A generating station has a maximum demand of 30 MW, a load factor of 60% and a plant capacity factor of 50%. The reserve capacity of the plant is 

 (a) 5 MW (b) 4 MW (c) 6 MW (d) 10 MW 

1 Answer

Answer :

A generating station has a maximum demand of 30 MW, a load factor of 60% and a plant capacity factor of 50%. The reserve capacity of the plant is 6 MW

Related questions

Description : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be

Last Answer : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be 720 MW.

Description : A generating st ation has a maximum, demand of 20 mW, load factor of 60%, a plant capacity factor of 50% and a plant Use factor of 72%. What is the reserve capacity of the plant, if the plant, while running as per schedule, were fully loaded?

Last Answer : 5 MW is the reserve capacity of the plant, if the plant, while running as per schedule, were fully loaded.

Description : A generating station has a maximum demand of 500 MW. The annual load factor is 50 percent. The energy generated per annum will be: A) 2.19 x 106 MWhr B) 600 MWhr C) 250 MWhr D) 7.50 x 106 MWhr

Last Answer : A generating station has a maximum demand of 500 MW. The annual load factor is 50 percent. The energy generated per annum will be: 2.19 x 106 MWhr 

Description : In a power generating station the Demand Factor and Load Factor are 0.5 and 0.2, respectively. If the connected load is 400 MW, the average demand is (A) 40 MW (B) 100 MW (C) 140 MW (D) 280 MW

Last Answer : In a power generating station the Demand Factor and Load Factor are 0.5 and 0.2, respectively. If the connected load is 400 MW, the average demand is 40 MW

Description : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is  (1) 122.8 GWh (2) 198.55 GWh (3) 128.2 GWh (4) 188.82 GWh

Last Answer : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is 122.8 GWh

Description : n a chemical factory where dyes are made, wet cake at 30 OC consisting of 60% moisture  is put in a dryer to obtain an output having only 5% moisture, at atmospheric pressure. In  each batch about 120 ... dryer and the dryer efficiency  is 80%. Latent heat of steam at 4 kg/cm2 is 520 kcal/kg.

Last Answer : Given that   Qty of material dried per batch - 120 Kgs  Moisture at inlet - 60% a. The quantity of moisture removed per batch.  Water quantity in a wet batch - 120 x 0.6 = 72 Kgs.  Quantity of bone dry ... - 48/0.95 = 50.5 Kgs.  Equivalent water in a dry batch - 50.5 - 48 = 2.5 Kgs.

Description : A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

Last Answer : B

Description : At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes (A) 0.85 (B) 1.00 (C) 0.80 lag (D) 0.90 lag

Last Answer : At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes  0.80 lag

Description : A power station supplies the peak load of 60 Mw, 40 MW and 70 MW to three localities. The annual load factor is 0.50 p.u. and the diversity factor of the load at the station is 1.55. The maximum demand on the station and average load respectively will be 

Last Answer : A power station supplies the peak load of 60 Mw, 40 MW and 70 MW to three localities. The annual load factor is 0.50 p.u. and the diversity factor of the load at the station is 1.55. The maximum demand on the station and average load respectively will be 103.2 MW, 51.61 .

Description : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per ... 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

Last Answer : A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained ... load to increase the line-to-line voltage at the load terminals to 11 kV is -10.1 MVAR

Description : What will be the efficiency when the transformer operates at unity power factor and 60% of full load 

Last Answer : What will be the efficiency when the transformer operates at unity power factor and 60% of full load 96.5%

Description : Define the following terms:- Reliability, Maximum demand, Reserve-generating capacity, Availability (operational).

Last Answer : Reliability: It is the capacity of the power system to serve all power demands without failure over long periods. Maximum Demand: It is maximum load demand required in a power station during a given ... percentage of the time a unit is available to produce power whether needed by the system or not.

Description : The maximum demand of consumer is 2 kW and his daily energy consumption is 20 units. Its Load Factor is (1) 10.15% (2) 41.6 % (3) 50 % (4) 60% 

Last Answer : Total maximum demand of energy in a day = 2kw*24= 48 units Consumer consumption is 20 units . Load factor = (number of units utilizing)/(total max. demand)      = 20/48 = 41.6%

Description : Tarapur (INDIA) atomic power station (A) Has two boiling water reactors of American design (B) Has an installed capacity of 400 MW (C) Is the first power reactor in India, which became critical in 1969 (D) All (A), (B) and (C)

Last Answer : (D) All (A), (B) and (C)

Description : Which of the following is true about the Accounts Receivable Lag and its implications on demand? a. If you offer no credit, demand falls to about 60% of normal. b. At 30 days, demand is 90%. c. At 45 days, demand is 95%. d. At 60 days, demand is 98.5%. e. At 90 days, demand is 100%.

