Answer :

In load flow analysis, the load connected at a bus is represented as constant real and reactive drawn from the bus.

Answer :

constant real and reactive powers drawn from bus

Related questions

Description : In a load flow analysis of a power system, the load connected at a bus is represented as a) Constant current drawn from the bus b) Constant impedance connected at the bus c) Voltage and frequency dependent sources at the boss d) Constant real and reactive power drawn from the bus

Last Answer : d) Constant real and reactive power drawn from the bus

Description : If the reference bus is changed in two load flow runs with same system data and power obtained for reference bus taken as specified P and Q in the latter run, the system losses  A) Will be ... C) As well as complex bus voltage will changed D) As well as complex bus voltage will be unchanged

Last Answer : If the reference bus is changed in two load flow runs with same system data and power obtained for reference bus taken as specified P and Q in the latter run, the system losses Will be unchanged but complex bus voltages will change

Description : In load flow Study, a PV bus is treated as a PQ bus when

Last Answer : Voltage at the bus becomes high 

Description : Generally in a power system network, the load is represented as a :  (A) Constant power in both load flow study and in stability study  (B) Constant power in load flow study and constant ... impedance in load flow study  (D) Constant impedance in both load flow study and in stability study

Last Answer : Generally in a power system network, the load is represented as a : Constant power in load flow study and constant impedance in stability study 

Description : If a voltage-controlled bus is treated as load bus, then which one of the following limits would be violated?   (a) Active power (b) Reactive power (c) Voltage (d) Phase angle 

Last Answer : If a voltage-controlled bus is treated as load bus, then which one of the following limits would be violated?   (a) Active power (b) Reactive power (c) Voltage (d) Phase angle 

Description : The sequence components of current of a single-phase load connected to a 3-phase system are (A) equal positive and negative sequence components (B) equal positive, negative and zero sequence components (C) vector sum of sequence currents is zero (D) algebraic sum of sequence currents is zero

Last Answer : The sequence components of current of a single-phase load connected to a 3-phase system are equal positive, negative and zero sequence components

Description : What is the need for slack bus in power flow analysis.

Last Answer : The slack/swing bus is needed to account for transmission line losses. In a power system the total power generated will be equal to sum of power consumed by loads and losses. In a power ... power are not specified for slack bus. They are estimated through the solution of load flow equations.

Description : Regarding an AC generator connected to the main electrical bus; as the electric load and power factor vary, a corresponding change is reflected in the generator armature reaction. These changes in ... . governor speed droop setting B. voltage regulator C. balance coil D. phase-balance relay

Last Answer : Answer: B

Description : A three phase, salient pole synchronous motor is connected to an infinite bus. It is operated at no load a normal excitation. The field excitation of the motor is first reduced to zero ... First increases and then decreases steeply (C) First decreases and then increases steeply (D) Remains constant

Last Answer : B

Description : A 3~phase synchronous motor, connected to infinite bus, is operating at no load at normal excitation. The field excitation of the motor is first decreased to zero and then increased in the ... 2) First decrease and then increase, (3) Increases continuously (4) First increase and then decreased

Last Answer : A 3~phase synchronous motor, connected to infinite bus, is operating at no load at normal excitation. The field excitation of the motor is first decreased to zero and then increased in the reverse direction. The armature current of the synchronous motor will: Increases continuously.

Last Answer : Generating capacity connected to the bus bars and ready to take load when switched on is known as spinning reserve.

