What are the protections provided in PMCC circuit breakers?

1 Answer

Answer :

1. IDMT O/C (CDG 34).

2. IDMT E/F (CDG 11). 

3. Under voltage (40% of 110V). 

Related questions

Description : What are the protections adopted in UPS or PMCC supply?

Last Answer : LV (incomer) or UPS input CTZM, Over current, Short circuit protections PMCC S or T input or UPS output Under voltage (27), 51RYB, 51N protections. 

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : Why Isolation switches are provided along with the circuit breakers?

Last Answer : Isolation switches are provided for separating the disconnected element from the live portion of the system for the purpose of safety

Description : What are the protections provided for DG?

Last Answer : 1. Differential protection (87). 2. Over speed of engine. 3. Reverse power protection (in LOCA condition time delay). 4. Low lubricating oil pressure. 5. Cooling water temperature high. 6. 6 ... 8. Emergency stops push button. In LOCA condition 4 - 8 protections are not permitted to operate. 

Description : What are the protections provided in charger?  

Last Answer : 1. Over load (49). 2. Over voltage (59). 3. Short-circuit (3250 Amps). 4. Phase sequence and phase fail. 5. di/dt and dv/dt protection. 

Description : What are the in-built protections provided in MCC cell? 

Last Answer : Fuses for short circuit protection. OLR for over load and single phasing protection. Electrical and Mechanical interlock in valve cell against short circuit. 

Description : What are the protections provided for motor feeder?  

Last Answer : Ith - Thermal over load I2S - Unbalance load I0S - Earth fault protection I1t - Stalling protection I1Inst. - Short circuit protection 

Description : Why all 415V transformers are chosen Dyn 11? What are the protections provided for the 415V transformers?

Last Answer : a) To facilitate interchange. b) To have momentary parallel during changeover. Protections a) Door interlock to trip HT and LT breakers. b) LT breaker can on only after HT breaker is in on position. c) ... and restricted E/F (51N + 64). f) Winding temp high trip (140°C trip and 130°C alarm) 

Description : What are the built in protections provided in 415 V breaker?  

Last Answer : a. DINF (making current magnetic release) This consists of a laminated magnetic circuit. This is placed under the lower current terminal pole. This is provided for all the three poles. It has a core that rotates ... by a lever. It is placed in front of the breaker. Setting range is 60% to 100%.  

Description : What are the protections provided for 220 kV lines and bus bars? 

Last Answer : a. Bus bar differential protection. b. Distance protection. c. Over current protection. d. Earth fault protection. 

Description : What type breakers are provided in 6.6 kV buses?

Last Answer : ABB. Make, SF6 gas, 1250A and 2000A capacity circuit breakers are provided in 6.6 kV buses. 

Description : State the types of protections provided by MCB. 

Last Answer : The types of protections provided by MCB: 1. MCB provides short circuit protection. 2. MCB provides overload protection

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : A ground is indicated by the ground-detecting system on the main electrical switchboard. The FIRST step in locating the actual ground is to _____________. A. close all circuit breakers in ... ground detection system indicates normal C. change over generators D. check each circuit with a megohmmeter

Last Answer : Answer: B

Description : During maintenance of circuit breakers, _______________. A. always smooth roughened contact surfaces with a file B. never pass more than rated breaker current through the overload heater element C. ... wear and misalignment of main contacts D. assume heater elements installed are of correct size

Last Answer : Answer: C

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : Periodic testing of circuit breakers is necessary to assure that a correctly rated and properly installed unit _________________. A. can trip faster as it increases in age B. will continue to provide ... not exceed its interrupting capacity D. be able to withstand at least 125% of applied voltage

Last Answer : Answer: B

Description : You can determine if a circuit breaker has tripped by ________________. A. examining the position of the handle B. checking for which of the breakers is warm C. looking for a burned-out link D. all of the above

Last Answer : Answer: A

Description : The purpose of a main switchboard circuit breaker's reverse-power trip is to _____________. A. prevent main circuit overload B. protect the circuit breaker blowout coil C. prevent alternator motorization D. prevent low voltage tripout

Last Answer : Answer: C

Description : A 'dead front' switchboard is one _____________. A. without switches on it B. with insulated switches and no exposed terminals C. without circuit breakers D. without safety hand rails nor rubber mats

Last Answer : Answer: B

Description : The purpose of a short circuit forcing module (short time trip) installed in a branch line is to provide ____________. A. high speed clearance of low impedance short circuits in the branch B. ... C. isolation of short circuits by selective tripping of branch circuit breakers D. all of the above

Last Answer : Answer: D

Description : What are different types of circuit breakers employed in thermal power plant?

Last Answer : Answer: For low voltage operation 415/220V vacuum circuit breakers or air break circuit breakers are employed. For voltage ratings about 6.6kV and beyond SF6 circuit breakers are employed.

Description : What are different types of circuit breakers employed in thermal power plant?

Last Answer : For low voltage operation 415/220V vacuum circuit breakers or air break circuit breakers are employed. For voltage ratings about 6.6kV and beyond SF6 circuit breakers are employed.

Description : Air Blast Circuit Breakers Advantages Disadvantages

Last Answer : Air Blast Circuit Breakers Advantages Disadvantages In air blast circuit breakers, compressed air at a pressure of 20-30 kg/cm2 is employed as an arc quenching medium. Air blast circuit breakers ... air blast circuit breaker current chopping problem exists There is a problem of re-striking voltage

Description : Why we need isolation transformers in power circuit ? why cant we use breakers to isolate?

Last Answer : In Isolation transformer is used, if there is change in parameter values of any side, the other side parameters will remain unchanged.