Last Answer : d. At 60 days, demand is 98.5%.

Description : The ratio of current year‘s production to the reference year‘s production is called as a) Demand factor b) Production factor c) Utilisation factor d) Load factor

Last Answer : Production factor 

Description : ECE Board Exam March 1996 The method of generating FM used by broadcasting station is A. direct B. all of these C. indirect D. insertion

Last Answer : C. indirect

Description : Which of the following quantities has the GREATEST influence on the overall efficiency of a conventional (Rankine cycle) electric generating station burning fossil fuels? w) steam temperature at the steam turbine ... pressure at the steam turbine inlet z) pounds of ash and sulfur per pound of fuel 

Last Answer : ANSWER: W -- STEAM TEMPERATURE AT THE STEAM TURBINE INLET 

Description : For a 210 MW, turbo-alternator in a thermal power plant, the possible specifications of rotor diameter, stator core length, and number of poles, respectively, are (A) 4.4 m, 1.2 m, 12 (B) 1.2 m, 4.4 m, 2 (C) 4.4 m, 1.2 m, 24 (D) 1.2 m, 4.4 m, 8

Last Answer : For a 210 MW, turbo-alternator in a thermal power plant, the possible specifications of rotor diameter, stator core length, and number of poles, respectively, are 1.2 m, 4.4 m, 2

Description : Two synchronous generators operating in parallel supply a common load of 2.5 MW. The frequency-power characteristics have a common slope of 1 MW/Hz and the no-load frequencies of the generators are 51.5 Hz and 51.0 Hz, ... system frequency is (A) 50 Hz (B) 51 Hz (C) 51.25 Hz (D) 51.5 Hz

Last Answer : Two synchronous generators operating in parallel supply a common load of 2.5 MW. The frequency-power characteristics have a common slope of 1 MW/Hz and the no-load frequencies of the generators are 51.5 Hz and 51.0 Hz, respectively. Then the system frequency is 50 Hz

Description : Define the following: Average demand, Maximum demand, Demand factor, Load factor.

Last Answer : Average Demand: the average power requirement during some specified period of time of considerable duration is called the average demand of installation. Maximum Demand: The maximum demand of an installation ... Load Factor: It is defined as the ratio of the average power to the maximum demand.

Description : The connected load of a consumer is 2 kW and his maximum demand is 1.5 kW. The load factor of the consumer is (a) 0.375 (b) 0.75 (c) 1.33 (d) None of these  

Last Answer : a

Description : The marketing function's main concern is with (a) producing goods or providing services ; (b) procuring materials, supplies, and equipment (c) building and maintaining a positive image ; (d) generating the demand for the organization's products or services

Last Answer :  (d) generating the demand for the organization's products or services 

Description : Among which locomotive steam engines have the highest efficiency? a) 1 MW b) 2 MW c) 30 MW d) 660 MW

Last Answer : d) 660 MW

Description : Multiple inlet system of air cooling of turbo-alternators can be used for machines of rating upto (a) 10 MW (b) 30 MW (c) 60 MW (d) 150 MW

Last Answer : (c) 60 MW

Description : Higher plant efficiency up to______ over the entire load range. a. 30%-50% b. 20%-40% c. 60%-90% d. 50%-80%

Last Answer : a. 30%-50%

Description : When can a corporation or association incorporated under the Philippine laws and with foreign investors be granted radio station license? A. When 60% of the capital is owned by Filipino citizens B. ... of the board is a Filipino D. When the president of the corporation/association is a Filipino

Last Answer : A. When 60% of the capital is owned by Filipino citizens

Description : Rankine cycle efficiency in a good steam power station may be in the range between........ a.15% - 20% b.35% - 40% c.50% - 60% d.90% - 95%

Last Answer : b.35% - 40%

Last Answer : Generating capacity connected to the bus bars and ready to take load when switched on is known as spinning reserve.

