Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The line voltage of the first machine is adjusted to 3300 V and that of the second machine is adjusted to 3200 V. The machine voltages are in phase at the instant they are paralleled. Under this condition, the synchronizing current per phase will be 

(A) 16.98 A (B) 29.41 A (C) 33.96 A (D) 58.82 A

1 Answer

Answer :

Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The line voltage of the first machine is adjusted to 3300 V and that of the second machine is adjusted to 3200 V. The machine voltages are in phase at the instant they are paralleled. Under this condition, the synchronizing current per phase will be 16.98 A

Related questions

Description : In single-phase alternators, in order for the voltages induced in all the armature windings to add together for a single output, how must the windings be connected?

Last Answer : In series.

Description : The graph shown in the illustration represents the speed droop curves of two equal capacity alternators about to be paralleled. When paralleled, the greater portion of the total load above 60% for each unit will be picked up ... unit 'A' B. by unit 'B' C. equally by each unit D. none of the above

Last Answer : Answer: A

Description : Two paralleled alternators are operating near rated load. If one trips out mechanically, which of the listed actions should be taken FIRST? A. Restart the tripped machine immediately. B. Strip the board ... circuits. C. Start the emergency generator. D. Transfer all vital loads to the emergency bus.

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation of the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. type of alternator

Last Answer : Answer: B

Description : The division of kilowatt load between two paralleled alternators is determined by the _____________. A. amount of field excitation to the leading machine B. load-speed characteristics of the governors C. amount of field excitation to the lagging machine D. number of field poles per alternator

Last Answer : Answer: B

Description : If the excitation of an alternator operating in parallel with other alternators decreased, its: (1) Power factor becomes more leading (2) Output Kw will change (3) Power factor becomes more lagging (4) Power factor becomes unity

Last Answer : If the excitation of an alternator operating in parallel with other alternators decreased, its: Power factor becomes more leading

Description : Which rotor is use for high speed in turbo alternators?

Last Answer : Non-salient pole rotor is used for high speed in turbo alternators.

Description : Which of the following statements is true concerning all three-phase alternators? A. Each has three separate but identical armature windings acted on by one system of rotating magnets. B. Each has one ... The three phases always provide power to the load through three sets of slip rings and brushes.

Last Answer : Answer: A

Description : When shore power is being connected to a ship in dry dock, _____________. A. the ship's generators are paralleled with the shore power to provide continuous power B. proper phase sequence must be ... 450 volts must be supplied from the shore D. exactly 60 Hz must be provided by the terminal

Last Answer : Answer: B

Description : A field excitation of 20 A in a certain alternator results in an armature current of 400 A in short circuit and a terminal voltage of 2000 V on open circuit. The magnitude of the internal voltage drop within the machine at a load current of 200 A is  (A) 1 V (B) 10 V (C) 100 V (D) 1000 V

Last Answer : 800

Last Answer : D.C. generators are connected to the busbars or disconnected from them only under the floating condition to avoid sudden loading of the primemover, to avoid mechanicaljerk to the shaft, to avoid burning of switch contacts.

Description : The angular displacement between two interconnected stations is mainly due to (a) armature reactance of both alternators (b) reactance of the interconnector (c) synchronous reactance of both the alternators (d) all of the above

Last Answer : (a) armature reactance of both alternators

Description : Will The Alternators Have Rotating Armature System Or Stationary Armature System?

Last Answer : Generally in alternators, the armature is stationary and the field rotates. Small low-voltage alternators often have a rotating armature and a stationary field winding. But in large alternators rotating armature field type is used.

Description : What is meant by armature reaction in Alternators?

Last Answer : The effect of armature flux on main flux

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description :  The driving power from the prime-mover driving the alternator is lost but the alternator remains connected to the supply network; the field supply also remains on. The alternator will: A) ... as a synchronous motor but will rotate in a reverse direction to that corresponding to generator action 

Last Answer : The driving power from the prime-mover driving the alternator is lost but the alternator remains connected to the supply network; the field supply also remains on. The alternator will: behave as a synchronous motor and will rotate in the same direction

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : When paralleled, AC generators must have the same _________. A. frequency B. number of phases C. phase rotation D. all of the above

Last Answer : Answer: D

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : In an alternator at lagging power factor the generated voltage per phase as compared to that at unity power factor?

Last Answer : In an alternator, at lagging power factor the generated voltage per phase as compared to that at unity power factor must be more than terminal voltage.

Description : Why EHV busbars are hallowed and circular?

Last Answer : Answer: To avoid corona effect

Description : The under voltage relay can be used for (a) generators (b) busbars (c) transformers (d) motors (e) all of the above

Last Answer : (e) all of the above

Description : Explain differential protection scheme for busbars with neat sketch.

Last Answer : Differential Protection Scheme for Bus bar:  Under normal conditions, the sum of the currents entering the bus bar zone is equal to those leaving it and no current flows through the relay ... of these currents will flow through the relay coil causing opening of circuit breaker of bus-bar.

