Why UT, SUT secondary is rated for 6.9kV where as bus voltage is 6.6kV? 

1 Answer

Answer :

The no load secondary 6.9kV voltage level adequately takes into account voltage drop during loaded condition to cater station buses at 6.6kV level. 

Related questions

Description : Why REF is provided in the LV side of SUT and UT? 

Last Answer : The LV sides of the two transformers are earthed through the resistance. This will limit the flow of current in case of LV earth fault. Hence the differential protection may not act for a LV earth fault. Hence ref protection is provided. 

Description : Why the neutral is earthed through earthing resistance in case of UT and SUT? 

Last Answer : This is done to limit the earth fault current.  

Description : What is the vector group of GT, UT, SUT?

Last Answer : Yd11 Dy1 Yy0 

Description : During unit operation, can we parallel UT & SUT continuously?

Last Answer : No, due to switchgear limitation.  

Description : What is E/F current limit for SUT and UT?

Last Answer : 400a limited by 10 ohms resistor.  

Description : Purpose of standby E/F protection in SUT/UT? 

Last Answer : Back up for LV winding, LV neutral CT- CDG 12 – resistance earthing – relay set high time delay to discriminate with LV feeder and trip transformer if sustained E/F, also protects neutral earthing resistor.

Description : Why twin secondary SUT? 

Last Answer : As per is, the rating single secondary power transformer is limited to 25MVA (6.6 kV) or 40 MVA (11 kV), in order to limit the 3 phase symmetrical fault level with in 26-40 kA (contribution from grid and local machines) 

Description : Where fault level is more, whether in generator bus duct or UT bus duct? Why?

Last Answer : Fault level is more in UT bus duct. Because the fault currents fed by the both generator and GT adds up within UT bus duct in case there is a fault in UT bus duct. 

Description : The operating voltage of high voltage cables is up to (a)l.lkV (b)3.3kV (c)6.6kV (d)llkV

Last Answer : (d)llkV

Description : What is the significance of SF6 gas pressure in 6.6kV breakers?

Last Answer : Density gauge Green – correct SF6 pressure (3 –3.5bar) Yellow – pressure for breaking system fault current (refilling should be done) Red – SF6 pressure less than 2 bar, which indicates leak in the system. 

Description : at the terminal of a three-phase 6.6Kv alternator a load R=200 ohm is connected between two-phase and the third phase is opened. Z1=z2=5 ohm Zo=2 find out the fault current .

Last Answer : 32A

Description : During unit operation can we have one UT feeding both unit 6.6 kV loads? 

Last Answer : No, logically prevented.  

Description : What are the protections for SUT? 

Last Answer : a) Over current protection for phase and earth fault b) Differential protection c) HV and LV restricted earthfault protection  d) HV side directional back up over current protection for phase ... protection f) Over fluxing protection g) Buchholz and high oil, winding temperature protection. 

Description : Why vector group of SUT is chosen as Yn-Yo-Yo?

Last Answer : To facilitate momentary paralleling of SUT with UT on 6.6kV buses.  

Description : During unit operation, can we parallel 2 SUT? 

Last Answer : No, due to switchgear limitation. 

Description : What is the coverage of differential protection for SUT?

Last Answer : Covers from 230 kV bushing to 6.6 kV breaker end.  

Description : Why REF is now is used for HV side also in GT/SUT?

Last Answer : The E/F setting of differential is poor.  

Description : By which of the following a bus-bar is rated ? (a) Current only (b) Current and voltage (c) Current, voltage and frequency (d) Current, voltage, frequency and short time current

Last Answer : (d) Current, voltage, frequency and short time current

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : What are the protections for UT?  

Last Answer : a) Differential protection b) LV restricted earthfault protection c) LV back up earthfault and over current protection d) Buchholz and high oil, winding temperature protection. 

Description : Why main generator/UT is not provided with separate overfluxing protection?

Last Answer : Since GT is provided with overfluxing protection, it is adequate to protect main generator / UT also. Main generator can withstand higher degree of overfluxing. If a generator CB is used, separate overfluxing protection is essential for main generator. 

Description : Which of the following precautions should be taken when a blown fuse, rated at 10 amperes, is replaced? A. Short out the fuse before removing it from the circuit. B. Use needle-nose pliers to ... D. Fuses of 10 ampere rating and less are virtually harmless when energized and may be handled freely.

