An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= _____. 

1 Answer

Answer :

An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= 0.6 

Related questions

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : The maximum demand of consumer is 2 kW and his daily energy consumption is 20 units. Its Load Factor is (1) 10.15% (2) 41.6 % (3) 50 % (4) 60% 

Last Answer : Total maximum demand of energy in a day = 2kw*24= 48 units Consumer consumption is 20 units . Load factor = (number of units utilizing)/(total max. demand)      = 20/48 = 41.6%

Description : A consumer consumes. 600 kWh per day at a load factor of 0.40. If the consumer increases the load factor of 0.70 without increasing the maximum demand, what is the consumption of energy in kWh?

Last Answer : A consumer consume. 600 kWh per day at a load factor of 0.40. If the coneumer increases the load factor of 0.70 without increasing the maximum demand, 1050 kWh is the consumption of energy in kWh.

Description : The corona loss in a 50 Hz system is 0.25 kW/ph/km. At a frequency of 60 Hz, the corona loss would be   (a) 0.30 kW/ph/km (b) 0.36 kW/ph/km (c) 028 kW/ph/km (d) 0.21 kW/ph/km

Last Answer : The corona loss in a 50 Hz system is 0.25 kW/ph/km. At a frequency of 60 Hz, the corona loss would be 028 kW/ph/km

Description : The connected load of a consumer is 2 kW and his maximum demand is 1.5 kW. The load factor of the consumer is (a) 0.375 (b) 0.75 (c) 1.33 (d) None of these  

Last Answer : a

Description : Two synchronous generators G1, G2 are operating in parallel and are equally sharing KVAR (Lag) component of load. To shift part of KVAR from G2 to G1, while keeping terminal voltage fixed, the following action must be done

Last Answer : Two synchronous generators G1, G2 are operating in parallel and are equally sharing KVAR (Lag) component of load. To shift part of KVAR from G2 to G1, while keeping terminal voltage fixed, the following action must be done Raise If1 and lower If2

Description : At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes (A) 0.85 (B) 1.00 (C) 0.80 lag (D) 0.90 lag

Last Answer : At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes  0.80 lag

Description : The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be?

Last Answer : The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be 0.667 kW/phase/km.

Description : A three-phase alternator is operating at 450 volts, 250 amps at 0.6 power factor. If the power factor increases to 0.8, the kw load potential will increase by _____________. A. 38.525 kw B. 116.91 kw C. 155.88 kw D. 194.85 kw

Last Answer : Answer: A

Description : The power of a locomotive is 315 kW and the total weight of the train is 2000 kN. If the track resistance is 15 N per kN, the maximum speed that the locomotive can attain on level track will be a.43 kmph b.83 kmph c.103 kmph d.107 dynes e.38 kmph

Last Answer : e. 38 kmph

Description : The power of a locomotive is 315 kW and the total weight of the train is 2000 kN. If the track resistance is qN per kN, the maximum speed that the locomotive can attain on level track will be a.103 kmph b.83 kmph c.107 dynes d.43 kmph e.63 kmph

Last Answer : e. 63 kmph

Description : In 2000-2001 the quantum of power has rose to ...... a) 45.29 million kW c) 170 million kW b) 85 million kW. d) 145 million kW

Last Answer : 170 million kW

Description : Two Pelton turbines A and B have the same specific speed and are working under the same head. Turbine A produces 400 kW at 1000 rpm. If turbine B produces 100kW, then its rpm is (a) 4000 (b) 2000 (c) 1500 (d) 3000

Last Answer : (b) 2000

Description : Why do Mexico and other countries in Central America lag behind in industrial development? -Geography

Last Answer : They lag behind in industrial development because most of these countries are small and do not have adequate power resources and raw materials needed for industrial development.

Description : Which of the following statements is correct concerning the motor performance curves and data table shown in the illustration? EL-0006 A. The motor RPM at full load is 1737 RPM. B. The motor draws 12.62 kw ... If the motor was developing 10 HP its power factor would be 0.92. D. All of the above.

Last Answer : Answer: D

Description : A 3-phase 50HZ SCIM takes a power input of 30 KW at its full load speed of 1440 rpm. Total stator losses are 1 KW. The slip and rotor ohmic losses at full load are a) 0.02, 600 W b) 0.04, 580 W c) 0.04, 1160 W d) 0.04, 1200 W

Last Answer : Ans: 0.04, 1160 W

Description : In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is :

Last Answer : In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is : 0.075

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be

Last Answer : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be 10 A

Description : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

Last Answer : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is 1.088 p.u.

Description : A 40 kW engine has a mechanical efficiency of 80 %. If the frictional power is assumed to be constant with load, what is the approximate value of the mechanical efficiency at 50 % of the rated load? (a) 45% (b) 55 % (c) 65% (d) 75%

Last Answer : Ans :c

Description : A vessel is equipped with two ship's service generators. Generator #1 is rated at 900 kw and generator #2 is rated at 600 kw. During parallel operation, with a hotel load of 1,000 kw, what should be the kw load on generator #2? A. 100 kw B. 400 kw C. 500 kw D. 600 kw

Last Answer : Answer: B

Description : A turbogenerator has a rated output of 1200 KW at 60 Hertz, with a no load frequency of 61.5 Hertz. What is its speed droop? A. 1.03% B. 1.50% C. 2.44% D. 2.50%

Last Answer : Answer: D

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : Which is a function of the voltage regulators used with AC generators? A. To cut out generators when they are no longer required. B. To cut in additional generators automatically as ... between generators operating in parallel. D. To divide reactive current between generators operating in parallel.

