What could be a possible cause for sudden foaming in a cooling tower?

1 Answer

Answer :

Assuming that no other changes have been made, especially to the water treatment chemicals, the  most common outcome to this mystery is a leaking heat exchanger.
Begin a systematic check of all of the heat exchangers that use the cooling tower water and inspect  them thoroughly for leaks. Even small amounts of some chemicals can cause big foaming problems in  the tower. In addition, not all of these components will set off a conductivity alarm

Related questions

Description : Austempering of steel requires it to be heated to 875°C followed by sudden cooling to 250-525°C, thereby changing austenite to (A) Sorbite (B) Bainite (C) Martensite (D) Troostite

Last Answer : (B) Bainite

Description : The suitable evaporator for concentration of foaming liquids is a __________ evaporator. (A) Long tube (B) Short tube (C) Vacuum (D) Falling film

Last Answer : (A) Long tube

Description : Plate efficiency (A) Is a function of the mass transfer between liquid and vapour (B) Increases due to foaming (C) Increases due to liquid entrainment (D) Increases due to weeping and dumping of liquid

Last Answer : (A) Is a function of the mass transfer between liquid and vapour

Description : Plate efficiency in a distillation column is reduced due to the __________ of liquid. (A) Entrainment (B) Foaming (C) Weeping & dumping (D) All (A), (B) & (C)

Last Answer : (D) All (A), (B) & (C)

Description : In case of evaporators, liquid entrainment results primarily due to (A) High vacuum in the evaporator (B) High evaporation rate (C) Foaming of the solution (D) High heat transfer rate

Last Answer : (C) Foaming of the solution

Description : Agitated film evaporator is suitable for concentrating __________ liquids. (A) Foaming (B) Viscous (C) Very thin (D) Corrosive

Last Answer : (B) Viscous

Description : Foaming and priming in boiler operation can be reduced by reduction in __________ in feed water. (A) Turbidity (B) Color (Hazen) (C) Total solids (D) All (A), (B) & (C)

Last Answer : (D) All (A), (B) & (C)

Description : Deaeration of high pressure boiler feed water is done to reduce (A) Foaming from boilers (B) Its dissolved oxygen content (C) Its silica content (D) Caustic embrittlement

Last Answer : (B) Its dissolved oxygen content

Description : Presence of nitrogen and phosphorous in waste water discharged into lakes and ponds causes (A) Foaming (B) Odour nuisances (C) Undesirable plant growth (D) Turbidity

Last Answer : (C) Undesirable plant growth

Description : The equipment frequently used for adiabatic humidification-cooling operation with recirculating liquid is (A) Natural draft cooling tower (B) Induced draft cooling tower (C) Spray chamber (D) None of these

Last Answer : (C) Spray chamber

Description : When the temperature and humidity of air is low, we usually use __________ draft cooling tower. (A) Natural (B) Forced (C) Induced (D) None of these

Last Answer : (A) Natural

Description : Make up water is supplied during cooling tower operation to compensate for water losses due to (A) Evaporation (B) Blowdown (C) Entrainment (D) All (A), (B) & (C)

Last Answer : (D) All (A), (B) & (C)

Description : Heat load in a cooling tower (A) Means the amount of heat thrown away (KCal/hr.) by the cooling tower (B) Is equal to the number of kg, of water circulated times the cooling range (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : The term "cooling range" in a cooling tower refers to the difference in the temperature of (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air (B) Hot water entering the ... air (C) Hot water entering the tower and the cooled water leaving the tower (D) None of these

Last Answer : (C) Hot water entering the tower and the cooled water leaving the tower

Description : A packed tower compared to a plate tower for a particular mass transfer operation (A) Incurs smaller pressure drop (B) Allows installation of cooling coils (C) Is less costly when built in large sizes/diameters (D) Is more suitable, if suspended solids are present in fluid stream

Last Answer : (A) Incurs smaller pressure drop

Description : Make up water is required in a cooling tower to replace the water lost by (A) Evaporation (B) Drift (C) Blowdown and leakage (D) All (A), (B) and (C)

Last Answer : (D) All (A), (B) and (C)