Description : How direct tests are conducted in circuit breakers?

Last Answer : Using a short circuit generator as the source. Using the power utility system or network as the source.

Description : State the different types of circuit breakers.

Last Answer : Air ,oil,vacuum circuit breakers.

Description : Write the classifications of test conducted on circuit breakers.

Last Answer : Type test Routine test Reliability test Commissioning test

Description : Write the classification of circuit breakers based on the medium used for arc extinction?

Last Answer : Air break circuit breaker Oil circuit breaker Minimum oil circuit breaker Air blast circuit breaker SF6 circuit breaker Vacuum circuit breaker

Description : What are the different Generator Protections employed in Thermal Power Plants?

Last Answer : Answer: Faults in the windings, Over load protection, Over heating of windings or bearings, Over speed protection, Loss of Excitation protection, Motoring operation protection, Inadvertent ... , out of step operation protection, sub-synchronous oscillations protection and earth fault protection

Description : What are the different Generator Protections employed in Thermal Power Plants?

Last Answer : Faults in the windings, Over load protection, Over heating of windings or bearings, Over speed protection, Loss of Excitation protection, Motoring operation protection, Inadvertent energisation ... , out of step operation protection, sub-synchronous oscillations protection and earth fault protection

Description : What are the protections used in 415 V Class II side?

Last Answer : LV to UPS 1. CTZM 2. 50 (instantaneous over current) 3. short circuit UPS to PMCC S & T 1. 51 RYB (inverse over current) 2. 27 (under voltage) 3. 51N (earth fault) From Class III to Class II tie CTZM at Class III and 51, 51N at Class II. 

Description : What are the protections used in Class III & Class IV 415 V LV side?  

Last Answer : Class III 415 V LV side 1. 51 (inverse over current) 2. 50 (instantaneous over current) 3. 27 (under voltage) 4. 51N (earth fault) 5. 64 (REF)  Class IV 415 V LV side 1. 51 RYB (inverse over current) 2. 51N (earth fault) 

Description : What are the protections are there for lines?  

Last Answer : Directional earthfault protection Directional over current protection Local breaker back up protection Pole discrepancy Main protection (distance protection)

Description : What are the protections are there for BUSBAR?

Last Answer : Instantaneous over current protection Bus bar differential protection Local breaker back up protection 

Description : What are the protections for UT?  

Last Answer : a) Differential protection b) LV restricted earthfault protection c) LV back up earthfault and over current protection d) Buchholz and high oil, winding temperature protection. 

Description : What are the protections for SUT? 

Last Answer : a) Over current protection for phase and earth fault b) Differential protection c) HV and LV restricted earthfault protection  d) HV side directional back up over current protection for phase ... protection f) Over fluxing protection g) Buchholz and high oil, winding temperature protection. 

Description : What are the protections for GENERATOR TRANSFORMER?  

Last Answer : a) Differential protection b) Restricted earthfault protection c) Backup earthfault protection d) GT phase back up protection e) Overfluxing protection f) Oil surge (gas) protection g) High winding temperature and oil temperature protection. 

Description : What are the built in protections for transformers?

Last Answer : a) Buchholz relay b) Explosion vent or relief valve c) Gas operated relay for on load tap changers. 

Description : What are the working principles of generator main protections?

Last Answer : GENERATOR START UP PROTECTIONS SUPPLEMENTARY PROTECTION OF GENERATOR The generator is normally expected to run rated speed before excitation power is applied by closing the field breaker. ... position to ensure that the protection is inoperable when the machine is connected to grid.  

Description : How are circuits protections devices connected to the circuit they are intended to protect and why are they connected in this way?

Last Answer : In series, so total current will be stopped when the device opens.

Description : What is the significance of SF6 gas pressure in 6.6kV breakers?

Last Answer : Density gauge Green – correct SF6 pressure (3 –3.5bar) Yellow – pressure for breaking system fault current (refilling should be done) Red – SF6 pressure less than 2 bar, which indicates leak in the system. 

Description : What FCN was implemented to avoid reactor trip on 220V-DC failure of PHT and PPP breakers?

Last Answer : The breaker close position supervision relay VAA 21 is changed by VAJC type, contacts position do not change if 220V-DC is lost now.

Description : Why under voltage tripping of motor is incorporated in motor feeder breakers? 

Last Answer : The under voltage can occur in case of bus fault. If the motors are kept connected they will feed the fault which may cause the damage. Due to the back feeding from the motor the motor will slow down ... case pht motor will not rotate for the designed 3 minute period in case of bus under voltage).  

Description : What is the difference in action of lock out pressure signal on 6.6 kV and 220 kV breakers?

Last Answer : When lock out signal comes to 6.6 kV breakers the breaker will trip. Where as in case of 220 kV breakers the breaker will not trip. If the breaker is open it will be open only and can not be closed. If it is in closed condition it will be closed.

Description : When I run more electrical appliances, the circuit breakers go out and I have to go "throw them". How to fix it? Call us electricians to put stronger circuit breakers? Or how is it handled?

Last Answer : calculate the power consumption of the appliances (current must be lower than the value of the circuit breaker (s)) the question is what appliances are involved (some, typically motors, need more ... "electricity", invite electricians and have specific options and needs explained "on the spot". ;-)

Description : When there's a storm outside and it hits the lead, will it help me that I have circuit breakers at home? Or what will burn in the drawer so?

Last Answer : the circuit breaker will not help, even the switched-off switch in the socket will not help, it may not burn out, but the electronics may be destroyed - even invisibly from the outside -

Description : Where are all the controls on most circuit breakers?

Last Answer : The only control on a circuit breaker is its on/off/reset leveror button.