In a forced draft cooling tower, water is cooled from 95 to 80°F by
exposure to air with a wet bulb temperature of 70°F. In this case, the
(A) Range is 15°F
(B) Approach is 10°F
(C) Both (A) & (B)
(D) Neither (A) nor (B)

1 Answer

Answer :

(C) Both (A) & (B)

Related questions

Description : In a forced draft cooling tower, water is cooled from 95 to 80°F by exposure to air with a wet bulb temperature of 70°F. In this case, the (A) Range is 15°F (B) Approach is 10°F (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : Pick out the wrong statement (A) A horizontal line on the humidity chart indicates the temperature changes at constant molal humidity (B) When water is cooled from 80 to 70°C by exposure ... & air cannot be increased by either reducing the mixture temperature or by increasing the total pressure

Last Answer : (D) Relative saturation of unsaturated mixture of water vapor & air cannot be increased by either reducing the mixture temperature or by increasing the total pressure

Description : Pick out the wrong statement pertaining to the cooling towers. (A) In case of induced draft cooling tower, the fan is placed at the top of the tower (B) Effectiveness of ... Effectiveness of a mechanical draft cooling tower is reduced with increase in air wet-bulb temperature

Last Answer : (D) Effectiveness of a mechanical draft cooling tower is reduced with increase in air wet-bulb temperature

Description : The term "approach" in a cooling tower refers to the difference in the temperature of the (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air (B ... (C) Hot water entering and the cooled water leaving the cooling tower (D) None of these

Last Answer : (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air

Description : Pick out the wrong statement. (A) Different solids have different equilibrium moisture curves (B) Total condenser or reboiler is considered equivalent to one theoretical plate in McCabe-Thiele method of ... (D) Even a forced draft cooling tower cannot cool water below the wet bulb temperature

Last Answer : (C) Heat removal load on cooler remains constant, even with increase of the reflux ratio in a distillation column

Description : The term "cooling range" in a cooling tower refers to the difference in the temperature of (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air (B) Hot water entering the ... air (C) Hot water entering the tower and the cooled water leaving the tower (D) None of these

Last Answer : (C) Hot water entering the tower and the cooled water leaving the tower

Description : Use of natural draft cooling tower is practised, when the air has low (A) Humidity (B) Temperature (C) Both 'a' & 'b' (D) Neither 'a' nor 'b'

Last Answer : (C) Both 'a' & 'b

Description : The temperature of water cooled in cooling tower is always __________ temperature of entering air. (A) More than the wet bulb (B) Less than the wet bulb (C) Equal to the wet bulb (D) Equal to the dry bulb

Last Answer : (A) More than the wet bulb

Description : The minimum temperature to which the water can be cooled in a cooling tower is the __________ temperature of air. (A) Ambient (B) Dry bulb (C) Dew point (D) Wet bulb

Last Answer : C) Dew point

Description : Minimum temperature upto which water can be theoretically cooled down in the cooling tower by evaporative cooling is equal to the __________ temperature of air. (A) Wet bulb (B) Dry bulb (C) Saturation (D) Dew point

Last Answer : Option A

Description : Noise produced by cooling fans (employed in air cooled heat exchangers or cooling tower) is mainly caused due to the turbulence created by blade passage through air. It can be reduced by use of a slower fan (A) With greater ... (B) Of increased diameter (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : A better indicators for cooling tower performance is _____. • Wet bulb temperature • Dry bulb temperature • Range • Approach

Last Answer : Approach

Description : Moist air is cooled along the line of constant __________ , when it is passed over a cold & dry cooling coil, such that no condensation occurs? (A) Enthalpy (B) Relative humidity (C) Wet bulb temperature (D) Dew point temperature

Last Answer : (D) Dew point temperature

Description : When the temperature and humidity of air is low, we usually use __________ draft cooling tower. (A) Natural (B) Forced (C) Induced (D) None of these