Description : In a forced draft cooling tower, water is cooled from 95 to 80°F by exposure to air with a wet bulb temperature of 70°F. In this case, the (A) Range is 15°F (B) Approach is 10°F (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : Can a cooling tower cool water below the wet bulb temperature of inlet air? (A) Yes (B) No (C) Yes; but height of cooling tower will be prohibitively high (D) Yes; but the air flow rate should be excessively high

Last Answer : (B) No

Description : Pick out the wrong statement. (A) Different solids have different equilibrium moisture curves (B) Total condenser or reboiler is considered equivalent to one theoretical plate in McCabe-Thiele method of ... (D) Even a forced draft cooling tower cannot cool water below the wet bulb temperature

Last Answer : (C) Heat removal load on cooler remains constant, even with increase of the reflux ratio in a distillation column

Description : Drift in a cooling tower is (A) The water entrained by the circulating air (B) Dependent on the water lost by evaporation (C) Desirable (D) All (A), (B) & (C)

Last Answer : (A) The water entrained by the circulating air

Description : __________ number indicates the ratio of the rates of the heat and mass transfer incase of a cooling tower. (A) Sherwood (B) Stanton (C) Lewis (D) Peclet

Last Answer : (C) Lewis

Description : The term "approach" in a cooling tower refers to the difference in the temperature of the (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air (B ... (C) Hot water entering and the cooled water leaving the cooling tower (D) None of these

Last Answer : (A) Cold water leaving the tower and the wet bulb temperature of the surrounding air

Description : Which of the following employs an accessory known as 'drift eliminator'? (A) Multiple effect evaporator (B) Mechanical draft cooling tower (C) Rotary dryer (D) Rotating disc contacto

Last Answer : (B) Mechanical draft cooling tower

Description : Use of natural draft cooling tower is practised, when the air has low (A) Humidity (B) Temperature (C) Both 'a' & 'b' (D) Neither 'a' nor 'b'

Last Answer : (C) Both 'a' & 'b

Description : The most efficient cooling tower out of the following is (A) Induced draft (B) Forced draft (C) Natural draft (D) Atmospheric

Last Answer : (A) Induced draft

Description : The cooling effect in a cooling tower cannot be increased by (A) Increasing the air velocity over the wet surfaces (B) Reducing the humidity of entering air (C) Lowering the barometric pressure (D) None of these

Last Answer : (D) None of these

Description : The temperature of water cooled in cooling tower is always __________ temperature of entering air. (A) More than the wet bulb (B) Less than the wet bulb (C) Equal to the wet bulb (D) Equal to the dry bulb

Last Answer : (A) More than the wet bulb

Description : Pick out the wrong statement pertaining to the cooling towers. (A) In case of induced draft cooling tower, the fan is placed at the top of the tower (B) Effectiveness of ... Effectiveness of a mechanical draft cooling tower is reduced with increase in air wet-bulb temperature

Last Answer : (D) Effectiveness of a mechanical draft cooling tower is reduced with increase in air wet-bulb temperature

Description : Blowdown in a cooling tower (A) Means discarding a small fraction of circulating water to prevent and limit the concentration of salt and impurities (B) Increases the scale forming tendencies of water (C) Is undesirable (D) All (A), (B) & (C)

Last Answer : (A) Means discarding a small fraction of circulating water to prevent and limit the concentration of salt and impurities

Description : A natural draft cooling tower is filled with wooden grids, which covers about __________ percent of the tower height. (A) 10-15 (B) 30-40 (C) 70-80 (D) 90-100

Last Answer : (A) 10-15

Description : The cooling effect in a cooling tower can be speeded up by (A) Increasing the air velocity and area of exposed wet surface (B) Reducing the barometric pressure (C) Reducing the humidity of the air (D) All (A), (B) and (C)

Last Answer : (D) All (A), (B) and (C)

Description : In a cooling tower, water becomes cool by (A) Loosing sensible heat (B) Heat transfer to surroundings (C) Vaporisation due to heat loss to air (D) Loosing latent heat

Last Answer : (A) Loosing sensible heat

Description : Noise produced by cooling fans (employed in air cooled heat exchangers or cooling tower) is mainly caused due to the turbulence created by blade passage through air. It can be reduced by use of a slower fan (A) With greater ... (B) Of increased diameter (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : 'Flare tower' used in industry is meant for (A) Venting off (after burning) the excess inflammable/toxic gases at high pressure (B) Absorbing the pollutant gases from the furnace exhaust (C) Cooling of furnace exhaust gases (D) None of these

