What is the purpose of back up impedance protection in main generator?  

1 Answer

Answer :

Covers inter-phase faults both externals to the GT and in GT. This also covers partially faults inside generator, time delayed to coordinate with 230 kV-distance protection. 

Related questions

Description : The purpose of a short circuit forcing module (short time trip) installed in a branch line is to provide ____________. A. high speed clearance of low impedance short circuits in the branch B. ... C. isolation of short circuits by selective tripping of branch circuit breakers D. all of the above

Last Answer : Answer: D

Description : Why main generator/UT is not provided with separate overfluxing protection?

Last Answer : Since GT is provided with overfluxing protection, it is adequate to protect main generator / UT also. Main generator can withstand higher degree of overfluxing. If a generator CB is used, separate overfluxing protection is essential for main generator. 

Description : Why 100% winding protection is felt essential for main generator stator E/F protection? (Used in NAPS onwards?)  

Last Answer : At MAPS 4% of winding is not protected. Earlier felt that the Electro magnetic stress due high external fault currents near 4% of neutral may not be high to cause E/F here. But now felt that the mechanical stress can leads to E/F. 

Description : How main generator protection grouped?

Last Answer : The various protections associated with the generator, Generator transformer and Unit transformer are connected to a trip unit through trip relays 86A, 86B and 86C. The protective levels of generator are in ... breaker. During Class C trip, the generator will come on House load mode of operation.  

Description : The purpose of the automatic bus transfer shown in the illustration is to ___________. EL-0014 A. stepdown voltage to the lighting distribution panel B. provide emergency power to ... emergency switchboard from the main switchboard D. provide overcurrent protection to the lighting distribution panel

Last Answer : Answer: B

Description : The main purpose of an electric space heater installed in a large AC generator is to _____________. A. keep the lube oil warm for quick starting B. prevent moisture from condensing in the ... is shutdown C. prevent the windings from becoming brittle D. prevent acidic pitting of the slip rings

Last Answer : Answer: B

Description : The purpose of the reverse power relay, provided on a ship's service alternator panel, is to trip the circuit in the event of ______________. A. main circuit overload B. high power transfer C. generator overspeeding D. alternator motorization

Last Answer : Answer: D

Description : The main purpose of an electric space heater installed in a large AC generator is to _____________. A. prevent the windings from becoming brittle B. prevent moisture from condensing in the windings during ... C. prevent acidic pitting of the slip rings D. keep the lube oil warm for quick starting

Last Answer : Answer: B

Description : What is the purpose of rotor AC Impedance measurement?

Last Answer : Periodic measurement of rotor impedance using an AC power supply is another means of detecting the presence of shorted turns in a rotor winding. Impedance measurement is more sensitive than the ... single shorted turn opposes the MMF of the entire coil, thus greatly reducing the reactance. 

Description : Why inter-turn protection is provided along with differential protection in generator?

Last Answer : Inter-turn protects two separate windings from the fault of the generator.  

Description : Purpose of start up protection? Is it always in service? 

Last Answer : Trips the generator. If generator is excited with internal fault the over current 50s trip the generator to prevent major damage. The earth fault relay 64c also. The relays are polarised dc armature ... initially during start up. Start up protection is cutout as soon as generator CB is closed.  

Description : The purpose of a magnetic relay is to _____________. A. open a circuit only in the event of overload B. remotely open and close contacts C. provide overcurrent protection during starting D. relay voltages at increased power

Last Answer : Answer: B

Description : The purpose of a motor undervoltage protection device is to _____________. A. prevent high armature current when power is restored B. start the motor at a very low voltage C. trip the load off the motor in case of fire D. protect personnel from low voltage shocks

Last Answer : Answer: A

Description : The purpose of an impressed current cathodic protection system aboard ship is to _______________. A. prevent corrosion of the hull, propeller, rudder and line shafting B. neutralize the vessel's ... the presence of salt air D. maintain a minimum constant alternator load to prevent overheating

Last Answer : Answer: A

Description : What is the basic purpose of class-B protection?

Last Answer : Class-B avoids load rejection. For modern machines, the inertia is less and easily gets damaged on overload. Therefore trip only for internal faults.  Low forward interlock prevents the risk of run away if a CIES valve fails to close. 

Description : Purpose of standby E/F protection in SUT/UT? 

Last Answer : Back up for LV winding, LV neutral CT- CDG 12 – resistance earthing – relay set high time delay to discriminate with LV feeder and trip transformer if sustained E/F, also protects neutral earthing resistor.

Description : ___________ is device that measures the internal open circuit voltage of an equivalent noise generator having an impedance of 600Ω and delivering noise power to a 600 Ω load. A. Psophometer B. Barometer C. Reflectometer D. Voltmeter

Last Answer : A. Psophometer

Description : Calculated the noise figure of the amplifier whose Req equals 2518Ω (RT=600Ω) if its driven by a generator whose output impedance is 50Ω. A. 39.4 B. 3.94 C. 394 D. 0.394

Last Answer : A. 39.4

Description : Discharge switches are often located on hand-driven meggers. The purpose of these switches is to discharge capacitive charges stored in the _____________. A. megger hand generator B. megger movement coils C. tested equipment while conducting test D. tested equipment after testing

Last Answer : Answer: D

Description : The purpose of DC generator brushes is to _____________. A. neutralize armature reaction B. conduct electric current to an outside circuit C. convert DC current to AC current D. provide excitation to a DC generator

Last Answer : Answer: B

Description : The purpose of the commutator and brushes on a DC generator is to _____________. A. transfer generated direct current voltage from the armature to the line B. convert the alternating voltage ... contact method to excite the field D. reduce sparking between the armature and the carbon brushes

Last Answer : Answer: B

Description : What is back up protection?

