The rated voltage of a 3-phase power system is given as 

A) rms phase voltage B) Peak phase voltage C) rms line to line voltage D) Peak line to line voltage

1 Answer

Answer :

The rated voltage of a 3-phase power system is given as rms line to line voltage

Related questions

Description : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

Last Answer : A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 35 kA 

Description : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the ... the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

Last Answer : A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume ... the shaft. The accelerating torque in the generator in MNm at the time of fault will be 1.018 

Description : if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then

Last Answer : if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then input voltage is sinusoidal and input current is non sinusoidal.

Description : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

Last Answer : A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he 0.52

Description : An alternator has a phase sequence of RYB for its phase voltage. In case the direction of rotation of alternator is reversed, the phase sequence will become?

Last Answer : An alternator has a phase sequence of RYB for its phase voltage. In case the direction of rotation of alternator is reversed, the phase sequence will become RBY.

Description : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be

Last Answer : The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be 115 V.

Description : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are (A) 6 (B) 12 (C) 16 (D) 24

Last Answer : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are 24

Description : A split-phase induction squirrel-cage motor will not come up to speed, even though the rated voltage, rated frequency, and rated load are applied. The suspected trouble could be due to _____________. A. a faulty centrifugal switch B. broken rotor bars C. worn bearings D. all of the above

Last Answer : Answer: D

Description : A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m.

Last Answer : (D) 75 r.p.m.

Description : A 3-phase induction motor is driving a constant torque load at rated voltage and frequency. If both voltage and frequency are halved, following statements relate to the new condition if stator resistance, leakage reactance and core loss are ... (A) All (B) 1, 2 and 3 (C) 2, 3 and 4 (D) 1 and 4

Last Answer : A 3-phase induction motor is driving a constant torque load at rated voltage and frequency. If both voltage and frequency are halved, following statements relate to the new condition if stator resistance, leakage reactance and core loss are ... A) All (B) 1, 2 and 3 (C) 2, 3 and 4 (D) 1 and 4

Description : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Last Answer : A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA

Description : A three-phase cage induction motor is started by direct-on-line (DOL) switching at the rated voltage. If the starting current drawn is 6 times the full load current, and the full load slip is 4%, then ratio of the ... load torque is approximately equal to (A) 0.24 (B) 1.44 (C) 2.40 (D) 6.00

Last Answer : A three-phase cage induction motor is started by direct-on-line (DOL) switching at the rated voltage. If the starting current drawn is 6 times the full load current, and the full load slip is 4%, then ratio of the starting developed torque to the full load torque is approximately equal to 1.44

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : For a fixed value of complex power flow in a transmission line having a sending and voltage V, the real power loss will be proportional to  A) V B) v2 C) 1/V2 D)1/V

Last Answer : For a fixed value of complex power flow in a transmission line having a sending and voltage V, the real power loss will be proportional to 1/V2

Description : A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

Last Answer : 0

Last Answer : When a given transformer is run at its rated voltage but reduced frequency, its core flux density is increased.

Description : The sequence components of current of a single-phase load connected to a 3-phase system are (A) equal positive and negative sequence components (B) equal positive, negative and zero sequence components (C) vector sum of sequence currents is zero (D) algebraic sum of sequence currents is zero

Last Answer : The sequence components of current of a single-phase load connected to a 3-phase system are equal positive, negative and zero sequence components

Description : The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be?

Last Answer : The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be 0.667 kW/phase/km.

Description : If voltage across a bulb rated 220 volt-100 watt drops by `2.5 %` of its value, the percentage of the rated value by which the power would decrease is

Last Answer : If voltage across a bulb rated 220 volt-100 watt drops by `2.5 %` of its value, the percentage of the rated value ... 20%` B. `2.5%` C. `5%` D. `10%`

Description : Rated power of a bulb at V voltage is P. Now, same voltage V is applied in all conditions mentioned in Column I. Match this Column I with Column II in

Last Answer : Rated power of a bulb at V voltage is P. Now, same voltage V is applied in all conditions ... Column II in which actual total power consumed is given.

Description : Why Voltage x Current do not equal rated power?

Last Answer : In an AC system power is equal to Voltage x Current x Powerfactor. Power factor is not constant and depends on the type of theload. Ideal value of the Power factor is 1, where as practicallyremains less then 1.

Description : An open shunt field in a direct current machine may be located by connecting the field circuit to an external power source, equal to the rated field voltage or less, and tested with a voltmeter from ... C. any suitable ground to any available line lead D. any field pole to each field coil lead

Last Answer : Answer: A

Description : The power factor of an AC generator operating singularly is determined by the __________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: A

Description : The power factor at which a paralleled AC generator operates is usually adjusted by the _____________. A. connected load B. prime mover speed C. field excitation D. generator's rated voltage

Last Answer : Answer: C

Description : Define the followings.   Insulation level, Rated short circuit breaking current, Making current, Short time rating, Impulse withstand voltage, Power frequency withstand voltage .

Last Answer : Insulation level - it is the combination of rated voltage, the corresponding impulse withstand voltage, which together characterize the insulation of the equipment as regards its ability to withstand ... wave of power frequency (50 Hz) which the insulation of equipment should withstand. 

Description : An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging case. If it is required to deliver rated current at rated voltage and 0.8 power-factor leading, the required excitation will be (A) less. (B) more. (C) more or less. (D) the same.