Last Answer : (A) Natural

Description : Heat load in a cooling tower (A) Means the amount of heat thrown away (KCal/hr.) by the cooling tower (B) Is equal to the number of kg, of water circulated times the cooling range (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : Which one of the following is true to estimate the range of cooling tower? a) Range = cooling water inlet temperature - wet bulb temperature b) Range = cooling water outlet temperature - wet bulb temperature ... = heat load in kcal per hour / water circulation in lines per hour d) None of the above

Last Answer : Range = heat load in kcal per hour / water circulation in lines per hour

Description : Dry bulb temperature of unsaturated air is more than its __________ temperature. (A) Dew point (B) Wet bulb (C) Both 'a' & 'b' (D) Neither 'a' nor 'b

Last Answer : (C) Both 'a' & 'b

Description : Which of the following faction affect the cooling tower performance? • The range • Heat load • Wet bulb temperature • All of the above

Last Answer : All of the above

Description : Can a cooling tower cool water below the wet bulb temperature of inlet air? (A) Yes (B) No (C) Yes; but height of cooling tower will be prohibitively high (D) Yes; but the air flow rate should be excessively high

Last Answer : (B) No

Description : Design of hyperbolic cooling tower standard for all cooling tower a) Mechanical draft b) Natural draft c) Both a & b d) Neither a & b

Last Answer : b) Natural draft

Description : The most efficient cooling tower out of the following is (A) Induced draft (B) Forced draft (C) Natural draft (D) Atmospheric

Last Answer : (A) Induced draft

Description : Unsaturated air (with dry and wet bulb temperatures being 35 and 25°C respectively) is passed through water spray chamber maintained at 35°C. The air will be (A) Cooled (B) Humidified (C) Both (A) & (B) (D) Dehumidified

Last Answer : (B) Humidified

Description : What Are The Advantages Of Induced Draft Cooling Tower Over Forced Draft Cooling Tower?

Last Answer : 1. The outlet water comes in contact with the driest air and warmest water comes in contact with most humid air. 2. The re-circulation is seldom a problem. 3. The first cost is low due to the reduction in pump power consumption.

Description : In case of unsaturated air (A) Dew point < wet bulb temperature (B) Wet bulb temperature < dry bulb temperature (C) Both (A) and (B) (D) Neither (A) not (B)

Last Answer : (C) Both (A) and (B)

Description : Unsaturated air (with dry bulb and wet bulb temperatures being 45°C and 25°C respectively) is passed through a water spray chamber maintained at 23°C. The air will be cooled and (A) ... temperature decreasing B) Humidified at constant wet bulb temperature (C) Dehumidified (D) None of these

Last Answer : (A) Humidified with wet bulb temperature decreasing

Description : Unsaturated air (with dry bulb temperature and dew point being 35°C and 18°C respectively) is passed through a water spray chamber maintained at 15°C. The air will be cooled (A) And ... (C) At the same relative humidity (D) And dehumidified with decrease in wet bulb temperature

Last Answer : (D) And dehumidified with decrease in wet bulb temperature

Description : When specifying a cooling tower, should I look up historic wet bulb temperatures for my area or should I take measurements?

Last Answer : If this is a new installation, look up historical wet bulb temperatures for area and be sure to report them to the cooling tower manufacturer as ambient wet bulb temperatures . The ... the tower entrance. The entering wet bulb temperature always higher than the ambient wet bulb temperature.

Description : When sizing a cooling tower the highest anticipate__________ should be used? • Dry bulb • Wet bulb • Both dry and wet bulb • None of the above

Last Answer : Wet bulb

Description : Air initially at 101. 3 kPa and 40°C and with a relative humidity of 50%, is cooled at constant pressure to 30°C. The cooled air has a (A) Higher dew point (B) Higher absolute (specific) humidity (C) Higher relative humidity (D) Higher wet bulb temperature

Last Answer : (C) Higher relative humidity

Description : During dehumidification of unsaturated air wet bulb temperature & partial pressure of vapor are not constant. However, during evaporative cooling process with recirculated water supply, the __________ remains ... pressure of water vapor (C) Relative humidity (D) None of these

Last Answer : (A) Wet bulb temperature

Description : During sensible cooling of air, its wet bulb temperature (A) Decreases but dew point remains constant (B) Increases but dew point remains constant (C) Increases & the dew point decreases (D) Decreases & the dew point increases