Last Answer : Is the second line of defence , which operates if the primary protection fails to activate within a definite time delay.

Description : Why auto transfer is blocked for back up protection?

Last Answer : Because Backup protection operates normally for bus faults. All main protections are generally operating for internal faults therefore there is no point in restoring the power supply through auto transfer when there is a bus fault existing. 

Description : What is Local Breaker Back up protection? 

Last Answer : In case of local breaker fails to operate during fault due to mechanical failure this protection will protect the system from sever damage. It will trip all the other breakers in that bus after time delay. 

Description : The main difference between a motor control circuit containing low voltage protection and low voltage release is that the latter contains _____________. A. a magnetic operating coil B. normally open line contacts C. thermal-overload protection D. a momentary-contact start button

Last Answer : Answer: D

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : Will main generator differential relay pick up for generator earth faults? 

Last Answer : No earth fault current limited to 5A, while differential setting is 10%. 

Description : The shipboard general alarm system must receive its main source of power from _____________. A. a storage battery B. the emergency generator C. an auxiliary generator D. the ship's service generator

Last Answer : Answer: A

Description : The source of emergency lighting and power at loss of normal ship's power on a cargo vessel should be obtained from the ______________. A. emergency generator supply to the emergency ... switchboard C. battery supply to the main switchboard D. turbogenerator supply to the emergency switchboard

Last Answer : Answer: A

Description : In preparing to take insulation resistance readings on a main generator, the windings should be grounded for about 15 minutes prior to the test to _____________. A. allow accurate zeroing of the meter ... the windings D. help the windings to cool to the same temperature as the ground test connection

Last Answer : Answer: C

Description : The prime mover of an AC two pole main propulsion generator drives the generator at 3600 RPM. If the main propulsion motor has 80 poles, what will be the propeller speed? A. 45 RPM B. 80 RPM C. 90 RPM D. 180 RPM

Last Answer : Answer: C

Description : As shown in the illustration, the motor generator(M-G) set's three-phase motor drives the ______________. EL-0101 A. motor and the generator B. motor and the exciter C. generator and the exciter D. main field and the interpole field

Last Answer : Answer: C

Description : Undervoltage trips are frequently installed on switchboard circuit breakers to trip ____________. A. out generators in the event of severe arcing or sparking B. out generators when there is reversal of power ... , but continues to run D. out generators when there is low voltage in the main circuit

Last Answer : Answer: D

Description : As shown in the illustration, the M-G set's three-phase motor drives the ______________. EL-0101 A. motor and the generator B. motor and the exciter C. generator and the exciter D. main field and the interpole field

Last Answer : Answer: C

Description : Upon failure of the normal power supply, the emergency generator is placed on the line by the _____________. A. main bus tie feeder B. automatic bus transfer device C. line connection feeder D. power failure alarm bus

Last Answer : Answer: B

Description : The frequency of an AC generator is adjusted by means of the ____________. A. main alternator field rheostat B. exciter field rheostat C. prime mover governor control D. equalizing reactor

Last Answer : Answer: C

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : In an AC synchronous motor electric propulsion plant, propeller speed is controlled by varying the _____________. A. prime mover speed B. electric coupling field strength C. number of energized main motor poles D. propulsion generator field strength

Last Answer : Answer: A

Description : In a diesel electric plant, raising the generator's field excitation will cause the DC propulsion motor to ________. A. increase in speed B. decrease in speed C. affect generator speed only D. affect main motor speed if done in conjunction with higher generator engine speeds

Last Answer : Answer: A

Description : On a vessel with turbo-electric drive, which of the following conditions would indicate that the propulsion motor had dropped out of synchronization with the propulsion generator? A. Excessive ... Tripped main motor interlocks C. Overheated crosstie busses D. Closed contact in the field circuits

Last Answer : Answer: A

Description : Why the earthing transformer primary voltage is 16.5 kV rated in main generator even though actual voltage during the E/F is root 3 times less?

Last Answer : The transformer should not saturate during E/F otherwise it will cause ferroresonance with the GT winding capacitance. Dangerous O/V and neutral shifting will occur. During loss of load or field ... saturation. Saturation can also occur due to point on wave of application causing flux doubling. 

Description : What precautions should be taken while meggering main generator?

Last Answer : All PT’s are racked out. Earthing transformer grounding terminals disconnected. Barring gear shall be kept off. Stator water shall be drained fully and hot air blown through conductors. Generator flexible lines shall be disconnected to isolate GT/UT. 

Description : What are the working principles of generator main protections?

Last Answer : GENERATOR START UP PROTECTIONS SUPPLEMENTARY PROTECTION OF GENERATOR The generator is normally expected to run rated speed before excitation power is applied by closing the field breaker. ... position to ensure that the protection is inoperable when the machine is connected to grid.  

Description : How main generator earthing is done?

Last Answer : Generator neutral earthing is done through transformer and earth fault current is limited through resistance, which is connected across the secondary of the transformer. Generator 16.5 kV earth fault current is isolated from 220 kV through GT. Only star point of the generator is grounded. 

Description : Write nameplate details of the main generator. 

Last Answer : Type THW-235 kW 237700 kVA 264000 Voltage 16500 V Amps 9240 A Power factor 0.9 lag. Field voltage 326 V Field current 2755 A Insulation Class-F Speed 3000 rpm 50 Hz, 3, double star connection. 

Description : Why cannot we have cables instead of bus duct in main generator? 

Last Answer : Very large number of cables in parallel required problems of sealing the terminations. 

Description : When the hydrogen explosion will take place in main generator?

Last Answer : When hydrogen concentration in air is more than 4% and less than 74% causes the explosion.