Two 550 kVA alternator operate in parallel to supply the following loads

I. 250 KW at 0.95 p.f. lagging

II. 100 KW at 0.85 p.f. leading

One machine is supplying 200 KW at 0.9 p.f. lagging. The p.f. of other machine must be

1 Answer

Answer :

Two 550 kVA alternator operate in parallel to supply the following loads


I. 250 KW at 0.95 p.f. lagging

II. 100 KW at 0.85 p.f. leading

One machine is supplying 200 KW at 0.9 p.f. lagging. The p.f. of other machine must be 0.89 leading

Related questions

Description : If field excitation is suddenly lost to an alternator operating in parallel, that alternator will _____________. A. supply excessive current to the bus B. operate at the same load, but with reduced voltage C. lose its load and tend to overspeed D. become overloaded and slow down

Last Answer : Answer: C

Description : If the energy input is significantly reduced to the prime mover of one shipboard alternator operating in parallel with others, that alternator will _____________. A. continue to operate at no load B. lose ... overspeed C. begin to motorize and then trip out D. slow down and operate at reduced load

Last Answer : Answer: C

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : Why are motor ratings given in KW and that of alternator and transformer given in KVA?

Last Answer : kW is the output mechanical power of a motor and is expressed in kW. kVA is the net (apparent) power input to the transformer. This input power is the output + losses. kW = kVA x system power factor

Description : While keeping the excitation constant, if the steam supply of an alternator running in parallel with another identical alternator is increased, then (A) It would over-run the other alternator (B) Its rotor ... (C) Its portion of share in load will increase (D) Its power factor would be decreased.

Last Answer : While keeping the excitation constant, if the steam supply of an alternator running in parallel with another identical alternator is increased, then Its portion of share in load will increase

Description : A four-pole induction motor, operating on three-phase 60 cycle current will operate at approximately ___________. A. 850 RPM B. 1,150 RPM C. 1,750 RPM D. 3,550 RPM

Last Answer : Answer: C

Description : Define armature reaction in an alternator. Explain the effect of armature reaction at various P.F. of loads of alternator.

Last Answer : Armature Reaction: The effect of armature flux on main flux is called as armature reaction.  Armature Reaction at Various Power Factors: When armature is loaded, the armature flux modifies ... lagging p.f. For capacitive loads the effect of flux is partly distorting and partly strengthening.

Description : Tapper roller bearing are used in disc harrow because a) It can take heavy radial loads b) It can take both radial as well as end thrust c) It can operate effectively at low speed and in contact with dirt d) Both (b) and (c) are true

Last Answer : d) Both (b) and (c) are true

Description : A 220/440 V, 50 Hz, 5 KVA, single phase transformer operates on 220V, 40Hz supply with secondary winding open circuited. Then (A) Both eddy current and hysteresis losses decreases. (B) Both ... same but hysteresis loss increases. (D) Eddy current loss increases but hysteresis loss remains the same.

Last Answer : (A) Both eddy current and hysteresis losses decreases.

Description : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease ... losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

Last Answer : If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: both the eddy current and the hysteresis losses will decrease

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Last Answer : D. Loading of the transformers not in proportion to their kVA ratings

Description : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their:

Last Answer : When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their: P u impedance are equal

Description : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is 500 kVA and its pu ... its pu leakage impedance is  (A) 0.20 (B) 0.10 (C) 0.05 (D) 0.025

Last Answer : Two transformers are to be operated in parallel such that they share load in proportion to their kVA ratings. The rating of the first transformer is 500 kVA ratings. The rating of the first transformer is ... .05 pu. If the rating of second transformer is 250 kVA, its pu leakage impedance is 0.10

Description : Attempting to parallel an AC generator which is out of phase with the bus will result in which of the following problems? A. The breaker should trip. B. The KVA will decrease. C. The synchronizing lamps will burn out. D. The power factor will be unitized.

Last Answer : Answer: A

Description : Why do we use 3 phase power supply for heavy loads?