Last Answer : (B) Increases but dew point remains constant

Description : Natural draft created by the chimney depends upon (A) Temperature of the flue gas (B) Its height (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : In natural draft cooling tower the air flow is obtained by___________ a) Difference in air pressure b) difference in air temperature c) Difference in air speed d) none of the above

Last Answer : Difference in air pressure

Description : Mode of heat transfer involved in the cooling of air cooled internal combustion engine is (A) Conduction (B) Natural convection (C) Forced convection (D) None of these

Last Answer : (B) Natural convection

Description : Cooling tower is a ______device a) Heat absorption b) heat rejection c) Both a and b c) neither a nor b

Last Answer : heat rejection

Description : __________ is the temperature at which a gas-vapor mixture becomes saturated, when cooled at constant total pressure out of contact with a liquid. (A) Dew point (B) Bubble point (C) Dry bulb temperature (D) Wet bulb temperature

Last Answer : (A) Dew point

Description : The temperature to which a vapour gas mixture must be cooled (at varying humidity) to become saturated is called the __________ temperature. (A) Dew point (B) Wet bulb (C) Dry bulb (D) None of these

Last Answer : (D) None of these

Description : Which of the following psychrometric processes is followed by water vapour laden unsaturated air, when it is passed through solid or liquid adsorbent? (A) Cooling and dehumidification ... (C) Dehumidification with dry bulb temperature remaining constant (D) None of these

Last Answer : (B) Heating and dehumidification at almost constant wet bulb temperature

Description : __________ remains constant during the adiabatic cooling of moist air. (A) Wet bulb temperature (B) Dry bulb temperature (C) Relative humidity (D) Specific humidity

Last Answer : Option A

Description : Which of the following increases during evaporative cooling process with recirculated water supply? (A) Wet bulb temperature (B) Relative humidity (C) Partial pressure of vapour (D) Both (B) and (C)

Last Answer : (D) Both (B) and (C)

Description : Cooling tower effectiveness is the ratio of a) Range/( Range + approach) b) Approach/(range + approach) c) Range /(range - approach) d) Approach/ /(range - approach)

Last Answer : Range/( Range + approach)

Description : Cooling tower effectiveness is the ratio of _____. • Range/(range + approach) • Approach/(range + approach) • Range/ Approach • Approach/ Range

Last Answer : Range/(range + approach)

Description : During sensible cooling process (A) Relative humidity decreases (B) Relative humidity increases (C) Wet bulb temperature decreases (D) Both (B) and (C)

Last Answer : (D) Both (B) and (C)

Description : Which of the following accentuates clinkering troubles on furnace grate burning coal? (A) Low reactivity of carbonised residue containing high proportion of iron & sulphur (B) Low forced draft & fuel bed temperature (C) Thick firebed and preheated primary air (D) All (A), (B) and (C)

Last Answer : (D) All (A), (B) and (C)

Description : Nusselt number (for forced convection heat transfer) is a function of the __________ number. (A) Prandtl (B) Reynolds (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : Forced circulation evaporators are normally used for concentrating liquids having (A) Scaling characteristics (B) High viscosity (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : The cooling effect in a cooling tower cannot be increased by (A) Increasing the air velocity over the wet surfaces (B) Reducing the humidity of entering air (C) Lowering the barometric pressure (D) None of these

Last Answer : (D) None of these

Description : The cooling effect in a cooling tower can be speeded up by (A) Increasing the air velocity and area of exposed wet surface (B) Reducing the barometric pressure (C) Reducing the humidity of the air (D) All (A), (B) and (C)

Last Answer : (D) All (A), (B) and (C)

Description : Which of the following remains constant during evaporative cooling process with recirculated water supply? (A) Relative humidity (B) Partial pressure of vapour (C) Wet bulb temperature (D) None of these

Last Answer : (C) Wet bulb temperature

Description : Which of the following decreases during evaporative cooling process with recirculated water supply? (A) Wet bulb temperature (B) Relative humidity (C) Partial pressure of vapour (D) None of these

Last Answer : (D) None of these