Can a cooling tower cool water below the wet bulb temperature of inlet
air?
(A) Yes
(B) No
(C) Yes; but height of cooling tower will be prohibitively high
(D) Yes; but the air flow rate should be excessively high

1 Answer

Answer :

(B) No

Related questions

Description : Pick out the wrong statement. (A) Different solids have different equilibrium moisture curves (B) Total condenser or reboiler is considered equivalent to one theoretical plate in McCabe-Thiele method of ... (D) Even a forced draft cooling tower cannot cool water below the wet bulb temperature

Last Answer : (C) Heat removal load on cooler remains constant, even with increase of the reflux ratio in a distillation column

Description : Which one of the following is true to estimate the range of cooling tower? a) Range = cooling water inlet temperature - wet bulb temperature b) Range = cooling water outlet temperature - wet bulb temperature ... = heat load in kcal per hour / water circulation in lines per hour d) None of the above

Last Answer : Range = heat load in kcal per hour / water circulation in lines per hour

Description : The term "cooling range" in a cooling tower refers to the difference in the temperature of (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air (B) Hot water entering the ... air (C) Hot water entering the tower and the cooled water leaving the tower (D) None of these

Last Answer : (C) Hot water entering the tower and the cooled water leaving the tower

Description : In a forced draft cooling tower, water is cooled from 95 to 80°F by exposure to air with a wet bulb temperature of 70°F. In this case, the (A) Range is 15°F (B) Approach is 10°F (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : The term "approach" in a cooling tower refers to the difference in the temperature of the (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air (B ... (C) Hot water entering and the cooled water leaving the cooling tower (D) None of these

Last Answer : (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air

Description : The temperature of water cooled in cooling tower is always __________ temperature of entering air. (A) More than the wet bulb (B) Less than the wet bulb (C) Equal to the wet bulb (D) Equal to the dry bulb

Last Answer : (A) More than the wet bulb

Description : The minimum temperature to which the water can be cooled in a cooling tower is the __________ temperature of air. (A) Ambient (B) Dry bulb (C) Dew point (D) Wet bulb

Last Answer : C) Dew point

Description : In a forced draft cooling tower, water is cooled from 95 to 80°F by exposure to air with a wet bulb temperature of 70°F. In this case, the (A) Range is 15°F (B) Approach is 10°F (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : Minimum temperature upto which water can be theoretically cooled down in the cooling tower by evaporative cooling is equal to the __________ temperature of air. (A) Wet bulb (B) Dry bulb (C) Saturation (D) Dew point

Last Answer : Option A

Description : Pick out the wrong statement pertaining to the cooling towers. (A) In case of induced draft cooling tower, the fan is placed at the top of the tower (B) Effectiveness of ... Effectiveness of a mechanical draft cooling tower is reduced with increase in air wet-bulb temperature

Last Answer : (D) Effectiveness of a mechanical draft cooling tower is reduced with increase in air wet-bulb temperature

Description : A better indicators for cooling tower performance is _____. • Wet bulb temperature • Dry bulb temperature • Range • Approach

Last Answer : Approach

Description : Which of the following faction affect the cooling tower performance? • The range • Heat load • Wet bulb temperature • All of the above

Last Answer : All of the above

Description : When specifying a cooling tower, should I look up historic wet bulb temperatures for my area or should I take measurements?

Last Answer : If this is a new installation, look up historical wet bulb temperatures for area and be sure to report them to the cooling tower manufacturer as ambient wet bulb temperatures . The ... the tower entrance. The entering wet bulb temperature always higher than the ambient wet bulb temperature.