Last Answer : With a single phase, the voltage drops to 0 every half-cycle. Therefore, the amount of power you can get out of the line is not constant over time; it has a very large 120-hz ripple. With ... this can be accomplished, but in every case there are drawbacks that are not present in the 3-phase system

Description : If the load requirement consists of both positive and negative voltages, what technique is used in the voltage divider to supply the loads from a single voltage source?

Last Answer : The ground (reference point) is placed in the proper point in the voltage divider so that positive and negative voltages are supplied

Description : In the illustration, if one of the devices labeled 'TURB' should fail the ___________. EL-0003 A. device labeled 'EXC' will drive the alternator B. device labeled 'BKR' for that ... -alternator D. emergency generator should automatically start and be placed on line to supply emergency load centers

Last Answer : Answer: B

Description : If two electrical loads are connected in parallel with each other and each load draw 6 amps what is the current of the circuit?

Last Answer : 12 Amperes is.

Description : In the illustration, the contacts between terminals 26 and 27 should be closed when _________. EL-0046 A. using one generator in isochronous mode only B. using two or more generators in ... through varying loads in parallel or single operation D. the circuit breaker is closed for that generator

Last Answer : Answer: C

Description : If l1 and l2 are the lengths of long and short spans of a two way slab simply supported on four edges and carrying a load w per unit area, the ratio of the loads split into w1 and w2acting on strips parallel to l2 and l1 is (A) ... l1 (B) w1/w2 = (l2/l1)² (C) w1/w2 = (l2/l1)3 (D) w1/w2 = (l2/l1)

Last Answer : Answer: Option D

Description : A pre-stressed rectangular beam which carries two concentrated loads W at L/3 from either end, is provided with a bent tendon with tension P such that central one-third portion of the tendon remains parallel to the longitudinal axis, the maximum dip h is (A) WL/P (B) WL/2P (C) WL/3P (D) WL/4P

Last Answer : Answer: Option C

Description : The total power consumed in a parallel circuit is __________. A. the sum of the powers used in each load (resistor) divided by the number of loads B. always less than the power used in the smallest ... of the powers used in each individual load D. never more than the power used in the largest load

Last Answer : Answer: C

Description : Which of the following statements represents the main difference between a relay and a contactor? A. Contactors control current and relays control voltage. B. A relay is series connected and a contactor ... loads than relays. D. Contactors are made from silver and relays are made from copper.

Last Answer : Answer: C

Description : Which type of heat exchanger is preferred for heavy heat loads? (A) Double pipe (B) Plate fine (C) Series and parallel set of shell and tube (D) None of these

Last Answer : (C) Series and parallel set of shell and tube

Description : The beds which have a gentle upstream dip will be_______ to the resultant force (R), hence can provides the best resistance to withstand the stresses or loads acting in the area. (A) Parallel (B) Perpendicular (C) None of these 

Last Answer : (B) Perpendicular  

Description : Which of the following statements is true concerning the operation of two alternators in parallel? A. The cycles per second of each alternator are the same. B. Both alternator governors must be set ... be the same on each alternator. D. The load must always be divided equally between alternators.

Last Answer : Answer: A

Description : If the pointer of the synchroscope is rotating in the slow direction when you are preparing to parallel two alternators, the _____________. A. incoming machine is turning faster than the load alternator B ... alternator is ready to split D. incoming machine is beginning to pick up some of the load

Last Answer : Answer: B

Description : Which of the following problems will occur if the circuit breaker of the incoming alternator is closed and it is 180° out of phase with the loaded alternator when paralleling? A. The rotor of the ... The rotor of the incoming alternator will stop. D. Both alternators will parallel 180° out of phase.

