Unnecessary and frequent applications of varnish to the generator windings to repair defective insulation will result in ____________. A. heavy coatings of varnish interfering with heat dissipation B. deficient air gap clearance and eventual damage to the casing C. failure of the rectifier assembly D. a built-up of varnish without changing generator operation

1 Answer

Answer :

Answer: A

Related questions

Description : The voltage output of an AC generator is accurately controlled by _____________. A. changing the sensitivity of the prime mover to large changes in voltage B. varying the reluctance of the air gap C. varying the DC exciter voltage D. shorting out part of the armature windings

Last Answer : Answer: C

Description : Routine maintenance of dry-type transformers should include ____________. A. cleaning the windings, if accessible, with a vacuum cleaner or very low pressure air B. measuring and recording the winding ... . making sure that the units are close to bulkheads or corners to protect them from damage

Last Answer : Answer: A

Description : Air gap readings should be taken periodicly on electrical generation equipment to __________. A. determine the amount of varnish that can be applied to correct insulation problems B. determine the ... field coil bolts and correct lateral adjustment of the field coils D. increase machine efficiency

Last Answer : Answer: B

Description : You are testing the insulation in an AC generator with a megohmeter. The resistance value of a dry, clean winding will ____________. A. continue to rise as the test potential is maintained, ... fairly steady after 5 to 7 minutes D. stabilize after approximately 2 to 4 minutes of fluctuation

Last Answer : Answer: A

Description : Electrical leads and insulation on a motor should be painted with ____________. A. heat-resisting acrylic B. heat-resisting aluminum C. insulating varnish D. insulating white lead

Last Answer : Answer: C

Description : The greatest detrimental effect on idle electrical equipment, such as cargo pump motors, is the _____________. A. loss of residual magnetism B. absorption of moisture in the insulation C. insulation varnish flaking D. dirt collecting on the windings

Last Answer : Answer: B

Description : When using a megohmmeter to test the dielectric strength of wire insulation, a continuous series of slight downscale kicks by the pointer is result of ____________. A. good insulation B. the ... dirty insulation C. the capacitance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : Accidental grounds in a shipboard electrical system must be repaired as soon as possible as they will ____________. A. result in immediate power outages B. damage circuit breakers C. appear on the ground detection system D. damage insulation and may cause outages

Last Answer : Answer: D

Description : Which statement is true concerning a split-phase induction motor? A. Motor rotation can be reversed without changing the windings or leads. B. Motor speed can be readily adjusted from zero to full ... proper wiring. D. Motor rotation can be reversed by reversing the leads on the starting winding.

Last Answer : Answer: D

Description : Which of the following procedures should be used to maintain a large electric motor during periods of inactivity? A. A thin layer of air-drying varnish should be applied on the windings. B. ... periodically to remove carbon dust. D. Space heaters should be used to prevent condensation of moisture.

Last Answer : Answer: D

Description : The removal of paint from electrical equipment, such as generators, should be cautiously undertaken because ____________. A. the mechanical shock of paint removal lessens the dielectric strength ... phase windings frequently become isolated from each other due to dust interference at the terminals

Last Answer : Answer: B

Description : When a megohmmeter is used to test the insulation of a large motor, the initial dip of the pointer toward 'zero' is caused by ____________. A. good insulation B. the capacitance of the ... of the current along the surface of dirty insulation D. the dielectric-absorption effect of the insulation

Last Answer : Answer: B

Description : In preparing to take insulation resistance readings on a main generator, the windings should be grounded for about 15 minutes prior to the test to _____________. A. allow accurate zeroing of the meter ... the windings D. help the windings to cool to the same temperature as the ground test connection

Last Answer : Answer: C

Description : The air gap in an induction motor should be checked periodically with a feeler gage to detect ____________. A. rotor contact with the laminations B. changes in armature magnetic strength C. excessive bearing wear D. electrical damage to the rotor

Last Answer : Answer: C

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test as the ______________. A. insulation may be damaged ... number of leakage paths D. larger machines may acquire a charge of static electricity during operation

Last Answer : Answer: D

Description : When a megohmmeter is used to test insulation, the gradual rise of the pointer reading as a result of continued cranking, is caused by _____________. A. good conductor resistance B. the ... insulation C. the inductive reactance of the windings D. the dielectric-absorption effect of the insulation

Last Answer : Answer: D

Description : Grounds occurring in electrical machinery as a result of insulation failure may result from _____________. A. deterioration through extended use B. excessive heat C. extended periods of vibration D. all of the above

Last Answer : Answer: D

Description : Maximum heat dissipation occurs from a steel wire (k = 0.5 W/m. k) of 15 mm diameter exposed to air (h = 20W/m2.k), when the insulation thickness is __________ mm. (A) 15 (B) 25 (C) 10 (D) 30

Last Answer : (B) 25

Description : The amount of voltage induced in the windings of an AC generator depends on ____________. A. the number of conductors in series per winding B. the speed at which the magnetic field passes across the winding C. the strength of the magnetic field D. all of the above

Last Answer : Answer: D

Description : As shown in the illustration, the generator field is excited with DC current provided by ____________. EL-0016 A. conductors '1', '2' and '3' B. inductor 'L1' C. rectifier 'CR1' D. winding 'S-2'

Last Answer : Answer: C

Description : When insulation failure produces a low resistance current path between two conductors, the resulting condition is known as ____________. A. an open B. a short circuit C. a ground D. a surge

Last Answer : Answer: B

Description : To repair a small electrical motor that has been submerged in saltwater, you should _____________. A. wash it with fresh water and apply an external source of heat B. renew the windings ... electrical parts with a carbon tetrachloride cleaning solvent and then blow dry the motor with compressed air

Last Answer : Answer: A

Description : Which of the following statements best describes the material known as varnished cambric? A. Felted asbestos sealed with varnish. B. Cotton cloth coated with insulating varnish. C. Rubber ... Paper impregnated with mineral oil, specially wrapped with nonmetallic tape, and coated with varnish.

