Why the neutral is earthed through earthing resistance in case of UT and SUT? 

1 Answer

Answer :

This is done to limit the earth fault current.  

Related questions

Description : Why UT, SUT secondary is rated for 6.9kV where as bus voltage is 6.6kV? 

Last Answer : The no load secondary 6.9kV voltage level adequately takes into account voltage drop during loaded condition to cater station buses at 6.6kV level. 

Description : Why REF is provided in the LV side of SUT and UT? 

Last Answer : The LV sides of the two transformers are earthed through the resistance. This will limit the flow of current in case of LV earth fault. Hence the differential protection may not act for a LV earth fault. Hence ref protection is provided. 

Description : What is the vector group of GT, UT, SUT?

Last Answer : Yd11 Dy1 Yy0 

Description : During unit operation, can we parallel UT & SUT continuously?

Last Answer : No, due to switchgear limitation.  

Description : What is E/F current limit for SUT and UT?

Last Answer : 400a limited by 10 ohms resistor.  

Description : Purpose of standby E/F protection in SUT/UT? 

Last Answer : Back up for LV winding, LV neutral CT- CDG 12 – resistance earthing – relay set high time delay to discriminate with LV feeder and trip transformer if sustained E/F, also protects neutral earthing resistor.

Description : What is the neutral point earthing and its advantages?

Last Answer : In substation all the neutrals of rotating machines, transformers, busbars and other equipment are connected to ground. Some of the advantages are: Earth fault protection is based on the method of ... , grounding of neutral helps to reduce the over-voltages which occur on the one healthy phases

Description : Why we do 2 types of earthing on transformer i.e.: body earthing & neutral earthing, what is function. I am going to install a 5oo kva transformer & 380 kva DG set what should the earthing value?

Last Answer : The two types of earthing are Familiar as Equipment earthing and system earthing. In Equipment earthing: body (non conducting part) of the equipment should be earthed to safeguard the human ... earthing will be further classified into directly earthed, Impedance earthing, resistive (NGRs) earthing.

Description : Why control transformer is earthed?

Last Answer : If it is not earthed grounding of control circuit at two different places can cause bypassing of logics. In case of primary and secondary of the control transformer is getting the main fuse ... 415v will be superimposed in the control circuit during short circuit of primary and secondary winding)

Description : A bird sitting on a high tension electric wire does not get electrocuted because – (1) it has high resistance (2) the body is earthed (3) it does not form a closed path for the flow of current (4) its feet are good insulators

Last Answer : (3) it does not form a closed path for the flow of current Explanation: Electricity travels from a place of high voltage to low voltage, just as water travels from high elevation to low ... When electricity travels through a body in this fashion, electrocution takes place, and the bird can die.

Description : A bird sitting on a high tension electric wire does not get electrocuted because (1) it has high resistance (2) the body is earthed (3) it does not form a closed path for the flow of current (4) its feet are good insulators 

Last Answer : it does not form a closed path for the flow of current

Description : What are the protections for SUT? 

Last Answer : a) Over current protection for phase and earth fault b) Differential protection c) HV and LV restricted earthfault protection  d) HV side directional back up over current protection for phase ... protection f) Over fluxing protection g) Buchholz and high oil, winding temperature protection. 

Description : Why vector group of SUT is chosen as Yn-Yo-Yo?

Last Answer : To facilitate momentary paralleling of SUT with UT on 6.6kV buses.  

Description : Why twin secondary SUT? 

Last Answer : As per is, the rating single secondary power transformer is limited to 25MVA (6.6 kV) or 40 MVA (11 kV), in order to limit the 3 phase symmetrical fault level with in 26-40 kA (contribution from grid and local machines) 

Description : During unit operation, can we parallel 2 SUT? 

Last Answer : No, due to switchgear limitation. 

Description : What is the coverage of differential protection for SUT?

Last Answer : Covers from 230 kV bushing to 6.6 kV breaker end.  