Last Answer : (A) Venting off (after burning) the excess inflammable/toxic gases at high pressure

Description : The minimum temperature to which the water can be cooled in a cooling tower is the __________ temperature of air. (A) Ambient (B) Dry bulb (C) Dew point (D) Wet bulb

Last Answer : C) Dew point

Description : In a forced draft cooling tower, water is cooled from 95 to 80°F by exposure to air with a wet bulb temperature of 70°F. In this case, the (A) Range is 15°F (B) Approach is 10°F (C) Both (A) & (B) (D) Neither (A) nor (B)

Last Answer : (C) Both (A) & (B)

Description : Minimum temperature upto which water can be theoretically cooled down in the cooling tower by evaporative cooling is equal to the __________ temperature of air. (A) Wet bulb (B) Dry bulb (C) Saturation (D) Dew point

Last Answer : Option A

Description : What factors should be compared when evaluating cooling tower bids?

Last Answer : Examining the following factors should allow for a reasonable evaluation of cooling towers: 1) Purchased cost 2) Installed cost 3) Fan energy consumption 4) Pump energy consumption 5) ... maintenance costs 8) Worker safety requirements 9) Environmental safety 10) Expected service life

Description : IS there a rule of thumb to estimate the footprint of a cooling tower during design phase?

Last Answer : Over the years, this one has seemed to stand the test of time: Every million Btu/h of tower capacity will require approximately 1000 ft2 of cooling tower basin area.

Description : When specifying a cooling tower, should I look up historic wet bulb temperatures for my area or should I take measurements?

Last Answer : If this is a new installation, look up historical wet bulb temperatures for area and be sure to report them to the cooling tower manufacturer as ambient wet bulb temperatures . The ... the tower entrance. The entering wet bulb temperature always higher than the ambient wet bulb temperature.

Description : What is the definition of “good” cooling tower water?

Last Answer : Generally speaking, cooling tower water should have a pH between 6 and 8, a chloride content no more than 750 ppm, a sulfate content (SO4) below 1200 ppm, and a sodium bicarbonate (NaHCO3) ... intermittently with a free residual not to exceed 1 ppm and this should be maintained for short periods.

Description : How much water is lost through a commercial cooling tower system with a throughput of about 600 GPM?

Last Answer : This question depends on many factors. It sounds like the tower is small. A rule of thumb suggests that the tower will see an evaporation loss of about 0.1% of the circulation flowrate for each ... and blow down. Blow down is simply a purge of tower water to prohibit the buildup of solids.

Description : In a refrigerator what produces the cooling? (1) The ice which deposits on the freezer (2) The sudden expansion of a compressed gas (3) The evaporation of a volatile liquid (4) None of these

Last Answer : (4) None of these Explanation: Basically, refrigeration system consists of devices that compress and expand refrigerant gas. When refrigerant gas is compressed it expels heat and when it is suddenly ... inside of the fridge is cooled to a temperature below the ambient temperature of the room.

Description : In a refrigerator what produces the cooling ? (1) The ice which deposits on the freezer (2) The sudden expansion of a compressed gas (3) The evaporation of a volatile liquid (4) None of these

Last Answer : None of these

Description : What is the mysterious foaming agent used in the liquid to operate a foam party machine?

Last Answer : The liquid is a solution of soap in water.

Description : Workability improved by adding (A) Air-entraining agent (B) Foaming agent (C) Oily-agent (D) All the above

Last Answer : (D) All the abov

Description : Foaming is caused by the formation of ___________ a) Acids b) Alcohols c) Oils and alkalis d) Ketones

Last Answer : c) Oils and alkalis

Description : The phenomenon during which the boiler material becomes brittle due to accumulation of caustic substances is known as ___________ a) Foaming b) Priming c) Corrosion d) Caustic embrittlement

Last Answer : d) Caustic embrittlement

Description : The propulsion of water into steam drum by extremely rapid, almost explosive boiling of water at the heating surface is called ___________ a) Foaming b) Priming c) Corrosion d) Caustic embrittlement

Last Answer : b) Priming

Description : Which of the following is not a result of the excess of impurity in boiler-feed. a) Scale and sludge formation b) Decomposition c) Corrosion, priming and foaming d) Caustic embrittlement

Last Answer : b) Decomposition