Description : When sizing a cooling tower the highest anticipate__________ should be used? • Dry bulb • Wet bulb • Both dry and wet bulb • None of the above

Last Answer : Wet bulb

Description : Moist air is cooled along the line of constant __________ , when it is passed over a cold & dry cooling coil, such that no condensation occurs? (A) Enthalpy (B) Relative humidity (C) Wet bulb temperature (D) Dew point temperature

Last Answer : (D) Dew point temperature

Description : During sensible cooling of air, its wet bulb temperature (A) Decreases but dew point remains constant (B) Increases but dew point remains constant (C) Increases & the dew point decreases (D) Decreases & the dew point increases

Last Answer : (B) Increases but dew point remains constant

Description : During dehumidification of unsaturated air wet bulb temperature & partial pressure of vapor are not constant. However, during evaporative cooling process with recirculated water supply, the __________ remains ... pressure of water vapor (C) Relative humidity (D) None of these

Last Answer : (A) Wet bulb temperature

Description : Pick out the wrong statement (A) A horizontal line on the humidity chart indicates the temperature changes at constant molal humidity (B) When water is cooled from 80 to 70°C by exposure ... & air cannot be increased by either reducing the mixture temperature or by increasing the total pressure

Last Answer : (D) Relative saturation of unsaturated mixture of water vapor & air cannot be increased by either reducing the mixture temperature or by increasing the total pressure

Description : Which of the following psychrometric processes is followed by water vapour laden unsaturated air, when it is passed through solid or liquid adsorbent? (A) Cooling and dehumidification ... (C) Dehumidification with dry bulb temperature remaining constant (D) None of these

Last Answer : (B) Heating and dehumidification at almost constant wet bulb temperature

Description : __________ remains constant during the adiabatic cooling of moist air. (A) Wet bulb temperature (B) Dry bulb temperature (C) Relative humidity (D) Specific humidity

Last Answer : Option A

Description : L/G ratio in a cooling tower is a ratio of _____. • Length and girth • Length and temperature gradient • Water flow rate and air mass flow rate • Air mass flow rate and water flow rate

Last Answer : Water flow rate and air mass flow rate

Description : The cooling effect in a cooling tower cannot be increased by (A) Increasing the air velocity over the wet surfaces (B) Reducing the humidity of entering air (C) Lowering the barometric pressure (D) None of these

Last Answer : (D) None of these

Description : The cooling effect in a cooling tower can be speeded up by (A) Increasing the air velocity and area of exposed wet surface (B) Reducing the barometric pressure (C) Reducing the humidity of the air (D) All (A), (B) and (C)

Last Answer : (D) All (A), (B) and (C)

Description : In a cooling tower, water becomes cool by (A) Loosing sensible heat (B) Heat transfer to surroundings (C) Vaporisation due to heat loss to air (D) Loosing latent heat

Last Answer : (A) Loosing sensible heat

Description : Which of the following remains constant during evaporative cooling process with recirculated water supply? (A) Relative humidity (B) Partial pressure of vapour (C) Wet bulb temperature (D) None of these

Last Answer : (C) Wet bulb temperature

Description : Which of the following decreases during evaporative cooling process with recirculated water supply? (A) Wet bulb temperature (B) Relative humidity (C) Partial pressure of vapour (D) None of these

Last Answer : (D) None of these

Description : Which of the following increases during evaporative cooling process with recirculated water supply? (A) Wet bulb temperature (B) Relative humidity (C) Partial pressure of vapour (D) Both (B) and (C)

Last Answer : (D) Both (B) and (C)

Description : During sensible cooling process (A) Relative humidity decreases (B) Relative humidity increases (C) Wet bulb temperature decreases (D) Both (B) and (C)

Last Answer : (D) Both (B) and (C)

Description : The cooling tower uses the phenomenon of evaporative cooling to cool warm water above the dbt of air. A. true B. false

Last Answer : ANSWER : B

Description : The cooling water reduces the water temperature close to _____. • Dry bulb temperature • Ambient wet bulb temperature • Dew point temperature • None of the above

Last Answer : Ambient wet bulb temperature

Description : A solid material shows case hardening properties while drying. Which of the following should be controlled to control the drying process? (A) Flow rate of inlet air (B) Relative humidity of outlet air (C) Humidity of inlet air (D) Temperature of the solid

Last Answer : (D) Temperature of the solid

Description : What come out from the the cooling tower of a nuclear power plant 1 smoke 2 cool air 3 hot air 4 none of theses

Last Answer : 1 smoke

Description : . Most cooling towers are capacity rated at a "standard" wet bulb temperature of ___of • 72°F • 52°F • 78°F • 75°F

