The connected load of a consumer is 2 kW and his maximum demand is 1.5 kW. The load factor of the consumer is (a) 0.375 (b) 0.75 (c) 1.33 (d) None of these  

3 Answers

Answer :

5

Answer :

D

Answer :

a

Related questions

Description : The maximum demand of consumer is 2 kW and his daily energy consumption is 20 units. Its Load Factor is (1) 10.15% (2) 41.6 % (3) 50 % (4) 60% 

Last Answer : Total maximum demand of energy in a day = 2kw*24= 48 units Consumer consumption is 20 units . Load factor = (number of units utilizing)/(total max. demand)      = 20/48 = 41.6%

Description : A building intended to be used for commercial purpose will be required to follow Energy conservation building code under Energy Conservation Act, 2001 provided its a) connected load is 120 kW and above b) ... and above c) connected load is100 kW and above or contract demand is 120 kVA and above

Last Answer : c) connected load is100 kW and above or contract demand is 120 kVA and above

Description : If 3000 kW power is to be transmitted over a distance of 30 km, the desirable transmission voltage will be.  (A) 11 kV (B) 33 kV (C) 66 kV (D) 132 kV

Last Answer : By

Description : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

Last Answer : A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is 80 MJ

Description : An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= _____. 

Last Answer : An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= 0.6 . 

Description : A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is  (A) 1.66 Nm (B) 95.50 Nm (C) 99.47 Nm (D) 624.73 Nm

Last Answer : A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is 99.47 Nm

Description : Which of the following statements is correct concerning the motor performance curves and data table shown in the illustration? EL-0006 A. The motor RPM at full load is 1737 RPM. B. The motor draws 12.62 kw ... If the motor was developing 10 HP its power factor would be 0.92. D. All of the above.

Last Answer : Answer: D

Description : A three-phase alternator is operating at 450 volts, 250 amps at 0.6 power factor. If the power factor increases to 0.8, the kw load potential will increase by _____________. A. 38.525 kw B. 116.91 kw C. 155.88 kw D. 194.85 kw

Last Answer : Answer: A

Description : [23] Transformers are rated in KVA instead of KW because A. load power factor is often not known B. KVA is fixed whereas KW depends on load power factor C. Total transformer loss depends on volt ampere D. It has become customary

Last Answer : C. Total transformer loss depends on volt ampere

Description : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

Last Answer : A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Last Answer : 1. Connected Load: It is the sum of load of all equipment's connected to supply system which are in use or not in use of each consumer. OR   The sum of connected load of all consumers ... is the maximum load which a consumer uses at a particular time period out of his total connected load. 

Description : Why are shunt reactors connected at the receiving end of long transmission line system: (1) To increase the terminal voltage (2) To compensate voltage rise caused by capacitive charging at light load (3) To improve power factor (4) None of these

Last Answer : Why are shunt reactors connected at the receiving end of long transmission line system: To compensate voltage rise caused by capacitive charging at light load

Last Answer : Galvanized iron wire is zinc coated steel wire it prevents rusting it have longer life.

Description : how the booster is connected in transmission line ?

Last Answer : Booster is connected in series with transmission line

Description : Define the following: Average demand, Maximum demand, Demand factor, Load factor.

Last Answer : Average Demand: the average power requirement during some specified period of time of considerable duration is called the average demand of installation. Maximum Demand: The maximum demand of an installation ... Load Factor: It is defined as the ratio of the average power to the maximum demand.

