What is the time of operation of a relay of rating 5 amp 2.2 sec, IDMT and having a relay of setting of 125% Tms = 0.6 It is connected to a supply circuit through a CT, 400 ratio. The fault current is 400 amp.

1 Answer

Answer :

1.92 sec is the time of operation of a relay of rating 5 amp 2.2 sec, IDMT and having a relay of setting of 125% Tms = 0.6 It is connected to a supply circuit through a CT, 400 ratio. The fault current is 400 amp.

Related questions

Description : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is

Last Answer : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is 6.25A

Description : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be

Last Answer : If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be 10 A

Description : Boiler rating is usually defined in terms of  (1) Maximum temperature of steam in Kelvin (2) Heat transfer rate in KJ/hr (3) Heat transfer area in metre2 (4) Steam output in kg/hr

Last Answer : Boiler rating is usually defined in terms of Steam output in kg/hr

Description : When charging a 100 amp-hour lead-acid battery, ___________. A. the temperature of the electrolyte should not be allowed to exceed 90°F B. the charging rate should be no greater than 125% of the ... nearing full charge and it will be necessary to reduce the charging current to a low finishing rate

Last Answer : Answer: C

Description : What is the line current of a circuit when the current transformer of 1000 : 5 rating measures 4 amp? (A) 5000 amp (B) 1000 amp (C) 400 amp (D) 800 amp 

Last Answer : What is the line current of a circuit when the current transformer of 1000 : 5 rating measures 4 amp? (A) 5000 amp (B) 1000 amp (C) 400 amp (D) 800 amp 

Description : The transmission line distance protection relay having the property of being inherently directional is (A) impedance relay (B) MHO relay (C) OHM relay (D) reactance relay

Last Answer : The transmission line distance protection relay having the property of being inherently directional is MHO relay

Description : A negative sequence relay is commonly used to protect  (A) an alternator (B) an transformer (C) a transmission line (D) a bus bar

Last Answer : A negative sequence relay is commonly used to protect  an alternator

Description : A reactance relay is (A) Voltage restrained directional relay (B) Directional restrained over-current relay (C) Voltage restrained over current relay (D) Directional restrained over voltage relay

Last Answer : A reactance relay is Directional restrained over-current relay

Description : In three pin plug 6 Amp. 220v AC rating. why earth pin diameter is higher than ohter two pin? what its purpose ?

Last Answer : Because Current flow in the conductor is inversely proportional to the conductor diameter. So if any short circuits occur in the system first high currents bypassed in the Earthling terminal.( R=Pl/a area of the conductor increases resistance value decreases)

Description : In accordance with Coast Guard Regulations (46 CFR), each battery operated relay-controlled lantern must _____________. A. be readily portable B. contain a dry cell battery having a minimum capacity of ... automatic battery charger to maintain the battery in a fully charged state D. all of the above

Last Answer : Answer: C

Description : Coil of relay is connected to the A. input of op-amp B. output of op-amp C. midpoint of op-am D. anywhere in between input and ouput of op-amp

Last Answer : output of op-amp

Description :  A device used to avoid the relay destroying the op-amp is A. diode B. LED C. reverse bias diode D. forward biased diode

Last Answer : reverse bias diode

Description : The relay with inverse time characteristic will operate within (a) 1.5 sec (b) 5 to 10 sec (c) 5 to 20 sec (d) 20 to 30 sec (e) none of the above

Last Answer : (b) 5 to 10 sec

Description : The receptor transduction mechanism with the fastest time-course of response effectuation is: A. Adenylyl cyclase-cyclic AMP pathway B. Phospholipase C-IP3: DAG pathway C. Intrinsic ion channel operation D. Protein synthesis modulation

Last Answer : C. Intrinsic ion channel operation

Description : In op-amp operation, Common Mode Rejection Ratio (CMRR)

Last Answer : In op-amp operation, Common Mode Rejection Ratio (CMRR) is desired to be high