Description : Why REF is now is used for HV side also in GT/SUT?

Last Answer : The E/F setting of differential is poor.  

Description : What is different between resistance grounding system and resistance earthing system?

Last Answer : In resistance grounding system the neutral point of the load is connected to the ground to carry the residual current in case of unbalanced conditions. Resistance earthing system is done in an electric equipment in order to protect the equipment in occurrence of fault in the system.

Description : Write down difference between equipment earthing and neutral earthing. 

Last Answer : Sr. No. Equipment earthing Neutral earthing 1 Connection of the non-current carrying metallic parts of the electrical equipment to earth is called as equipment earthing. Connection of the neutral ... 6 It is an equipment earthing. It is a source or system earthing.

Description : State the methods of Neutral Grounding. State difference between Earthing and grounding. 

Last Answer : Neutral Grounding connections are of three types:  1. Solid earthing 2. Resistance earthing 3. Reactance earthing SR. NO. Earthing Grounding 1 Earthing means connecting the dead part ... earthing provides suitable means for earth fault protecting system.  10

Description : What are the protections for UT?  

Last Answer : a) Differential protection b) LV restricted earthfault protection c) LV back up earthfault and over current protection d) Buchholz and high oil, winding temperature protection. 

Description : Why main generator/UT is not provided with separate overfluxing protection?

Last Answer : Since GT is provided with overfluxing protection, it is adequate to protect main generator / UT also. Main generator can withstand higher degree of overfluxing. If a generator CB is used, separate overfluxing protection is essential for main generator. 

Description : During unit operation can we have one UT feeding both unit 6.6 kV loads? 

Last Answer : No, logically prevented.  

Description : Where fault level is more, whether in generator bus duct or UT bus duct? Why?

Last Answer : Fault level is more in UT bus duct. Because the fault currents fed by the both generator and GT adds up within UT bus duct in case there is a fault in UT bus duct. 

Description : An electrical appliance is earthed to 1. Protect the appliance against any damage 2. Prevent electric shocks 3. Avoid short-circuiting Which of the above is/are correct? (a) 1 only (b) 2 only (c) 1 and 2 (d) 2 and 3

Last Answer : Ans:(b)

Description : Can I wear any type of footwear and still be earthed?

Last Answer : No. Standard plastic/rubber or composite soles do not conduct the Earth's electric energy. Most shoes today are made from those materials. You need leather or hide soles, which used to be ... . Hopefully soon shoe companies will begi shoe companies will begin making n making grounded grounded shoes.

Description : In a semiconductor diode, p-side is earthed and to n-side is applied a potential of -2 volt; the diode shall (a) Conduct (b) Not conduct (c) Conduct partially (d) Break down

Last Answer : a) Conduct

Description : Explain types of Earthing.

Last Answer : A:The two types of earthing are Equipment earthing and system earthing. In Equipment earthing: body ( non conducting part) of the equipment should be earthed to safegaurd the human beings ... . This type of earthing is further classified into directly earthed, Impedance earthing, resistive earthing.

Description : State the various types of earthing.

Last Answer : Solid earthing, resistance earthing , reactance earthing , voltage transformer earthing and zig-zag transformer earthing.

Description : What is difference between earthing and grounding?

Last Answer : Both have same meaning. The term earthing is used in U.K. and grounding in U.S.A.ground means earth.

Description : How many earthing should be done for motors? Why? 

Last Answer : Two. For reliability.  

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : How main generator earthing is done?

Last Answer : Generator neutral earthing is done through transformer and earth fault current is limited through resistance, which is connected across the secondary of the transformer. Generator 16.5 kV earth fault current is isolated from 220 kV through GT. Only star point of the generator is grounded. 

Description : What is the purpose of shaft earthing and bearing insulation?

Last Answer : The voltage generated in the shaft due to the leakage fluxes can circulate current through the shaft. If shaft earthing is not done the leakage current will flow through the bearings to ground and pitting of bearings will result. Hence bearing foundation and pipelines are insulated. 