Description : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the infinite bus voltage is 1 pu. The ... fault at the generator terminal is  (A) 53.5 (B) 60.2 (C) 70.8 (D) 79.6

Last Answer : A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the ... clearing angle, in degrees, for a three-phase dead short circuit fault at the generator terminal is 79.6

Description : A large AC generator, supplying power to an infinite bus, has a sudden short-circuit occurring at its terminals. Assuming the prime mover input and the voltage behind the transient reactance to remain constant immediately after the fault, acceleration of the generator rotor is

Last Answer : A large AC generator, supplying power to an infinite bus, has a sudden short-circuit occurring at its terminals. Assuming the prime mover input and the voltage behind the transient reactance ... , acceleration of the generator rotor is inversely proportional to the moment of inertia of the machine

Description : If a 5-bus test system contains 6 transmission lines and one transformer, how many non-zero elements are there in the system Y-bus ? (A) 25 (B) 12 (C) 11 (D) 19

Last Answer : If a 5-bus test system contains 6 transmission lines and one transformer, 19 non-zero elements are there in the system Y-bus.

Description : What technique is used to solve load flow problems using Z-bus (Bus impedance matrix)?

Last Answer : The formulation of load flow problem using Zbus employs Diakoptics techniques which is actually the piecewise solution of the power system problem by using tearing off technique.

Description : In a load flow problem solved by newton-Raphson method with polar coordinates, the size of the Jactobian is 100 × 100. If there are 20 PV buses in addition to PQ buses and a slack bus, the total number of buses in the system is_____

Last Answer : 61

Description : In load flow studies of a power system, a voltage control bus is specified by a) Real power and reactive power b) Reactive power and voltage magnitude c) Voltage and voltage phase angle d) Real power and voltage magnitude

Last Answer : d) Real power and voltage magnitude

Description : Which of the following matrix is used for load flow studies? a) null matrix b) Unit matrix c) Z bus matrix d) Y bus matrix

Last Answer : d) Y bus matrix

Description : For load flow studies, what are the quantities specified at load bus are. a) P and V b) P and Q c) V and δ d) δ and Q

Last Answer : b) P and Q

Description : A DC reactor is connected in series with each pole of a converter station in order to: A) prevent commutation failures in the inverter B) supply reactive power to the converter C) improve system stability D) increase the power transfer capability

Last Answer : A DC reactor is connected in series with each pole of a converter station in order to:  prevent commutation failures in the inverter

Description : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of ... the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

Last Answer : A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, ... line. The voltage of the alternator neutral with respect to ground during the fault is 642.2 V

Description : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are (A) 6 (B) 12 (C) 16 (D) 24

Last Answer : A hydraulic turbine having rated speed of 250 rpm is connected to a synchronous generator. In order to produce power at 50 Hz, the number of poles required in the generator are 24

Description : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 ... load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

Last Answer : A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/ ... MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be 36 

Description : The 'Equal area criterion' for the determination of transient stability of a synchronous machine connected to an infinite bus  (1) ignores line as well as synchronous machine resistance ... consideration the possibility of machine losing synchronism after it has survived during the first swing.

Last Answer : 1

Description : If non-linear loads are connected to the power system, then (A) displacement power factor is same as the total power factor (B) displacement power factor is not equal to the total power ... factor is due to harmonic currents (D) total power factor is due to fundamental component of current

Last Answer : If non-linear loads are connected to the power system, then displacement power factor is not equal to the total power factor

Description : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

Last Answer : A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is 3.63 Ω

Description : In 2003, the people preferring to travel by bus represented approximately what per cent of the people preferring to travel by own vehicles, buses and rails together in the year? a) 46 b) 54 c) 22 d) 14 e) 37

Last Answer : e) 37

Description : What is the need for load flow analysis.

Last Answer : The load flow study of a power system is essential to decide the best operation of existing system and for planning the future expansion of the system. It is also essential for designing a new power system.

Description : A power system has 100 buses including 10 generator buses. For the load flow analysis using Newton-Raphson method in polar coordinates, the size of the Jacobian is a) 189x189 b) 100x100 c) 90x90 d) 180x180

Last Answer : a) 189x189

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes (A) 0.85 (B) 1.00 (C) 0.80 lag (D) 0.90 lag

Last Answer : At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes  0.80 lag

Description : Load factor is the  (1) Ratio of maximum load on the station to sum of consumer's maximum load.  (2) Ratio of average demand to maximum demand.  (3) Factor used for increasing load.  (4) Reciprocal of (1).