Last Answer : Answer: C

Description : An open shunt field in a direct current machine may be located by connecting the field circuit to an external power source, equal to the rated field voltage or less, and tested with a voltmeter from ... C. any suitable ground to any available line lead D. any field pole to each field coil lead

Last Answer : Answer: A

Description : A split-phase induction squirrel-cage motor will not come up to speed, even though the rated voltage, rated frequency, and rated load are applied. The suspected trouble could be due to _____________. A. a faulty centrifugal switch B. broken rotor bars C. worn bearings D. all of the above

Last Answer : Answer: D

Description : In the illustrated circuit the voltage is 12 VDC and the resistance is 3 ohms. If the battery is rated for 120 amp-hours, how long before the voltage will drop to 1.75 volts per cell? EL-0018 A. 12 hours B. 1.75 days C. 30 hours D. 2.5 days

Last Answer : Answer: C

Description : When troubleshooting a motor controller, all indications are that a relay coil should be energized. If there were no magnetic pull, with rated voltage measured across the coil, the most probable cause ... open C. auxiliary contact in series with the coil is defective D. relay armature is stuck

Last Answer : Answer: A

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : If an induction motor were to be operated at 90% rated voltage, _____________. A. there would be an increase in starting torque B. starting current would increase slightly C. synchronous speed would decrease slightly D. the slip would increase

Last Answer : Answer: D

Description : The full load torque of an electric motor is the __________. A. minimum torque developed by the motor accelerating from stop to full speed B. turning moment exerted by the motor at rated load ... and frequency D. turning moment exerted by the motor from any rotor angular position at any load

Last Answer : Answer: B

Description : One method of testing for a reversed shunt field coil in a DC generator or motor is by connecting the field to a direct current source, at reduced field rated voltage, and test for ... placed near each field C. test lamp across adjacent fields D. copper jumper across the interpole connections

Last Answer : Answer: B

Description : Fuses are rated in _____________. A. voltage B. amperage C. interrupting capacity D. all the above

Last Answer : Answer: D

Description : The torque produced by a motor when its shaft will not turn, even though rated voltage is applied to the stator, is known as _____________. A. locked-rotor torque B. pullout torque C. breakdown torque D. torque margin

Last Answer : Answer: A

Description : Why the open circuit test on a transformer is conducted at rated voltage?

Last Answer : A:The open circuit on a transformer is conducted at a rated voltage because core loss depends upon the voltage. This open circuit test gives only core loss or iron loss of the transformer.

Description : Define the followings.   Insulation level, Rated short circuit breaking current, Making current, Short time rating, Impulse withstand voltage, Power frequency withstand voltage .

Last Answer : Insulation level - it is the combination of rated voltage, the corresponding impulse withstand voltage, which together characterize the insulation of the equipment as regards its ability to withstand ... wave of power frequency (50 Hz) which the insulation of equipment should withstand. 

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : When 220V dc shunt alternator generating the voltage at rated value. If direction of rotation is reversed, then alternator will a) Build up its voltage with same polarity b) Build up its voltage with opposite polarity c) No build up of voltage d) None

Last Answer : Ans: No build up of voltage

Description : An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging case. If it is required to deliver rated current at rated voltage and 0.8 power-factor leading, the required excitation will be (A) less. (B) more. (C) more or less. (D) the same.

Last Answer : Ans: B Over excitation gives leading power factor and under excitation gives lagging p.f .

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : The primary winding of a 220/6 V, 50 Hz transformer is energised from 110 V, 60 Hz supply. The secondary output voltage will be (A) 3.6 V. (B) 2.5 V. (C) 3.0 V. (D) 6.0 V.

Last Answer : (C) 3.0 V.

Description : The purpose of the automatic bus transfer shown in the illustration is to ___________. EL-0014 A. stepdown voltage to the lighting distribution panel B. provide emergency power to ... emergency switchboard from the main switchboard D. provide overcurrent protection to the lighting distribution panel

Last Answer : Answer: B

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : Motorization of an alternator is undesirable because _____________. A. the alternator will be damaged B. it puts an additional load on the bus C. high voltage pulses are induced in the bus D. all of the above

Last Answer : Answer: B

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : If field excitation is suddenly lost to an alternator operating in parallel, that alternator will _____________. A. supply excessive current to the bus B. operate at the same load, but with reduced voltage C. lose its load and tend to overspeed D. become overloaded and slow down

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : When paralleling two AC generators, the frequency of the incoming machine immediately prior to closing its breaker should be ____________. A. controlled by placing the governor switch in the automatic ... regulator C. slightly greater than the bus frequency D. slightly less than the bus frequency

Last Answer : Answer: C