Last Answer : Answer: B

Description : If the excitation of an alternator operating in parallel is decreased below normal, its _____________. A. power factor will change in the lagging direction B. power factor will change in the leading direction C. ampere load will be greatly increased D. kilowatt load will be greatly decreased

Last Answer : Answer: B

Description : Severe vibration, accompanied by flashover at the collector rings of an alternator operating in parallel, is a symptom of _____________. A. reverse current motorization B. loss of synchronism C. destructive overspeeding D. reversed polarity

Last Answer : Answer: B

Description : An alternator operating in parallel begins to vibrate severely and eventually trips out on the reverse power relay. The cause of the vibration was a result of ______________________. A. the ... C. the alternator was operating out of synchronism D. flashover at the alternator collector rings

Last Answer : Answer: C

Description : To remove an alternator operating in parallel with another unit from the main electrical bus, you must FIRST _________. A. adjust the power factor on both units B. set the desired voltage on ... C. open the circuit breaker on the outgoing alternator D. remove the load from the outgoing alternator

Last Answer : Answer: D

Description : A change in field excitation of an alternator operating in parallel will cause a change in its _____________. A. alternator frequency B. kilowatt load C. voltage output D. all of the above

Last Answer : Answer: C

Description : What steps are to be taken before disconnecting one Alternator from parallel operation?

Last Answer : The following steps are to be taken before disconnecting one Alternator from parallel operation · The prime-mover input of the outgoing generator has to be decreased and that of other generators ... delivered by the outgoing generator is zero, it has to be disconnected from parallel operation.

Description : If the excitation of an alternator operating in parallel with other alternators decreased, its: (1) Power factor becomes more leading (2) Output Kw will change (3) Power factor becomes more lagging (4) Power factor becomes unity

Last Answer : If the excitation of an alternator operating in parallel with other alternators decreased, its: Power factor becomes more leading

Description : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is (A) 1000 kVA (B) 1100 kVA (C) 11000 kVA (D) 12100 kVA

Last Answer : A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is 12100 kVA

Description : Why are generators rated in kVA not in kW ?

Last Answer : Because It's rating of generator kva is apparent power. Kw is active power which we use. And one is kvar reactive power.

Description : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Last Answer : KVA of an Auto-transformer of V1/V2 = 220/150 for a load of 100KVA is: a. 100KVA b. 50KVA c. 33.3KVA d. 20KVA 

Description : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Last Answer : What should be kVA rating of each transformer in V-V bank when three phase balanced load is 40 kVA ? (A) 19 (B) 28 (C) 37 (D) 23

Description : A consumer finds that after running 10 kVA equipment on full load for six hours, his energy consumption was 48 kWH. It can be concluded that (A) The load factor of consumer for the day was unity. (B ... (C) The equipment was drawing only reactive power. (D) The power factor of equipment was 0.8. 

Last Answer : A consumer finds that after running 10 kVA equipment on full load for six hours, his energy consumption was 48 kWH. It can be concluded that  The power factor of equipment was 0.8. 

Description : In short circuit calculations, the selected base kVA is equal to (A) That of the largest Plant (B) The total plant Capacity (C) Any arbitrary value (D) Can be any one of (A), (B), (C)

Last Answer : A

Description : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be :  (A) 34.64 kVA (B) 75 kVA (C) 20 kVA (D) None of the above

Last Answer : The kVA rating of Three-phase transformer with Voltage = 200V and Current = 100A will be : 34.64 kVA

Description : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: A. 4 kVA B. 0.25 kVA C. 16 kVA D. 8 kVA

Last Answer : The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: 16 kVA

Description : Short-circuit kVA is obtained by multiplying the base kVA by (1) 10% X (2) 20% X (3) 50% X (4) 100% X

Last Answer : 100%

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

Last Answer : 543A

Description : The apparent power drawn by an A.C. circuit is 10 kVA and active power is 8 kW. The reactive power in the circuit is?

Last Answer : The apparent power drawn by an A.C. circuit is 10 kVA and active power is 8 kW. The reactive power in the circuit is 6 kVAR.

Description : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is?

Last Answer : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is 32 kW.

Description : Transformer generally rated in KVA

Last Answer : The power of transformer is apparent power because it has no power factor and it is the product of voltage and current.

Description : How does an uninterruptible power supply operate?

Last Answer : An uninterruptible power supply (or UPS) operates, in most cases, as a specialized battery for the computer. The computer will be plugged into the UPS battery. And when the power goes down or surges, the UPS will take over and supply power at the proper voltage.