Last Answer : Answer: B

Description : The initial gap between the extra full-length leaf and the graduated-length leaf before the assembly, is called as (A) clearance (B) nip (C) gap

Last Answer : (B) nip

Description : A generator has been exposed to water and is being checked for its safe operation. Therefore, it is necessary to _______________. A. check for shorted coils with a growler B. take moisture readings with a ... a megger D. ground the commutator, or slip rings and run it at half load for 12 hours

Last Answer : Answer: C

Description : The reactive power drawn by a motor from an AC generator is the power which is _____________. A. used to establish the magnetic field of the motor B. lost in overcoming friction in the ... by current flow through the windings D. transmitted directly through the rotor shaft to perform useful work

Last Answer : Answer: A

Description : If air gap readings for an electical generating machine have changed significantly from the last reading, you should check _________. A. the bearings B. insulation readings and machine cleanliness C. the prime mover thrust bearing D. the field coil bolts for the proper torque values

Last Answer : Answer: A

Description : Proper storage battery maintenance includes ____________. A. keeping connections tight and casing surfaces clean B. making sure electrolyte level is below the separator plates C. insulating the terminals with naval jelly D. maintaining a high charging rate at all times

Last Answer : Answer: A

Description : If you hear a loud buzzing noise coming from a magnetic motor controller, you should ____________. A. assume that the motor is operating at a full load B. assume that the controller is operating normally C. ... of the problem D. feel the outside of the casing with your hand to see if it is hot

Last Answer : Answer: C

Description : Voltage failure of an AC generator may be caused by ____________. A. failure of the exciter generator B. a tripped bus circuit breaker C. high mica segments on the stator bus bar D. excessive prime mover speed

Last Answer : Answer: A

Description : Basically, a magnetic amplifier is a saturable reactor with the addition of _____________. A. AC to the bias winding B. variable capacitance to all windings C. eddy current protectors D. a rectifier in the load circuit

Last Answer : Answer: D

Description : Grease coatings on electrical contact surfaces increase contact resistance and should be removed with a/an _______________. A. small wire brush B. compressed air jet C. clean dry cloth D. 10% solution carbon solvent and water

Last Answer : Answer: C

Description : A loss of field excitation to an AC generator while operating in parallel will cause it to ____________. A. absorb more and more load due to decreased armature reaction B. lose its load due to ... polarity D. lose its load, begin to motorize, trip out on reverse power relay, and possibly overspeed

Last Answer : Answer: D

Description : What is used to purge hydrogen from the generator casing?

Last Answer : During generator purging CO2 is used to purge out H2 from the casing. 

Description : Which of the following statements, concerning the general maintenance of a brushless generator, is correct? A. Paint should be applied to insulating surfaces on an annual basis. B. Alcohol should be used to ... . D. Accessible generator parts should be wiped with a clean dry rag on a periodic basis.

Last Answer : Answer: D

Description : An AC generator operating in parallel loses its excitation without tripping the circuit breaker. This will __________. A. not affect the faulty generator due to the compensation of the other generators B. ... between the armature and the bus D. cause high currents to be induced in the field windings

Last Answer : Answer: D

Description : An open in the armature of a DC motor is suspected, but is not found by visual inspection of the commutator. The next step in troubleshooting this problem is to ________________. A. conduct a ... windings C. conduct an insulation resistance test of the armature D. test the commutator for a ground

Last Answer : Answer: A

Description : Which of the conditions listed will indicate the need to clean the insulation on the windings of an electric motor? A. Higher than normal operating temperature. B. Excessive vibration at normal speed. C. Sparking at the brushes. D. High megger readings.

Last Answer : Answer: A

Description : Moisture absorbed in the windings or condensed on the surface of electrical machinery insulation ________. A. is good for long term preserving since most insulation is organic and contains some amount B. ... D. reduces the amount of current supplied or drawn by the machine so horsepower is limited

Last Answer : Answer: B

Description : Before testing insulation with a megohmmeter, the windings of large machines should be grounded for about 15 minutes just prior to the test, because the ___________. A. static charge of the machine ... number of leakage paths C. insulation may be damaged D. insulation may be covered with moisture

Last Answer : Answer: A

Description : The greatest single cause of electrical failures is ______. A. the breakdown of insulation B. overcurrent C. high inductance D. too frequent testing

Last Answer : Answer: A

Description : The operator of electrical motors should keep a constant check on the loads they carry because _____________. A. low loads necessitate frequent insulation cleaning B. exceeding nameplate values shortens ... wasted if full loading is not utilized D. power factor correction methods are load dependent

Last Answer : Answer: B

Description : Electrical machinery insulation will break down more rapidly due to _________________. A. low loading of motors and generators B. frequent megger testing C. high temperatures and vibration D. high operating frequencies

Last Answer : Answer: C

Description : Routine maintenance of a ship's service alternator should include ______________. A. changing the pedestal bearing insulation yearly B. megger testing of all rectifying diodes C. lubricating excitation slip rings D. periodic cleaning of the air filters or screens

Last Answer : Answer: D

Description : An alternator will fail to produce line voltage as a result of _____________. A. a closed circuit breaker B. oxidized slip rings C. improperly staggered brushes D. exciter generator failure

Last Answer : Answer: D

Description : Air gap readings for electrical generating equipment should be taken periodicly. This is to _______. I. determine the condition of the bearings II. prevent damage to the rotor and stator A. I only B. II only C. both I and II D. neither I or II