Why IDMT over current relay is always used as backup?

1 Answer

Answer :

Because setting has to be 200% to emergency loading and TMS be large to grade with feeder. Therefore very slow for internal faults/terminal faults/uncleared LV faults. 

Related questions

Description : Define IDMT relay?

Last Answer : It is an Inverse Definite Minimum Time relay. In IDMT relay its operating is inversely proportional and also a characteristic of minimum time after which this relay operates. It is inverse in the sense; the tripping time will decrease as the magnitude of fault current increase.

Description : Draw a typical time-current characteristic for IDMT relay. 

Last Answer : Time-Current Characteristic for IDMT Relay:

Description : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is

Last Answer : A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is 6.25A

Description : IDMT relays are used to protect the transformer against :  (A) Internal short -circuits (B) Open circuits (C) External short circuits (D) Oil leakage

Last Answer : IDMT relays are used to protect the transformer against : External short circuits

Description : What is the difference between over voltage relay and over current relay?

Last Answer : A:The current increases not only for over voltages but also for under voltage(As most of the loads are non-linear in nature). So,the over voltage protection & over current protection are completely ... , for a better protection of the system.It should have both over voltage & over current relay.

Description : When voltage increases then current also increases then what is the need of over voltage relay and over current relay? Can we measure over voltage and over current by measuring current only?

Last Answer : No. We can't sense the over voltage by just measuring the current only because the current increases not only for over voltages but also for under voltage (As most of the loads are non-linear in ... So, for a better protection of the system. It should have both over voltage & over current relay.

Description : What is the advantage of CMM relay over normal Inv. O/C current relay?

Last Answer : Inv. O/C relay under protects at low current and over protects at high currents. CMM: accounts for both +ve and -ve sequence currents i.e. Single phasing / unbalance supply conditions ... closely matched to motor heating characteristic. So it is better than thermal overload relay also. 

Description : Purpose of Over current & earth fault relay; type- CAG  

Last Answer : This relays are designed for instantaneous phase or earth fault protection and instantaneous high set over current protection.; A standard hinged-armature unit forms the basic movement for this relay. It consists an ... to the end of the core while the other arm to operate a set of contacts.  

Description : Purpose of Directional inverse Over current & earth fault relay; type- CDD

Last Answer : Directional phase or earth fault protection of ring-mains, parallel transformers, transformer feeders, parallel feeders etc., employing the time graded principle.; This relay comprises an inductive ... induction disc unit. The directional unit is normally provided with voltage polarising coils. 

Description : Purpose of over current relay (Inverse); type- CDG  

Last Answer : It is a self powered inverse time over current and earth fault relay, used for selective phase and earth fault protection in time graded systems for A.C. machines, transformers, feeders ... it rotates the driving torque increases and offsets the changing restraining torque of the control spring. 

Description : What is the characteristic of inverse time over current relay?  

Last Answer : If the fault current increases the time of the operation of the relay will be decreases.  

Description : When voltage increases then current also increases then why we need of over voltage relay and over current relay? Can we measure over voltage and over current by measuring current only?

Last Answer : No. We cannot sense the over voltage by just measuring the current only because the current increases not only for over voltages but also for under voltage (As most of the loads are non-linear in ... , for a better protection of the system. It should have both over voltage & over current relay.

Description : Inverse definite minimum time lag relay is also called ___________ (A) pilot relay. (B) differential relay. (C) over current relay. (D) directional overcurrent relay.

Last Answer : Ans: B Inverse definite minimum time lag relay characteristic is inverse but minimum time is fixed. The operating time is inversely proportional to the magnitude of actuating quantity.

Description : The full torque electric brake on an electric cargo winch functions to _____________. A. act as a backup brake in the event the mechanical brake should fail B. automatically hold the load ... automatically govern the lowering speed of the load D. automatically govern the hoisting speed of the load

Last Answer : Answer: B

Description : When an operating motor is connected to the controller shown in the illustration, the a path of current flow through the circuit is ____________. EL-0010 A. 'L1', stop button, start button, coil 'CR', 'L2' B. 'L1' ... L2' D. 'L1', stop button, start button, 'CR' contact, 'M' contact, 'CR' coil, 'L2'

Last Answer : Answer: B

Description : A diesel driven emergency generator is prevented from being paralleled with the ship's service generators by __________. A. an electrical interlock system B. an automatic paralleling trip switch C. the synchronizing oscilloscope D. the reverse current relay

Last Answer : Answer: A

Description : Which of the listed procedures is the best way to tell if a motor has become overloaded? A. Measure the current flow and compare it with the motor full load current flow as shown on the nameplate. ... Watch for telltale signs of smoke coming from the motor. D. Periodic opening of the O/L relay coil

Last Answer : Answer: A

Description : A reverse-current relay will prevent AC generator motorization by ____________. A. automatically redirecting the load B. automatically speeding up the prime mover C. tripping the panel board main switch D. tripping the generator circuit breaker

Last Answer : Answer: D

Description : Equal power factors on paralleled AC generators are maintained by an automatic _____________. A. voltage regulator B. reverse power relay C. reverse current relay D. governor control switch

Last Answer : Answer: A

Description : A loud buzzing noise in an AC controller is probably caused by _____________. A. poor contact with the overload relay B. an incorrectly sized heater C. a broken shading coil D. abnormal starting current

Last Answer : Answer: C

Description : If a magnetic controller relay fails to drop out when the coil voltage is removed from the relay, the probable cause may be _____________. A. excessive spring tension B. overvoltage C. excessive current D. welded contacts

Last Answer : Answer: D

Description : Protection against sustained overloads occurring in molded-case circuit breakers is provided by a/an __________. A. overvoltage release B. thermal acting trip C. thermal overload relay D. current overload relay

Last Answer : Answer: B

Description : Which of the following statements represents the main difference between a relay and a contactor? A. Contactors control current and relays control voltage. B. A relay is series connected and a contactor ... loads than relays. D. Contactors are made from silver and relays are made from copper.

