Where fault level is more, whether in generator bus duct or UT bus duct? Why?

1 Answer

Answer :

Fault level is more in UT bus duct. Because the fault currents fed by the both generator and GT adds up within UT bus duct in case there is a fault in UT bus duct. 

Related questions

Description : Which is better, whether a) Phase segregated bus duct or b) Common bus duct?

Last Answer : Phase segregated bus duct is better, since phase to phase faults are avoided.  

Description : Why cannot we have cables instead of bus duct in main generator? 

Last Answer : Very large number of cables in parallel required problems of sealing the terminations. 

Description : Why UT, SUT secondary is rated for 6.9kV where as bus voltage is 6.6kV? 

Last Answer : The no load secondary 6.9kV voltage level adequately takes into account voltage drop during loaded condition to cater station buses at 6.6kV level. 

Description : Why main generator/UT is not provided with separate overfluxing protection?

Last Answer : Since GT is provided with overfluxing protection, it is adequate to protect main generator / UT also. Main generator can withstand higher degree of overfluxing. If a generator CB is used, separate overfluxing protection is essential for main generator. 

Description : Why aluminium bus duct is used?

Last Answer : Aluminium is nonmagnetic material. Short circuit forces are less. 

Description : How moisture entry is prevented into bus duct?  

Last Answer : Silicagel breathers at either end. 

Description : How generator earth fault relay works? 

Last Answer : 100% earth fault relay works on the principle involving monitoring of neutral side and line side components of 3rd harmonic voltages produced by generator in service. Since the machine is grounded with ... be detected by VL3 neutral displacement module, which is tuned to find frequency.   

Description : Why earth fault current of generator should not be reduced below 5A? 

Last Answer : To limit over voltage due to neutral shift.  

Description : What are the protections for UT?  

Last Answer : a) Differential protection b) LV restricted earthfault protection c) LV back up earthfault and over current protection d) Buchholz and high oil, winding temperature protection. 

Description : Why REF is provided in the LV side of SUT and UT? 

Last Answer : The LV sides of the two transformers are earthed through the resistance. This will limit the flow of current in case of LV earth fault. Hence the differential protection may not act for a LV earth fault. Hence ref protection is provided. 

Description : Why the neutral is earthed through earthing resistance in case of UT and SUT? 

Last Answer : This is done to limit the earth fault current.  

Description : What is the vector group of GT, UT, SUT?

Last Answer : Yd11 Dy1 Yy0 

Description : During unit operation, can we parallel UT & SUT continuously?

Last Answer : No, due to switchgear limitation.  

Description : During unit operation can we have one UT feeding both unit 6.6 kV loads? 

Last Answer : No, logically prevented.  

Description : What is E/F current limit for SUT and UT?

Last Answer : 400a limited by 10 ohms resistor.  

Description : Purpose of standby E/F protection in SUT/UT? 

Last Answer : Back up for LV winding, LV neutral CT- CDG 12 – resistance earthing – relay set high time delay to discriminate with LV feeder and trip transformer if sustained E/F, also protects neutral earthing resistor.

Description : In the schematic diagram of the DC compound generator shown in the illustration, the positive ammeter reading is 500 amps and the negative ammeter reading is 475 amps. What is the current flow through the neutral bus? EL-0037 A. 0 amp B. 12.5 amp C. 25 amp D. 975 amp

Last Answer : Answer: C

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : As shown in the illustration, the function of the switch labeled 'PFSW' is to determine the ______________. EL-0003 A. bus frequency B. reactive volt amperes of the bus C. frequency of either generator D. power factor of either generator

Last Answer : Answer: D

Description : In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

Last Answer : Answer: B

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : When paralleling two AC generators, the frequency of the machine coming online, immediately prior to closing its breaker, should be ____________. A. slightly less than the oncoming generator frequency B. the ... bus frequency C. slightly greater than the bus frequency D. the same as the bus voltage

Last Answer : Answer: C

Description : When paralleling two AC generators, the synchroscope selector switch and frequency meter switch should be set up to sense the frequency of the _____________. A. bus B. generator on the line C. oncoming generator D. bus transfer relay