Description : A generating station has a maximum demand of 500 MW. The annual load factor is 50 percent. The energy generated per annum will be: A) 2.19 x 106 MWhr B) 600 MWhr C) 250 MWhr D) 7.50 x 106 MWhr

Last Answer : A generating station has a maximum demand of 500 MW. The annual load factor is 50 percent. The energy generated per annum will be: 2.19 x 106 MWhr 

Description : A generating station has a maximum demand of 30 MW, a load factor of 60% and a plant capacity factor of 50%. The reserve capacity of the plant is   (a) 5 MW (b) 4 MW (c) 6 MW (d) 10 MW 

Last Answer : A generating station has a maximum demand of 30 MW, a load factor of 60% and a plant capacity factor of 50%. The reserve capacity of the plant is 6 MW

Description : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is  (1) 122.8 GWh (2) 198.55 GWh (3) 128.2 GWh (4) 188.82 GWh

Last Answer : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is 122.8 GWh

Description : A generating st ation has a maximum, demand of 20 mW, load factor of 60%, a plant capacity factor of 50% and a plant Use factor of 72%. What is the reserve capacity of the plant, if the plant, while running as per schedule, were fully loaded?

Last Answer : 5 MW is the reserve capacity of the plant, if the plant, while running as per schedule, were fully loaded.

Description : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be

Last Answer : A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be 720 MW.

Description : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

Last Answer : A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is 0.707

Description : The three non -inductive loads of 5 kW, 3 kW and 2 kW are connected in a star network between R, Y and B phases and neutral. The line voltage is 400 V. The current in the neutral wire is nearly (a) 11 A (b) 14 A (c) 17 A (d) 21 A

Last Answer : The three non -inductive loads of 5 kW, 3 kW and 2 kW are connected in a star network between R, Y and B phases and neutral. The line voltage is 400 V. The current in the neutral wire is nearly 11 A

Description : The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor ... Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

Last Answer : The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is 45.0 A 

Description : A turbogenerator has a rated output of 1200 KW at 60 Hertz, with a no load frequency of 61.5 Hertz. What is its speed droop? A. 1.03% B. 1.50% C. 2.44% D. 2.50%

Last Answer : Answer: D

Description : A meter whose constant is 600 revolutions/kWh makes 5 revolutions in 20 seconds. Calculate the load in kW. (1) 0.5 kW (2) 1 kW (3) 1.5 kW (4) 2 kW  

Last Answer : 1.5 kW 

Description : An overhead transmission line has a span of 260 m. The weight of the conductor is 0.68 kg/m. The maximum allowable tension in the line is 1550 kg. Maximum sag of the line should be (a) 5.8 m (b) 4.6 m (c) 2.7 m (d) 3.7 m 

Last Answer : Maximum sag = (l^2)/8c So c = T/W c = 1550/0.68 c= 2279.4 Now Maximum sag = (260^2)/8(2279.4) = 3.7 (d)

Description : A 40 kW engine has a mechanical efficiency of 80 %. If the frictional power is assumed to be constant with load, what is the approximate value of the mechanical efficiency at 50 % of the rated load? (a) 45% (b) 55 % (c) 65% (d) 75%

Last Answer : Ans :c

Description : A vessel is equipped with two ship's service generators. Generator #1 is rated at 900 kw and generator #2 is rated at 600 kw. During parallel operation, with a hotel load of 1,000 kw, what should be the kw load on generator #2? A. 100 kw B. 400 kw C. 500 kw D. 600 kw

Last Answer : Answer: B

Description : A circuit breaker for a 300 KW alternator is rated at 470 amperes of full continuous load. The amount of overcurrent allowed is 125%. Which of the following conditions will trip the breaker? A. ... 10 minutes. C. Momentary starting load of 550 amperes. D. Sustained current flow of 590 amperes.

Last Answer : Answer: D

Description : The KW load is evenly distributed between two alternators just placed in parallel by adjusting _____________. A. a balance coil B. the governor settings C. the field excitation D. a rheostat

Last Answer : Answer: B

Description : Which is a function of the voltage regulators used with AC generators? A. To cut out generators when they are no longer required. B. To cut in additional generators automatically as ... between generators operating in parallel. D. To divide reactive current between generators operating in parallel.