Description : Why shaft-earthing brush is different from normal brush?

Last Answer : The contact resistance should be very low for shaft earthing brush, to prevent even small current through the oil film, so used copper magnite brush or silver carbon brush.

Description : What should the statutory provision of earthing?  

Last Answer : a. Earthing shall generally be carried out in accordance with the requirement of India electricity rule 1956, as amended from time to time and the relevant regulations of the electricity supply ... , etc. used in earthing shall conform to Indian standard specifications, wherever these exist. 

Description : What is difference between earthing and grounding?

Last Answer : Both have same meaning. The term earthing is used in U.K. and grounding in U.S.A. ground means earth.  

Last Answer : earthing Of Resistance Max 5 Ohm To be Will be

Description : What should be the value of earthing resistance for large power stations?

Last Answer : 0.5 Ω should be the value of earthing resistance for large power stations.

Description : From the point of view of safety, the resistance of earthing electrode should be   (a) Low (b) High (c) Medium (d) The value of resistance of earth does not affect the safety 

Last Answer : A

Description : Good hiking/camping spots in UT and CO?

Last Answer : Gotta hit Bryce or Zion in Utah for sure! Both are spectacular. Look into reservations for camping online first, you may need to reserve a night now with the summer tourist hub kicking into high gear. Colorado I am less sure of, traveled through but didn’t camp anywhere.

Description : Nightlife in Mesquite (NV) and St. George (UT)?

Last Answer : Remember Utah is a semi-dry state for alcohol, so if partying is part of the equation…. you have to go through a little extra to get to a bar. Mesquite has over five or six casinos/resorts. I’ve eaten at Virgin River in Mesquite.

Description : Should I go to grad school at UC Irvine or UT Austin?

Last Answer : I think that would depend entirely on each school’s program.

Description : I'm ut mobile and I have to recharge 100 MB of data once a month, but they can't run, please advise

Last Answer : Need Answer

Description : What is the mystery greene discusses and why does he say ut is something we should all care about?

Last Answer : Feel Free to Answer

Description : Moab, UT?

Last Answer : Moab, UT is a great site to visit. Until the 1950's Moab did nothave much to offer. Charlie Steen discovered uranium there and thetown has grown very quickly since that time. In Moab, UT there ... using whitewater rafting or a person can rent awhitewater raft and take their own tour.Moab, UT is n

Description : How do I go about finding a caregiver for my elderly mother in Provo, UT?

Last Answer : First, check in the local community for recommendations. Even if you live far away, call your mother's pastor or someone else that she knows in the community and ask for recommendations. If ... servicemagic has licensed, bonded, insured and rated caregivers listed for provo and the service is free.

Description : Is there a tae kwon do class offered in Salt Lake City, UT?

Last Answer : Yes. One in particular, is Master Kwon World Class, located at 3909 Highland Drive. Their phone number is (801) 272-5444, if you would like more information.

Description : The Union Government on 22 May 2016 appointed whom as the new Lieutenant Governor of the Union Territory (UT) of Pondicherry? (1) Kiran Bedi (2) Kalyan Singh (3) Ram Naik (4) Mukul Sangma

Last Answer : (1) Kiran Bedi Explanation: BJP leader and former IPS officer Kiran Bedi was, in May 2016, appointed Lieutenant Governor of Puducherry. The post had been lying vacant after the Narendra Modi ... The Union Territory was under the additional charge of Lt. Governor of Andaman and Nicobar Islands.

Description : Which amongst the following States/UT has not identified tribal community? (1) Chhattisgarh (2) Haryana (3) Maharashtra (4) Karnataka

Last Answer : (2) Haryana Explanation: There are 84 million Scheduled Tribe persons in India as counted in the Census of 2001. Of them, about one third are in the Central Indian region comprising ... in the northern region of Jammu and Kashmir and the adjoining districts of Himachal Pradesh and Uttarakhand.