Last Answer : Answer: C

Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus

Last Answer : Answer: A

Description : Which of the listed sections of an emergency switchboard is used to supply power for alarm signals under emergency conditions? A. The generator and bus transfer section B. The 450 volt, 60 cycle, 3 phase bus C. The 120 volt, 3 phase, 60 cycle bus D. The 24 volt DC bus

Last Answer : Answer: D

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. main bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : A bus disconnect link is used to isolate _____________. A. one bus bar from another B. the generator circuit breaker from the bus C. different phases from the equalizer connection D. positive and negative buses from the neutral

Last Answer : Answer: B

Description : Prior to starting an AC generator prime mover, the voltage regulator cutout switch should be placed in the __________. A. manual position B. bus neutral position C. raise voltage position D. transfer position

Last Answer : Answer: A

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : What will be the reactive power and bus voltage whan the generator bus is treated as load bus.

Last Answer : When the generator bus is treated as load bus, the reactive power of the bus is equated to the limit it has violated, and the previous iteration value of bus voltage is used for calculating current iteration value.

Description : When the generator buses are treated as load bus.

Last Answer : If the reactive power constraints of a generator bus violates the specified limits then the generator is treated as load bus.

Description : Define voltage controlled bus(generator bus/PV bus).

Last Answer : A bus is called voltage controlled bus if the magnitude of voltage |V| and real power (P) are specified for it. In a voltage controlled bus, the magnitude of the voltage is not allowed to change. Voltage controlled bus is also called as Generator bus and PV bus.

Description : Explain fault bus protection scheme.

Last Answer : Fault bus protection of busbar: In this scheme, the substation is so designed that every fault on the bus bar is converted to earth fault. Under normal operating conditions, there is no current flowing ... This results in operation of relay to actuate trip coil of CB to trip the circuit.

Description : The zero sequence current of a generator for line to ground fault is j 2.4 p.u. The current through the neutral during the fault is (a) j 0.8 p.u (b) j 2.4 p.u. (c) j 0.24 p.u. (d) j 7.2 p.u. 

Last Answer : j7.2

Description : Electrical fault between two windings of same phase of a generator having double star winding can be detected by the following protection in a generator:

Last Answer : Electrical fault between two windings of same phase of a generator having double star winding can be detected by the following protection in a generator: inter turn fault protection

Description : The steady-state fault current during a 3 phase terminal fault on a generator is limited by: (1) Transient reactance of the generator (2) Sub-transient reactance of the generator (3) Synchronous reactance of the generator (4) DC off—set during the instant of the fault

Last Answer : 1

Description : For a fault at the terminals of a synchronous generator, the fault current is maximum for a  A) 3-phase fault B) 3-phase to ground fault C) Line to ground fault D) Line to line fault

Last Answer : C) Line to ground fault

Description : Which of the listed safety features should be provided in small rooms or lockers where batteries are stored? A. Installation of a fixed CO2 system. B. An exhaust duct is to be provided and led from within ... An exhaust duct is to be provided and led from the top of the locker to the open air.

Last Answer : Answer: D

Description : Which of the following is/are true concerning electric power operated watertight door systems? A. Each motor driven door must use the main bus as its source of power. B. Each distribution panel for ... to permit quick activation of the system. D. Each system must have a separate branch circuit.

Last Answer : Answer: D

Description : Good hiking/camping spots in UT and CO?

Last Answer : Gotta hit Bryce or Zion in Utah for sure! Both are spectacular. Look into reservations for camping online first, you may need to reserve a night now with the summer tourist hub kicking into high gear. Colorado I am less sure of, traveled through but didn’t camp anywhere.

Description : Nightlife in Mesquite (NV) and St. George (UT)?

Last Answer : Remember Utah is a semi-dry state for alcohol, so if partying is part of the equation…. you have to go through a little extra to get to a bar. Mesquite has over five or six casinos/resorts. I’ve eaten at Virgin River in Mesquite.

Description : Should I go to grad school at UC Irvine or UT Austin?

Last Answer : I think that would depend entirely on each school’s program.

Description : I'm ut mobile and I have to recharge 100 MB of data once a month, but they can't run, please advise

Last Answer : Need Answer

Description : What is the mystery greene discusses and why does he say ut is something we should all care about?

Last Answer : Feel Free to Answer