Description : A type rating is applicable to: a. An aircraft requiring a Certificate of Airworthiness b. An aircraft with a Certificate of Airworthiness issued by the State c. An aircraft that requires multi-pilot operation d. An aircraft that requires additional skills training

Last Answer : c. An aircraft that requires multi-pilot operation

Description : A type rating is applicable to: a. An aircraft requiring a Certificate of Airworthiness b. An aircraft with a Certificate of Airworthiness issued by the State c. An aircraft that requires multi-pilot operation d. An aircraft that requires additional skills training

Last Answer : c. An aircraft that requires multi-pilot operation

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : If the centrifugal switch or relay used for cutting out the starting winding of a split-phase induction motor fails to open once the motor is in operation, the _____________. A. motor will overspeed B ... C. motor will immediately stall under load D. motor torque will be above normal at rated speed

Last Answer : Answer: B

Description : During its operation, loud buzzing and resultant welding of contacts of a magnetic relay may be caused by __________. A. overheating of the contactor coil B. low voltage on the operating coil C. low insulation resistance to ground D. lubrication of the contact bearing points

Last Answer : Answer: B

Description : Sources of impulse noise induced in communication channels. A. Erroneous digital coding bit caused by an error on a transmission facility B. Transients due to relay operation C. Crosstalk from dc signaling systems D. All of these

Last Answer : D. All of these

Description : Explain the principle of operation of attracted armature relay with equation and characteristics curve.

Last Answer : Principle: It works on the principle that when a current is passed through a coil magnetic lines of force develop and the coil behaves like a magnet. When we place a magnetic material inside the coil it is ... ) time delay. If we want a time delay we can add a slug in the armature core.  

Description : Which of the following statements is incorrect? (a) Station batteries are used to operate relay only (b) The lightning arresters are basically surge diverters (c) An impedance relay has maximum fault current when fault occurs near the relay (d) A high speed relay has an operation of 1 to 2 cycles

Last Answer : (a) Station batteries are used to operate relay only

Description : With the help of neat diagram, explain operation of static relay.

Last Answer : Operation of Static Relay: Operation: 1) The solid-state component used are transistors, diodes, resistors, IC s, capacitor etc. The function of comparison and measurement are accomplished by ... ) An auxiliary dc supply is provided for operation of static relay elements as shown in figure.

Description : Describe the construction and Operation of Buchholz relay with neat labeled diagram.

Last Answer : Construction of Buchholz Relay: It takes the form of a domed vessel placed in the connecting pipe between the main tank and the conservator. The device has two elements. The upper element ... manner that it senses the sudden violent movement of oil/gas from transformer tank to conservator. 

Description : Describe the operation of current differential relay with neat sketch.

Last Answer : Operation of Current Differential Relay: Figure shows an arrangement of an overcurrent relay connected to operate as a differential relay for alternator protection under fault conditon. ... current flows through relay coil, causing relay to operate for protection of alternator winding.

Description : Explain operation of balanced beam type relay.

Last Answer : Balanced Beam Type Relay: Under normal operating condition the current through relay coil is such that the beam is held in the horizontal position by the spring. When the fault occurs on the system the ... becomes greater than pick-up value and beam is attracted to close the trip circuit. 

Description : Explain operation of µP based relay with block diagram

Last Answer : Operation of Microprocessor (µP) based relay: The inputs from the power system through CTs and PTS are received by the analog Input receiver; they are sampled simultaneously or ... compares the dynamic inputs and decides accordingly to generate trip/alarm signal to the output device.

Description : Explain construction and operation of induction type directional over current relay.

Last Answer : Directional overcurrent relay: Construction: It consists of two units: i) Non-directional Over-current unit ii) Directional power unit The directional unit consists of upper electromagnet ... closes the trip circuit. This operates circuit breaker which isolates the faulty section. 

Description : Describe the operation of solid state relay.