Last Answer : Ans: B Over excitation gives leading power factor and under excitation gives lagging p.f .

Description : An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging. For delivering rated current at rated voltage and 0.8 poWer—factor leading, the required excitation will be:  (A) less  (B) more (C) more or less (D) the same

Last Answer : An alternator is delivering rated current at rated voltage and 0.8 power -factor lagging. For delivering rated current at rated voltage and 0.8 power -factor leading, the required excitation will be: more 

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is (A) 1204 MW (B) 1504 MW (C) 2085 MW (D) 2606 MW

Last Answer : A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is 2085 MW

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

Last Answer : Vscos¢s-Vrcos¢r=IR

Description : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of   (a) 250A (b) 50 A (c) 150 A (d) 350 A 

Last Answer : A 10 kVA, 400 V/200 V single phase transformer with 10% impedance draws a steady short-circuit line current of 250A

Description : A three phase 50 Hz line consists of three conductors each of diameter 21 mm, The spacing between the conductors all follows:A - B = 3m, B - C = 5m, C - A = 3.6mIf the line operates at 132 k V, the reactive voltampere generatd by the line per km is?

Last Answer : A three phase 50 Hz line consists of three conductors each of diameter 21 mm, The spacing between the conductors all follows:A - B = 3m, B - C = 5m, C - A = 3.6mIf the line operates at 132 k V, the reactive voltampere generated by the line per km is  51.70 kVAr.

Description : A three phase overhead transmission line has its conductors horizontally spaced with spacing between adjacent conductors equal to 'd'. if now the conductors of the line are rearranged to form and the equilateral triangle of sides equal to 'd' then?

Last Answer : A three-phase overhead transmission line has its conductors horizontally spaced with spacing between adjacent conductors equal to 'd'. if now the conductors of the line are rearranged to form and an equilateral triangle of sides equal to 'd' then average capacitance and inductance will increase.

Description :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is?

Last Answer :  A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is 0.6 lagging.

Description : For equilateral spacing of conductors of an untrasposed 3-phase line, we have?

Last Answer : For equilateral spacing of conductors of an untrasposed 3-phase line, we have balanced receiving end voltage and communication interference.

Description : For a single phase overhead line having solid copper conductors of diameter 1 cm, spaced 60 cm between centers, the inductance in mH/km is?

Last Answer : For a single phase overhead line having solid copper conductors of diameter 1 cm, spaced 60 cm between centers, the inductance in mH/km is 0.05 + 0.2 ln (6010.5).

Description : The conductor of a 10 km long, single phase, two wire line are separated by a distance of 1.5 m. The diameter of each conductor is 1 cm, If the conductors are of copper, the inductance of the circuit is

Last Answer : The conductor of a 10 km long, single phase, two wire line are separated by a distance of 1.5 m. The diameter of each conductor is 1 cm, If the conductors are of copper, the inductance of the circuit is 23.8 mH.

Description : High Voltage DC (HVDC) transmission is mainly used for  (A) bulk power transmission over very long distances (C) inter-connecting two systems with same nominal frequency (C) eliminating reactive power requirement in the operation (D) minimizing harmonics at the converter stations

Last Answer : High Voltage DC (HVDC) transmission is mainly used for bulk power transmission over very long distances 

Description : If a voltage-controlled bus is treated as load bus, then which one of the following limits would be violated?   (a) Active power (b) Reactive power (c) Voltage (d) Phase angle 

Last Answer : If a voltage-controlled bus is treated as load bus, then which one of the following limits would be violated?   (a) Active power (b) Reactive power (c) Voltage (d) Phase angle 

Description : The function of the earth wire in an extra high voltage line is to?

Last Answer : The function of the earth wire in an extra high voltage line is to provide a shield to the phase conductors from direct lightning stroke.

Description : The non-uniform distribution of voltage across the units in a string of suspension type insulators is due to?

Last Answer : The non-uniform distribution of voltage across the units in a string of type insulators is due to the existence of stray capacitance between the metallic junctions of the units and the tower body.

Description : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill

Last Answer : A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill 2000 MW .

Description : With 100 % inductive shunt compensation, the voltage profile is flat for?

Last Answer : With 100 % inductive shunt compensation, the voltage profile is flat for zero loading of line.

Description : For certain geometry and operating voltage of the uncompensated transmission line, the ratio of power transfer capability to the surge impedance loading with an increase in length

Last Answer : For certain geometry and operating voltage of the uncompensated transmission line, the ratio of power transfer capability to the surge impedance loading with an increase in length decreases.

Description : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

Last Answer : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is 1.088 p.u.

Description : In a string of suspension insulators, the voltage distribution across the different units of a string could be made uniform by the use of a grading ring, because it?

Last Answer : In a string of suspension insulators, the voltage distribution across the different units of a string could be made uniform by the use of a grading ring, because it forms capacitances which help to cancel the charging current from link pins.

Description : To increase the visual critical voltage of cporona for an overhead line, one solid phase-conductor is replaced by a "bundle" of four smaller conductors per phase, having an aggregate cross- ... solid conductor is 40 mm, then the radius of each of the bundle conductors would be?

Last Answer : To increase the visual critical voltage of cporona for an overhead line, one solid phase-conductor is replaced by a "bundle" of four smaller conductors per phase, having an aggregate cross- ... conductor is 40 mm, then the radius of each of the bundle conductors would be 30 mm.