Last Answer : Load factor is the Ratio of average demand to maximum demand. 

Description : A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

Last Answer : 0

Description : The load duration curve for unity load factor will be of  (1) Rectangular shape (2) Triangular shape (3) L -shape (4) I -shape

Last Answer : The load duration curve for unity load factor will be of Rectangular shape

Description : Load compensation in power systems is a process to :  (A) Maintain better voltage profile (B) Increase short circuit capacity of the system (C) Generate required harmonics for loads like arc furnaces (D) Compensate for the line reactance

Last Answer : Load compensation in power systems is a process to : Maintain better voltage profile

Description : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is  (1) 122.8 GWh (2) 198.55 GWh (3) 128.2 GWh (4) 188.82 GWh

Last Answer : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is 122.8 GWh

Description : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

Last Answer : A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is 1.088 p.u.

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Description : A generating st ation has a maximum, demand of 20 mW, load factor of 60%, a plant capacity factor of 50% and a plant Use factor of 72%. What is the reserve capacity of the plant, if the plant, while running as per schedule, were fully loaded?

Last Answer : 5 MW is the reserve capacity of the plant, if the plant, while running as per schedule, were fully loaded.

Description : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be

Last Answer : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be 720 MW.

Description : A power station supplies the peak load of 60 Mw, 40 MW and 70 MW to three localities. The annual load factor is 0.50 p.u. and the diversity factor of the load at the station is 1.55. The maximum demand on the station and average load respectively will be 

Last Answer : A power station supplies the peak load of 60 Mw, 40 MW and 70 MW to three localities. The annual load factor is 0.50 p.u. and the diversity factor of the load at the station is 1.55. The maximum demand on the station and average load respectively will be 103.2 MW, 51.61 .

Description : The yearly load duration curve of a power plant is a straight line. The maximum load is 750 MW and the minimum load is 600 Mw. The capacity of the plant is 900 MW. What is the capacity factor and utilization factor? 

Last Answer : 0.75, 0.83 is the capacity factor and utilization factor.

Description : A consumer consumes. 600 kWh per day at a load factor of 0.40. If the consumer increases the load factor of 0.70 without increasing the maximum demand, what is the consumption of energy in kWh?

Last Answer : A consumer consume. 600 kWh per day at a load factor of 0.40. If the coneumer increases the load factor of 0.70 without increasing the maximum demand, 1050 kWh is the consumption of energy in kWh.

Description : What is the maximum value of a load which consume 500 KWh per day at a load factor of 0.40, if the consumer increases the load factor of 0.50 without increasing the maximum demand?

Last Answer : 52.08 kW is the maximum value of a load which consume 500 KWh per day at a load factor of 0.40, if the consumer increases the load factor of 0.50 without increasing the maximum demand.

Description : An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= _____. 

Last Answer : An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= 0.6 . 

Description : A load is connected to the secondary of the transformer illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps

Last Answer : Answer: C

Description : A load is connected to the secondary of the device illustrated and the current through the load is 10 amps. If the step-up ratio is 10 to 1 and the input voltage is 110 VAC, what will be the current flow through the primary? EL-0055 A. 1 amp B. 10 amps C. 100 amps D. 1000 amps

Last Answer : Answer: C

Description : For a fixed value of complex power flow in a transmission line having a sending and voltage V, the real power loss will be proportional to  A) V B) v2 C) 1/V2 D)1/V

Last Answer : For a fixed value of complex power flow in a transmission line having a sending and voltage V, the real power loss will be proportional to 1/V2

Description : The power flow problem mathematical model for a linear transmission network (A) is non-linear (B) is linear (C) considers time variation of generation (D) does not consider tap-changing transformers

Last Answer : The power flow problem mathematical model for a linear transmission network is non-linear