b) A non-sense mutation (c) C ATG ATG ATG (d) CA TGA TGA TG

Last Answer : (a) CAT GAT GAT G

Description : Shear modulus G is given by (a) G = t/g (b) G = g/t (c) G = Tg/t (d) G = T/g

Last Answer : (a) G = t/g

Description : Angle of twist of a circular shaft is given by a. GJ/Tl b. Tl/GJ. c. TJ/Gl. d.TG/Jl.

Last Answer : b. Tl/GJ.

Description : Specific drug therapy to lower serum triglycerides (TG) in a subject with normal LDL-cholesterol level is indicated: A. In all subjects with serum TG> 150 mg/dl B. In subjects with existing coronary artery disease and serum TG ... < 40 mg/dl and serum TG > 150 mg/dl D. Both 'B' and 'C' are correct

Last Answer : D. Both 'B' and 'C' are correct

Description : Where automatic restart does not present a hazard after a power failure, Coast Guard Regulations (46 CFR) require motor controllers for auxiliaries vital to the propelling equipment to be provided ... overload protection B. low voltage protection C. low voltage release D. reverse current protection

Last Answer : Answer: C

Description : If overloading a DC machine becomes necessary in an emergency, you should ____________. A. cool the machine with portable blowers and fans B. hold thermal overload relays open with blocks of ... the windings for cooling D. increase the residual magnetism value of windings to reduce eddy currents

Last Answer : Answer: A

Description : Which of the following statements is true concerning the motor controller diagram shown in the illustration? EL-0023 A. Terminal 'T2' is hot only on high speed. B. Both indicating lights will be lit on ... high speed operation only. D. 'L2' is always connected to 'T2' whenever the motor is running.

Last Answer : Answer: D

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : If a DC motor runs faster than designed, with all other conditions being normal, the possible cause could be a/an ______________. A. shorted shunt field coil B. open armature coil C. reversed commutating pole D. overload

Last Answer : Answer: A

Description : Component F in the illustrated device is for _________. EL-0033 A. short circut protection B. latching the trip unit closed after resetting the breaker C. overload protection D. providing a flexible connection between the input terminal G and the tripping unit E

Last Answer : Answer: C

Description : In the illustrated motor controller, the motor fails to start. A voltmeter reading between 1 and 6 reads line voltage, while the voltmeter reading between 2 and 6 reads 0 VAC. The problem is __________. EL- ... in the 'M' coil, 'Ma' contact/start switch or overload contacts D. fuse '10a' is blown

Last Answer : Answer: B

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0042 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : If a synchronous motor begins to vibrate severely and pull out of synchronism, the cause may be ____________. A. an overload B. an open in the field coils C. no exciter voltage D. all of the above

Last Answer : Answer: D

Description : An overload in which of the listed motors will result in the illumination of an indicating light at the propulsion control station alarm panel? A. Fuel pump motor B. Steering motor C. Condensate pump motor D. Forced draft blower motor

Last Answer : Answer: B

Description : In the illustration if the compressor fails to start but the condenser fan motor is running the problem is _______. EL-0043 A. no power between L1 and L2 B. the yellow wire is open at the freezer temperature control switch C. the overload is open D. the blue wire from the defrost heater is open

Last Answer : Answer: C

Description : In the illustration, the purpose of part B is to _________. EL-0033 A. increase resistance in series with the contacts as they close to prevent arcing B. create a magnetic field in the steel ... event of an overload D. provide ventilation to the contact when the breaker is close to rated capacity

Last Answer : Answer: B

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : The illustrated motor fails to start and gives a loud hum when the start button is depressed, your first action should be to __________. EL-0007 A. disassemble the motor to fix the centrifical ... D. hold the 'M' contactor closed by hand while wearing electrical safety gloves to get motor started

Last Answer : Answer: B

Description : The motor starts when the start button in the illustration is pushed, but stops when the button is released the trouble is _________. EL-0007 A. the incorrect thermal overload coil B. a faulty 'M' coil C. a dirty contact on the Disc.Sw. at 'L3' D. a faulty holding relay contact

Last Answer : Answer: D

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : In the illustration, 'D' is the symbol for a/an __________. EL-0005 A. thermal overload heater B. portable cable C. fuse D. indicating lamp

Last Answer : Answer: C

Description : The 'reset' contacts of the master switch shown in the illustration provides the winch controller with ___________. EL-0102 A. low voltage release B. overload protection C. low voltage protection D. high power factor correction

Last Answer : Answer: C

Description : If the motor fails to start and a voltmeter reading between 1 and 6, as illustrated, indicates line voltage, your next step should be to ________. EL-0007 A. replace fuse '10a' B. replace or repair contact 'Ma' C. reset and determine the cause of the overload D. check line voltage between L1 and L3

Last Answer : Answer: C

Description : When power is restored after a complete power failure, a steering gear pump motor will ____________. A. have to be restarted B. have to be reset C. restart automatically D. trip its overload relays

Last Answer : Answer: C

Description : As shown in the illustration, 'S' is the __________. EL-0017 A. safety switch B. overload trip C. start button D. stop button

Last Answer : Answer: D

Description : The arc resulting from the tripping of a circuit breaker is prevented from damaging the contacts by _____________. A. designing the contacts to open slowly B. directing the arc into an ... an inverse timed thermal trip for short circuit currents D. instantaneous magnetic trip for overload currents

Last Answer : Answer: B

Description : 'A-1', as shown in the illustration, is/are ____________. EL-0017 A. normally-closed overload relay contacts B. a double pole knife switch C. normally-open overload relay contacts D. a single pole knife switch

Last Answer : Answer: A

Description : As shown in the illustration, a 'pitch cutback' feature is incorporated in the system. This circuit reduces pitch amount to prevent engine overload when it senses ____________. EL-0095 A. pitch error of ... servo' C. excessive propeller speed or fuel to either engine D. only one engine on the line

Last Answer : Answer: C

Description : If a magnetic controller contactor fails to pick up when the coil voltage is applied to the contactor coil, the cause may be _____________. A. overload B. misalignment of the affected contactor contacts C. low spring pressure D. an open contactor coil

Last Answer : Answer: D

Description : Humming or buzzing of electric contacts is a symptom of ____________. A. low voltage on the operating coil B. power failure to the operating coil C. a control circuit ground D. a control circuit overload

Last Answer : Answer: A

Description : If the illustrated motor fails to start and gives a loud hum when the start button is pushed, the problem is ________. EL-0007 A. one of the phases to the motor is not energized because of ... electrical distribution system D. 'OL1' is open because of 'T1' overload causing the motor to single phase

Last Answer : Answer: A

Description : The pitting of controller contacts can be caused by _____________. A. excessive spring pressure B. insufficient contact pressure C. continuous motor overload D. all of the above

Last Answer : Answer: B

Description : If a transformer is connected to a DC source, the transformer will overload at the ____________. A. contacts B. primary coil C. secondary coil D. core

Last Answer : Answer: B

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C