Last Answer : Answer: D

Description : A building intended to be used for commercial purpose will be required to follow Energy conservation building code under Energy Conservation Act, 2001 provided its a) connected load is 120 kW and above b) ... and above c) connected load is100 kW and above or contract demand is 120 kVA and above

Last Answer : c) connected load is100 kW and above or contract demand is 120 kVA and above

Description : The formula for tension difference or effective pull, required to transmit the load at.... (a) (Tt-Ts)=1000(kw/V) (b) Tt/Ts=c^ke (c) (Tt-Ts)= 1000(Hp/V) (d) None of the above

Last Answer : (a) (Tt-Ts)=1000(kw/V)

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : A 50 KVA transformer has iron loss 2 kW on full load. Calculate its iron loss at 75% of full load.

Last Answer : Iron loss is dependent on voltage and independent of load. Hence iron loss at 75% of Load = Iron loss at full load = 2 kW

Description : A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is  (A) 1.66 Nm (B) 95.50 Nm (C) 99.47 Nm (D) 624.73 Nm

Last Answer : A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is 99.47 Nm

Description : A meter whose constant is 600 revolutions/kWh makes 5 revolutions in 20 seconds. Calculate the load in kW. (1) 0.5 kW (2) 1 kW (3) 1.5 kW (4) 2 kW  

Last Answer : 1.5 kW 

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : A 150 kW electric motor has an efficiency of 92 %, when it operates at full load. Calculate the losses in the machine.  (A) 92 kW (B) 150 kW (C) 163 kW (D) 13 kW 

Last Answer : efficiency  -output /input * 100 150/0.92----------163(input) losses-----(163--150)  ---------13kw.

Description : At dead short circuit at terminals of Alternator then the current I is a) ZPF Lag b) ZPF lead c) Unity power factor d) 0.8 Power factor lag

Last Answer : Ans: ZPF Lag

Description : A three-phase alternator operates at 450 volts with a power factor of 0.8. If the ammeter indicates 250 amperes, what should be the KW meter reading? A. 90.00 KW B. 127.27 KW C. 155.70 KW D. 194.85 KW

Last Answer : Answer: C

Description : A three-phase alternator is developing 300 amps, with a 0.8 power factor, at 450 volts. The true indicated power on the kilowatt meter, located on the main switchboard, will be ____________. A. 133 kw B. 155 kw C. 187 kw D. 212 kw

Last Answer : Answer: C

Description : A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter would then read ____________. A. 181.4 KW B. 186.8 KW C. 194.2 KW D. 201.4 KW

Last Answer : Answer: B

Description : A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter reading would increase by ___ A. 17.8 KW B. 23.2 KW C. 30.6 KW D. 37.8 KW

Last Answer : Answer: B

Description : The thermal radiative flux from a surface of emissivity = 0.4 is 22.68 kW/m2 . The approximate surface temperature (K) is (Stefan-Boltzmann constant = 5.67 × 10 -8 W/m2 .K4 ) (A) 1000 (B) 727 (C) 800 (D) 1200

Last Answer : (A) 1000

Description : The radiation heat flux from a heating element at a temperature of 800°C, in a furnace maintained at 300°C is 8 kW/m2 . The flux, when the element temperature is increased to 1000°C for the same furnace temperature is (A) 11.2 kW/m2 (B) 12.0 kW/m2 (C) 14.6 kW/m2 (D) 16.5 kW/m

Last Answer : (D) 16.5 kW/m2

Description : COP of a refrigerator drawing 1 kW of power per ton of refrigeration is about (A) 0.5 (B) 3.5 (C) 4.5 (D) 8.5

Last Answer : (B) 3.5

Description : The power intensity of Indian farms increase from ...... to kW/hectare on basis of net-cropped area. a)0.2 to 1.30. c) 1.0 to 2.5 b) 0.5 to 1.60. d) 1.3 to 2.8

Last Answer : 0.2 to 1.30.

Description : The likely estimate on equivalent power wastage for a leakage from 7 bar compressed air system through 1.6 mm orifice size is ____ a) 0.2 kW b) 3.0 kW c) 0.8 kW d) 12 kW

Last Answer : c) 0.8 kW

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : If the reference bus is changed in two load flow runs with same system data and power obtained for reference bus taken as specified P and Q in the latter run, the system losses  A) Will be ... C) As well as complex bus voltage will changed D) As well as complex bus voltage will be unchanged

Last Answer : If the reference bus is changed in two load flow runs with same system data and power obtained for reference bus taken as specified P and Q in the latter run, the system losses Will be unchanged but complex bus voltages will change

Description : If a voltage-controlled bus is treated as load bus, then which one of the following limits would be violated?   (a) Active power (b) Reactive power (c) Voltage (d) Phase angle 

Last Answer : If a voltage-controlled bus is treated as load bus, then which one of the following limits would be violated?   (a) Active power (b) Reactive power (c) Voltage (d) Phase angle 

Description : In load flow Study, a PV bus is treated as a PQ bus when

Last Answer : Voltage at the bus becomes high 

Description : Load factor is the  (1) Ratio of maximum load on the station to sum of consumer's maximum load.  (2) Ratio of average demand to maximum demand.  (3) Factor used for increasing load.  (4) Reciprocal of (1).

Last Answer : Load factor is the Ratio of average demand to maximum demand. 

Description : A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

Last Answer : 0