Last Answer : Solidstate relay is electronic equivalent of an electromechanical relay. It consists of controlled power semiconductor switch like triac. There are four terminals. Two are the power terminals for load and two control ... is turned ON. When triac is ON, the load is connected to AC supply

Description : The operation of the relay which is most affected due to arc resistance is A) Mho relay B) Reactance relay C) Impedance relay D) All are equally affected

Last Answer : The operation of the relay which is most affected due to arc resistance is Mho relay

Description : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  (1) second harmonic current  (2) third harmonic current  (3) fifth harmonic current  (4) seventh harmonic current

Last Answer : To prevent mal-operation of differentially connected relay while energizing a transformer, the relay restraining coil is based with  second harmonic current 

Description : has amplitude of vibration is 200mm and frequency of operation is 400 cycle/ sec. b. Acme tooth harrow c. Blade harrow d. None of the above

Last Answer : Ans- a. Reciprocating power harrow

Description : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the infinite bus voltage is 1 pu. The ... fault at the generator terminal is  (A) 53.5 (B) 60.2 (C) 70.8 (D) 79.6

Last Answer : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the ... clearing angle, in degrees, for a three-phase dead short circuit fault at the generator terminal is 79.6

Description : The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

Last Answer : Vscos¢s-Vrcos¢r=IR

Description : If a 5-bus test system contains 6 transmission lines and one transformer, how many non-zero elements are there in the system Y-bus ? (A) 25 (B) 12 (C) 11 (D) 19

Last Answer : If a 5-bus test system contains 6 transmission lines and one transformer, 19 non-zero elements are there in the system Y-bus.

Description : The time taken for a surge to travel a 600 km long overhead transmission line is?

Last Answer : The time taken for a surge to travel a 600 km long overhead transmission line is 0.002s.

Description : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

Last Answer : The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: 400 Mega Joule

Description : Which statement out of the following statements about ‘corona’ is incorrect? A) Corona gives rise to radio interference B) Corona results in loss of power in transmission C) Corona discharge can be observed as red luminescence D) Corona is always accompanied by a hissing voice

Last Answer : Which statement out of the following statements about ‘corona’ is incorrect? A) Corona gives rise to radio interference B) Corona results in loss of power in transmission C) Corona discharge can be observed as red luminescence D) Corona is always accompanied by a hissing voice

Description : A DC reactor is connected in series with each pole of a converter station in order to: A) prevent commutation failures in the inverter B) supply reactive power to the converter C) improve system stability D) increase the power transfer capability

Last Answer : A DC reactor is connected in series with each pole of a converter station in order to:  prevent commutation failures in the inverter

Description : The melting point of carbon is: A) 1800 degree Centigrade B) 2200 degree Centigrade C) 3500 degree Centigrade D) 5500 degree Centigrade

Last Answer : The melting point of carbon is:  3500 degree Centigrade 

Description :  A power system is subjected to a fault which makes the zero sequence component of current equal to zero. The nature of fault current is: A) Double line to ground fault B) Line to line fault C) Line to ground fault D) Three-phase to ground fault

Last Answer :  A power system is subjected to a fault which makes the zero sequence component of current equal to zero. The nature of fault current is: Line to line fault

Description : The zero sequence current of a generator for line to ground fault is j 2.4 p.u. The current through the neutral during the fault is (a) j 0.8 p.u (b) j 2.4 p.u. (c) j 0.24 p.u. (d) j 7.2 p.u. 

Last Answer : j7.2

Description : It is always economical to improve the power factor of an electric installation to (a) zero (b) unity (c) a little less than unity (d) a little more than unity 

Last Answer : To  a  little  less  than  unity.

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : Choose two appropriate auxiliary components of a HVDC transmission system from the following P. D.C line inductor Q. A.C line inductor R. Reactive power sources S. Distance relays on D.C line T. Series capacitance on A.C. line  (A) P and Q (B) P and R (C) Q and S (D) S and T

Last Answer : Choose two appropriate auxiliary components of a HVDC transmission system from the following P. D.C line inductor Q. A.C line inductor R. Reactive power sources S. Distance relays on D.C line T. Series capacitance on A.C. line  (A) P and Q (B) P and R (C) Q and S (D) S and T

Description : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are (A) 6 (B) 12 (C) 16 (D) 24

Last Answer : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are 24