Description : The output power of a filter is 100 mW, when the signal frequency is 6 kHz. When the frequency is increased to 25 kHz, the output power falls to 50 mW. What is the dB change in power ? (a) -3 dB (b) -5 dB (c) -7 dB (d) -2 dB

Last Answer : The output power of a filter is 100 mW, when the signal frequency is 6 kHz. When the frequency is increased to 25 kHz, the output power falls to 50 mW. What is the dB change in power ?  -3 dB 

Description : Calculate the power loss, if power generated by two plants are P1=50 MW and P2 =40 MW and the loss coefficients are B11=0.001, B22=0.0025 and B12=-0.0005.  (A) 4.5 MW (B) 5.5 MW (C) 6.5 MW (D) 8.5 MW

Last Answer : A

Description : Bhabha Atomic Research Centre (BARC) located at Trombay (near Bombay, INDIA) has (A) Five operating research reactors (namely Apsara, Cirus Zerelina, Purnima and Dhurva) (B) A 420 MW nuclear power plant (C) A very large capacity (100 tons/yr) heavy water plant (D) All (A), (B) and (C)

Last Answer : (A) Five operating research reactors (namely Apsara, Cirus Zerelina, Purnima and Dhurva)

Description : For steam power plant having capacity 600 MW capacity a cooling tower is required to set up with condenser. Suggest the type of condenser and cooling tower with justification. 

Last Answer : For Steam power plant having Capacity 600 MW the requirement of condenser and cooling tower is as follow. 1) Condenser:- Given Capacity is medium to low capacity for this we can use Jet Condenser ... and efficiency of tower is high  -Temperature of water coming out from tower can be controlled.

Last Answer : Load factor of a power station is generally less than unity.

Last Answer : Load factor of a power station is defined as average load/maximum demand.

Description : Name three conventional ways of generating power. Of these three, which one contributes maximum generation in India.

Last Answer : Coal, Gas and Hydro are the examples of conventional method of generating power. Coal contributes maximum generation in India. India generates 219.81 Gw by thermal power plant (coal).

Description : The graph shown in the illustration represents the speed droop curves of two equal capacity alternators about to be paralleled. When paralleled, the greater portion of the total load above 60% for each unit will be picked up ... unit 'A' B. by unit 'B' C. equally by each unit D. none of the above

Last Answer : Answer: A

Description : Which of the following is usually not the generating voltage : -  a) 6.6 EV b) 11 KV c) 12.5 KV d) 13.2 KV

Last Answer : Which of the following is usually not the generating voltage : -   12.5 KV

Description : Volumetric efficiency of air compressor is of the order of A. 20% to 30 % B. 40% to 50% C. 60% to 70% D. 70% to 90%

Last Answer : ANSWER : D

Description : In trickling filter, B.O.D. is reduced to A. 30 to 40% B. 40 to 60% C. 60 to 80% D. 80 to 90%

Last Answer : ANS: C

Description : A liquid mixture contains 30% o-xylene, 60% p-xylene and 10%. m￾xylene (all percentages in w/w). Which of the following statements would be true in respect of this mixture? (A) The mixture exhibits ... : o-xylene 30, p-xylene 60 and m-xyoene 10 (D) The mixture contain optical isomers

Last Answer : (A) The mixture exhibits an azeotrope at 101.3 kPa

Description : or efficient performance of a blast furnace, the extent of reduction of Wustite (FeO) should be (A) 100% indirect reduction (B) 100% direct reduction (C) 50-60% indirect reduction (D) 30-40% indirect reduction

Last Answer : (C) 50-60% indirect reduction

Description : or efficient performance of a blast furnace, the extent of reduction of Wustite (FeO) should be (A) 100% indirect reduction (B) 100% direct reduction (C) 50-60% indirect reduction (D) 30-40% indirect reduction

Last Answer : (C) 50-60% indirect reduction

Description : A person, by selling an article at half of the list price incurs a loss of 20%. Find the profit percentage if he sells at the list price? A. 25% B. 60% C. 5% D. 30 %

Last Answer : Answer – B (60 %) Explanation – 0.50 MP = 0.8 CP (since 20% loss) So, MP = 160CP ⇒ 60% gain.

Description : Brass is an alloy of copper and zinc having the relative percentage (A) 60-70% Cu and 30-40% Zn (B) 50-60% Cu and 40-50% Zn (C) 40-50 % Cu and 60-50% Zn (D) 30-40 % Cu and 60-70% Zn

Last Answer : A) 60-70% Cu and 30-40% Zn

Description : The majority of the U.S. electricity generating plant use what thermodynamic cycle?

Last Answer : ANSWER: RANKINE

Last Answer : 1. Connected Load: It is the sum of load of all equipment's connected to supply system which are in use or not in use of each consumer. OR   The sum of connected load of all consumers ... is the maximum load which a consumer uses at a particular time period out of his total connected load. 

Description : How were you affected by the MW/NE Blackout of Aug. 14, 2003?

Last Answer : in the dark ,sorry lol