What are the protections for SUT? 

1 Answer

Answer :

a) Over current protection for phase and earth fault

b) Differential protection

c) HV and LV restricted earthfault protection 

d) HV side directional back up over current protection for phase and earth fault.

e) LV back up over current and earth fault protection

f) Over fluxing protection

g) Buchholz and high oil, winding temperature protection. 

Related questions

Description : Why vector group of SUT is chosen as Yn-Yo-Yo?

Last Answer : To facilitate momentary paralleling of SUT with UT on 6.6kV buses.  

Description : Why UT, SUT secondary is rated for 6.9kV where as bus voltage is 6.6kV? 

Last Answer : The no load secondary 6.9kV voltage level adequately takes into account voltage drop during loaded condition to cater station buses at 6.6kV level. 

Description : Why twin secondary SUT? 

Last Answer : As per is, the rating single secondary power transformer is limited to 25MVA (6.6 kV) or 40 MVA (11 kV), in order to limit the 3 phase symmetrical fault level with in 26-40 kA (contribution from grid and local machines) 

Description : Why REF is provided in the LV side of SUT and UT? 

Last Answer : The LV sides of the two transformers are earthed through the resistance. This will limit the flow of current in case of LV earth fault. Hence the differential protection may not act for a LV earth fault. Hence ref protection is provided. 

Description : Why the neutral is earthed through earthing resistance in case of UT and SUT? 

Last Answer : This is done to limit the earth fault current.  

Description : What is the vector group of GT, UT, SUT?

Last Answer : Yd11 Dy1 Yy0 

Description : During unit operation, can we parallel UT & SUT continuously?

Last Answer : No, due to switchgear limitation.  

Description : During unit operation, can we parallel 2 SUT? 

Last Answer : No, due to switchgear limitation. 

Description : What is the coverage of differential protection for SUT?

Last Answer : Covers from 230 kV bushing to 6.6 kV breaker end.  

Description : What is E/F current limit for SUT and UT?

Last Answer : 400a limited by 10 ohms resistor.  

Description : Purpose of standby E/F protection in SUT/UT? 

Last Answer : Back up for LV winding, LV neutral CT- CDG 12 – resistance earthing – relay set high time delay to discriminate with LV feeder and trip transformer if sustained E/F, also protects neutral earthing resistor.

Description : Why REF is now is used for HV side also in GT/SUT?

Last Answer : The E/F setting of differential is poor.  

Description : What are the different Generator Protections employed in Thermal Power Plants?

Last Answer : Answer: Faults in the windings, Over load protection, Over heating of windings or bearings, Over speed protection, Loss of Excitation protection, Motoring operation protection, Inadvertent ... , out of step operation protection, sub-synchronous oscillations protection and earth fault protection

Description : What are the different Generator Protections employed in Thermal Power Plants?

Last Answer : Faults in the windings, Over load protection, Over heating of windings or bearings, Over speed protection, Loss of Excitation protection, Motoring operation protection, Inadvertent energisation ... , out of step operation protection, sub-synchronous oscillations protection and earth fault protection

Description : What are the protections provided for DG?

Last Answer : 1. Differential protection (87). 2. Over speed of engine. 3. Reverse power protection (in LOCA condition time delay). 4. Low lubricating oil pressure. 5. Cooling water temperature high. 6. 6 ... 8. Emergency stops push button. In LOCA condition 4 - 8 protections are not permitted to operate. 

Description : What are the protections used in 415 V Class II side?

Last Answer : LV to UPS 1. CTZM 2. 50 (instantaneous over current) 3. short circuit UPS to PMCC S & T 1. 51 RYB (inverse over current) 2. 27 (under voltage) 3. 51N (earth fault) From Class III to Class II tie CTZM at Class III and 51, 51N at Class II. 

Description : What are the protections used in Class III & Class IV 415 V LV side?  

Last Answer : Class III 415 V LV side 1. 51 (inverse over current) 2. 50 (instantaneous over current) 3. 27 (under voltage) 4. 51N (earth fault) 5. 64 (REF)  Class IV 415 V LV side 1. 51 RYB (inverse over current) 2. 51N (earth fault) 

Description : What are the protections provided in charger?  