Description : When paralleling two alternators, the synchronizing lamps remain lit as the synchroscope pointer approaches the 0°. This indicates the _____________. A. incoming alternator is running too fast B. alternator ... apart C. synchroscope is defective or broken D. alternator power factors are in phase

Last Answer : Answer: C

Description : When paralleling two alternators the synchronizing lamps grow dim and are totally darkened as the synchroscope pointer approaches the 0° position. This indicates the ____________. A. alternator voltages ... alternator is in phase with the bus voltage D. synchroscope pointer is defective or broken

Last Answer : Answer: C

Description : When paralleling two alternators using three synchronizing lamps, the flickering of all three lamps becomes progressively slower and slower. This means the ______________. A. frequency of the incoming ... the bus D. terminal voltage of the incoming alternator is approaching that of the bus

Last Answer : Answer: A

Description : To equalize the power factor of two alternators operating in parallel, the ____________. A. field excitation of both units is adjusted B. governors of both units are adjusted C. phase sequence is altered D. kilowatt load is evenly divided

Last Answer : Answer: A

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B

Description : Handheld phase sequence indicators are useful when ________. A. preparing to parallel alternators B. connecting lighting branch circuits C. troubleshooting DC motors D. connecting shore power lines to the ship

Last Answer : Answer: D

Description : Which of the following statements is true concerning the operation of two alternators in parallel? A. The cycles per second of each alternator are the same. B. Both alternator governors must be set ... be the same on each alternator. D. The load must always be divided equally between alternators.

Last Answer : Answer: A

Description : An equalizing connection between two compound-wound DC generators when paralleled, serves to _____________. A. reverse the polarity of the incoming generator as the series field weakens B. automatically ... the series field of the incoming generator D. parallel the series fields of the generators

Last Answer : Answer: D

Description : When two AC generators are being paralleled, the breaker should be closed with the synchroscope pointer rotating in the ____________. A. 'slow' direction, just before the 12 o'clock position B. 'fast' ... just before the 12 o'clock position D. 'slow' direction, just after the 12 o'clock position

Last Answer : Answer: C

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : An alternator is being paralleled with one on the line. At the INSTANT the circuit breaker is closed, the frequency of the incoming alternator will normally _____________. A. increase B. not change C. decrease D. be exactly 60 hertz

Last Answer : Answer: C

Description : The kilowatt load can be adjusted on a paralleled generator by using the _____________. A. field rheostat B. governor control C. automatic voltage regulators D. hand tachometer

Last Answer : Answer: B

Description : A shore power circuit breaker should be closed only _____________. A. when the ship's generators have been directly paralleled to those on shore B. in a shipyard C. if a quick disconnect coupling is used D. when the ship's generators have been removed from the bus

Last Answer : Answer: D

Description : Why is it desirable to operate paralleled AC generators at the same power factor? A. Circulating currents are kept to a minimum. B. Field excitation losses are kept to a minimum. C. Generator ... will have a lesser tendency to hunt. D. Because a power factor increase will decrease kilowatt output.

Last Answer : Answer: A

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : A series wound DC motor has its armature and field connected in series with a resistor. When the motor is disconnected from its power supply, this motor will exemplify __________. A. the ... the proper connections for an automatic strip heater C. a reversing controller circuit D. dynamic braking

Last Answer : Answer: D

Description : A DC shunt generator has its field windings connected in _____________. A. series with the series windings B. parallel with the field rheostat C. series with the armature windings D. parallel with the armature windings

Last Answer : Answer: D

Description : Which of the following types of DC motors has its field connected in parallel with its armature? A. Counter EMF B. Shunt C. Salient pole D. Series

Last Answer : Answer: B

Description : To carry out an insulation resistance test, one terminal of the megohmmeter should be connected to the winding, with the other terminal being connected to the ____________________. A. power supply B. variable resistor C. frame of the machine D. armature

Last Answer : Answer: C

Description : Which one of the following statements for a dc machine which is provided with inter pole winding (IW) as well as compensating winding (CW) is correct a) Both IW and CW are connected in ... parallel with Armature winding d) CW connected in series but IW is connected in parallel with Armature winding

Last Answer : Ans: Both IW and CW are connected in series with Armature winding

Description : The number of parallel paths in armature winding of four pole wave winding connected dc machine having 22 coil sides is (1) 4 (2) 22 (3) 2 (4) 11 

Last Answer : Ans- Option (3) because wave winding always have 2 parallel paths

Description :  The number of parallel paths in the armature winding of a 4 -pole, wave connected d.c. machine having 28 coilside is : -  a) 28 b) 14 c) 4 d) 2

Last Answer : 2

Last Answer : The commutator segments are connected to the armature conductors by means of copper lugs.

Last Answer : In a A.C. series motor armature coils are usually connected to commutator through resistance.

Description : State working principle of alternator. State the meaning self and separate excitation. 

Last Answer : Working principle of alternator: When a conductor is moved in magnetic field or a magnetic field moved with respect to conductor, according to Faraday's law of electromagnetic induction, the conductor ... like battery or shaft-mounted exciter, then the excitation is said to be separate excitation.

Description : Explain the construction of alternator with neat diagram.

Last Answer : Diagram: Construction of three phase alternator: Construction wise, an alternator generally consists of field poles placed on the rotating fixture of the machine i.e. rotor as shown in the ... of rotor used in construction of alternator, 1. Salient pole type. 2. Cylindrical rotor type.