Last Answer : 78°F

Description : In natural draft cooling tower the air flow is obtained by___________ a) Difference in air pressure b) difference in air temperature c) Difference in air speed d) none of the above

Last Answer : Difference in air pressure

Description : In SI engines knocking can be reduced by (a) Increasing the compression ratio (b) Increasing the cooling water temperature (c) Retarding the spark advance (d) Increasing the inlet air temperature

Last Answer : Ans :c

Description : For the case of flow of air past a wet bulb thermometer (air water vapour system), the approximate value of h2 /ky .Cz is around (A) 0.60 (B) 0.24 (C) 1 (D) 0.72

Last Answer : (C) 1

Description : For the air water system under ambient conditions, the adiabatic saturation temperature and the wet bulb temperature are nearly equal, because (A) Water has a high latent heat of evaporation (B) Lewis number is close to unity (C) They are always equal under all circumstances

Last Answer : (A) Water has a high latent heat of evaporation

Description : In which system is Cooling of hot water is done on tray as step by? a) Mechanical draught cooling system b) Hyperbolic cooling tower c) Atmospheric cooling tower d) Wet cooling tower

Last Answer : Atmospheric cooling tower

Description : In which system is Cooling of hot water is done on tray as step by? a. Mechanical draught cooling system b. Hyperbolic cooling tower c. Atmospheric cooling tower d. Wet cooling tower

Last Answer : Atmospheric cooling tower

Description : . In which system is Cooling of hot water is done on tray as step by? a) Mechanical draught cooling system b) Hyperbolic cooling tower c) Atmospheric cooling tower d) Wet cooling tower

Last Answer : Atmospheric cooling tower

Description : Organic catalysts differ from the inorganic catalyst in the sense that the former is (A) Active at cryogenic temperatures only (B) Prohibitively costly (C) Proteinous in nature (D) Active at very high temperature only

Last Answer : (C) Proteinous in nature

Description : What is the reason to service a cooling tower? a) to ensure proper air flow b) to clean the tubes c) to inspect the water pump d) all of these

Last Answer : all of these

Description : The black cotton soil (A) Undergoes volumetric changes (B) Swells excessively when wet (C) Shrinks excessively when dry (D) All the above

Last Answer : Answer: Option D

Description : A natural draft cooling tower is filled with wooden grids, which covers about __________ percent of the tower height. (A) 10-15 (B) 30-40 (C) 70-80 (D) 90-100

Last Answer : (A) 10-15

Description : If people work excessively hard at preventing global warming, isn't there a risk of going too far and causing global cooling?

Last Answer : It is too late to prevent global warming; the current cycle has been in progress for some time. The concern is that unless action is taken now to reduce the rate at which the atmospheric ... the atmospheric conditions are known to evolve in a nonlinear fashion (e.g., The Butterfly effect).

Description : Unsaturated air (with dry bulb and wet bulb temperatures being 45°C and 25°C respectively) is passed through a water spray chamber maintained at 23°C. The air will be cooled and (A) ... temperature decreasing B) Humidified at constant wet bulb temperature (C) Dehumidified (D) None of these

Last Answer : (A) Humidified with wet bulb temperature decreasing

Description : Unsaturated air (with dry bulb temperature and dew point being 35°C and 18°C respectively) is passed through a water spray chamber maintained at 15°C. The air will be cooled (A) And ... (C) At the same relative humidity (D) And dehumidified with decrease in wet bulb temperature

Last Answer : (D) And dehumidified with decrease in wet bulb temperature

Description : When dry bulb temperature & wet bulb temperature of moist air is the same, it means that the (A) Partial pressure of water vapour is less than the total pressure (B) Humidity is < 100% & dew ... Dew point temperature of air has not reached & air is not saturated fully (D) Air is fully saturated

Last Answer : (D) Air is fully saturated

Description : When the temperature and humidity of air is low, we usually use __________ draft cooling tower. (A) Natural (B) Forced (C) Induced (D) None of these

Last Answer : (A) Natural

Description : Use of natural draft cooling tower is practised, when the air has low (A) Humidity (B) Temperature (C) Both 'a' & 'b' (D) Neither 'a' nor 'b'

Last Answer : (C) Both 'a' & 'b