Last Answer : Answer: C

Description : What precaution should be taken while removing a current operated relay when the equipment is in service?

Last Answer : Ensure that the CT is not getting opened by shorting the appropriate terminals. (Eventhough the terminals are automatically shorted once relay is removed the above point may carried out to ensure the same) 

Description : What are the advantages of static relay over electromagnetic relay?

Last Answer : o Low power consumption as low as 1mW o No moving contacts; hence associated problems of arcing, contact bounce, erosion, replacement of contacts o No gravity effect on operation of ... testing and servicing. Can convert even non-electrical quantities to electrical in conjunction with transducers.

Description : Why CT operated over load relay is using for loads of high acceleration time upto 30 seconds? How it getting back?

Last Answer : The saturable current transformers linearly transforms the current upto twice the set current, but above this value the transformer core gets saturated and the secondary current is proportionally less. Thus ... overload. When current reduces the core gets de-saturated, as material design is such. 

Description : Does over load relay give 100% guarantee against the single phasing?  

Last Answer : No. It depends on the motor load and the motor winding (star or delta).  

Description : Autotransformer starters or compensators are sometimes used with polyphase induction motors to _____________. A. reduce the voltage applied to the motor during the starting period B. increase the voltage for ' ... to be either stepped up or down, depending on the application, to ensure full torque

Last Answer : Answer: A

Description : What is the backup protection available for an alternator?

Last Answer : Overcurrent and earth fault protection is the backup protections.

Description : Why auto transfer is prevented if the backup protection is operated?  

Last Answer : The back up protection is supposed to operate in case of a bus fault. Hence the auto transfer is prevented. 

Description : Describe over current relay with time-current characteristic.

Last Answer : Over current relay with time-current characteristics:- 1. Definite time over current relay: Operating time is constant, the relays operates after a predetermined time when the current exceeds the pickup ... of fault current and definite time characteristics at higher values of fault current.

Description : Explain construction and operation of induction type directional over current relay.

Last Answer : Directional overcurrent relay: Construction: It consists of two units: i) Non-directional Over-current unit ii) Directional power unit The directional unit consists of upper electromagnet ... closes the trip circuit. This operates circuit breaker which isolates the faulty section. 

Description : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above 

Last Answer : A series resistance is added to the over-current relay in a bus bar differential protection scheme which: a. Helps to develop some voltage across it which otherwise should appear across the relay and is ... the effects of CT saturation and lowers the pickup value of the relay d. All of the above 

Description : In the induction type directional over current relay, when a short-circuit occurs in the circuit (A) power flows in reverse direction (B) power flows in normal direction (C) directional power element does not operate (D) over current element is not energized

Last Answer : In the induction type directional over current relay, when a short-circuit occurs in the circuit power flows in reverse direction

Description : In induction type directional over current relay the driving torque is due to interaction of magnetic fields derived from (A) current in the potential coil (B) both voltage and current in the ... (C) directional element and non-directional element (D) non-directional element and the trip circuit

Last Answer : In induction type directional over current relay the driving torque is due to interaction of magnetic fields derived from directional element and non-directional element

Description : In a static over-current relay, inverse time characteristics are obtained by   (a) A differentiating circuit (b) An integrating circuit (c) A transistor amplifier (d) A transistor switch

Last Answer : B

Description : In accordance with Coast Guard Regulations (46 CFR), each battery operated relay-controlled lantern must _____________. A. be readily portable B. contain a dry cell battery having a minimum capacity of ... automatic battery charger to maintain the battery in a fully charged state D. all of the above

Last Answer : Answer: C

Description : As shown in the illustration, once the "LV" relay is energized for operation, what contacts must remain closed to maintain the "LV" relay energized when the control lever is moved away from the "off" or "stop" ... . B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C

Description : The division of the reactive KVA load between paralleled AC generators is initiated by the ______________. A. prime mover governors B. voltage regulators C. phase balance relay D. proportioner

Last Answer : Answer: B

Description : The schematic diagram shown in the illustration uses symbol 'A' to represent a/an _________. EL-0011 A. non-renewable fuse link B. circuit breaker coil C. overload relay coil D. thermal overload heater

Last Answer : Answer: D

Description : Diesel generators #1 and #2 are operating in parallel at near full load capacity. Diesel generator #1 suddenly trips out mechanically due to low lube oil pressure. The reverse power relay functions ... all nonvital circuits. D. Secure alarms, reset reverse power relay, and restart #1 engine.

Last Answer : Answer: C

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : An alternator operating in parallel begins to vibrate severely and eventually trips out on the reverse power relay. The cause of the vibration was a result of ______________________. A. the ... C. the alternator was operating out of synchronism D. flashover at the alternator collector rings

Last Answer : Answer: C

Description : In order to safely carry out repairs to a generator circuit breaker, it must be isolated from the bus. This is accomplished by opening the _____________. A. reverse power relay B. bus disconnect link C. generator bus fuse connections D. power directional relay

Last Answer : Answer: B

Description : Why is it a good practice to have the frequency of the incoming alternator adjusted slightly higher than that of the loaded alternator when paralleling two alternators? A. This allows the oncoming machine to ... line. C. The reverse power relay is prevented from activating. D. All of the above.

Last Answer : Answer: D

Description : As shown in the illustration, what is responsible for maintaining the "LV" relay energized when the master switch handle is moved away from the "off" position? EL-0102 A. "DBa" contact. B. Reset contacts. C. Upper set of "LVa" contacts. D. Lower set of "LVa" contacts.

Last Answer : Answer: C