Last Answer : Answer: D

Description : A 3-phase 50HZ SCIM takes a power input of 30 KW at its full load speed of 1440 rpm. Total stator losses are 1 KW. The slip and rotor ohmic losses at full load are a) 0.02, 600 W b) 0.04, 580 W c) 0.04, 1160 W d) 0.04, 1200 W

Last Answer : Ans: 0.04, 1160 W

Description : The formula for tension difference or effective pull, required to transmit the load at.... (a) (Tt-Ts)=1000(kw/V) (b) Tt/Ts=c^ke (c) (Tt-Ts)= 1000(Hp/V) (d) None of the above

Last Answer : (a) (Tt-Ts)=1000(kw/V)

Description : A 50 KVA transformer has iron loss 2 kW on full load. Calculate its iron loss at 75% of full load.

Last Answer : Iron loss is dependent on voltage and independent of load. Hence iron loss at 75% of Load = Iron loss at full load = 2 kW

Description : In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is :

Last Answer : In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is : 0.075

Description : One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

Last Answer : 100

Description : A 150 kW electric motor has an efficiency of 92 %, when it operates at full load. Calculate the losses in the machine.  (A) 92 kW (B) 150 kW (C) 163 kW (D) 13 kW 

Last Answer : efficiency  -output /input * 100 150/0.92----------163(input) losses-----(163--150)  ---------13kw.

Description : A consumer consumes. 600 kWh per day at a load factor of 0.40. If the consumer increases the load factor of 0.70 without increasing the maximum demand, what is the consumption of energy in kWh?

Last Answer : A consumer consume. 600 kWh per day at a load factor of 0.40. If the coneumer increases the load factor of 0.70 without increasing the maximum demand, 1050 kWh is the consumption of energy in kWh.

Description : A three-phase alternator operates at 450 volts with a power factor of 0.8. If the ammeter indicates 250 amperes, what should be the KW meter reading? A. 90.00 KW B. 127.27 KW C. 155.70 KW D. 194.85 KW

Last Answer : Answer: C

Description : A three-phase alternator is developing 300 amps, with a 0.8 power factor, at 450 volts. The true indicated power on the kilowatt meter, located on the main switchboard, will be ____________. A. 133 kw B. 155 kw C. 187 kw D. 212 kw

Last Answer : Answer: C

Description : A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter would then read ____________. A. 181.4 KW B. 186.8 KW C. 194.2 KW D. 201.4 KW

Last Answer : Answer: B

Description : A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter reading would increase by ___ A. 17.8 KW B. 23.2 KW C. 30.6 KW D. 37.8 KW

Last Answer : Answer: B

Description : A three phase induction motor is drawing 16 Ampere at 440 Volts. If the operating power factor of the motor is 0.90 and the motor efficiency is 92%, then the mechanical shaft power output of the motor is a) 12.04 kW b) 10.09 kW c) 10.97 kW d) None of the above

Last Answer : b) 10.09 kW

Description : Which of the following statements are true? i) reactive current is necessary to build up the flux for the magnetic field of inductive devices ii) some portion of reactive current is converted into work iii) the cosine of angle ... called power factor a) i & iv b) ii & iii c) i & iii d) iii & iv

Last Answer : a) i & iv

Description : In a power generating station the Demand Factor and Load Factor are 0.5 and 0.2, respectively. If the connected load is 400 MW, the average demand is (A) 40 MW (B) 100 MW (C) 140 MW (D) 280 MW

Last Answer : In a power generating station the Demand Factor and Load Factor are 0.5 and 0.2, respectively. If the connected load is 400 MW, the average demand is 40 MW

Description : The maximum power suggested by KBP on 919-1312 AM broadcast station in Metro Manila is A. 10 kW B. 20 kW C. 15 kW D. 5 kW

Last Answer : B. 20 kW

Description : The ratio of current year‘s production to the reference year‘s production is called as a) Demand factor b) Production factor c) Utilisation factor d) Load factor

Last Answer : Production factor 

Description : Which of the following meters uses a shunt connected in series with the load, but parallel with the meter movement? A. voltmeter B. power factor meter C. wattmeter D. ammeter

Last Answer : Answer: D

Description : Which of the listed meters uses a shunt connected in series with the load, but parallel with the meter movement? A. Voltmeter B. Power factor meter C. Ammeter D. Wattmeter

Last Answer : Answer: C