Last Answer : 1. Over load (49). 2. Over voltage (59). 3. Short-circuit (3250 Amps). 4. Phase sequence and phase fail. 5. di/dt and dv/dt protection. 

Description : What are the protections adopted in UPS or PMCC supply?

Last Answer : LV (incomer) or UPS input CTZM, Over current, Short circuit protections PMCC S or T input or UPS output Under voltage (27), 51RYB, 51N protections. 

Description : What are the protections are there for lines?  

Last Answer : Directional earthfault protection Directional over current protection Local breaker back up protection Pole discrepancy Main protection (distance protection)

Description : What are the protections are there for BUSBAR?

Last Answer : Instantaneous over current protection Bus bar differential protection Local breaker back up protection 

Description : What are the in-built protections provided in MCC cell? 

Last Answer : Fuses for short circuit protection. OLR for over load and single phasing protection. Electrical and Mechanical interlock in valve cell against short circuit. 

Description : What are the protections provided in PMCC circuit breakers?

Last Answer : 1. IDMT O/C (CDG 34). 2. IDMT E/F (CDG 11).  3. Under voltage (40% of 110V). 

Description : What are the protections provided for motor feeder?  

Last Answer : Ith - Thermal over load I2S - Unbalance load I0S - Earth fault protection I1t - Stalling protection I1Inst. - Short circuit protection 

Description : What are the protections for UT?  

Last Answer : a) Differential protection b) LV restricted earthfault protection c) LV back up earthfault and over current protection d) Buchholz and high oil, winding temperature protection. 

Description : What are the protections for GENERATOR TRANSFORMER?  

Last Answer : a) Differential protection b) Restricted earthfault protection c) Backup earthfault protection d) GT phase back up protection e) Overfluxing protection f) Oil surge (gas) protection g) High winding temperature and oil temperature protection. 

Description : What are the built in protections for transformers?

Last Answer : a) Buchholz relay b) Explosion vent or relief valve c) Gas operated relay for on load tap changers. 

Description : Why all 415V transformers are chosen Dyn 11? What are the protections provided for the 415V transformers?

Last Answer : a) To facilitate interchange. b) To have momentary parallel during changeover. Protections a) Door interlock to trip HT and LT breakers. b) LT breaker can on only after HT breaker is in on position. c) ... and restricted E/F (51N + 64). f) Winding temp high trip (140°C trip and 130°C alarm) 

Description : What are the working principles of generator main protections?

Last Answer : GENERATOR START UP PROTECTIONS SUPPLEMENTARY PROTECTION OF GENERATOR The generator is normally expected to run rated speed before excitation power is applied by closing the field breaker. ... position to ensure that the protection is inoperable when the machine is connected to grid.  

Description : What are the built in protections provided in 415 V breaker?  

Last Answer : a. DINF (making current magnetic release) This consists of a laminated magnetic circuit. This is placed under the lower current terminal pole. This is provided for all the three poles. It has a core that rotates ... by a lever. It is placed in front of the breaker. Setting range is 60% to 100%.  

Description : What are the protections provided for 220 kV lines and bus bars? 

Last Answer : a. Bus bar differential protection. b. Distance protection. c. Over current protection. d. Earth fault protection. 

Description : Why are children considered deserving of protections that other weak or powerless individuals do not get?

Last Answer : We do have protections in place. Every state has an Adult Protective Services division and that people are allowed to file bankruptcy rather than be held totally responsible for their debts is a form of protecting ... 't we can only protect them so far and so much and then they are on their own.

Description : What store sells laptop protections?

Last Answer : Best Buy would have laptop protectors. And yes it would be a good investment to buy one for your laptop. It will protect your laptop from getting scratched or dinged from being dropped.

Description : How are circuits protections devices connected to the circuit they are intended to protect and why are they connected in this way?

Last Answer : In series, so total current will be stopped when the device opens.

Description : State the types of protections provided by MCB. 

Last Answer : The types of protections provided by MCB: 1. MCB provides short circuit protection. 2. MCB provides overload protection